用电负荷计算书001
- 格式:docx
- 大小:25.80 KB
- 文档页数:2
用电负荷计算书《民用建筑电气设计规范》JGJ 16-2008:参考手册:《工业与民用配电设计手册》第三版:AP1:负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ)Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 207.36无功功率Qc: 128.51视在功率Sc: 243.95有功同时系数kp:0.60无功同时系数kq:0.60计算电流Ic: 370.65总功率因数: 0.85【计算过程(不计入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=207.36(kW)Qc = kq * ∑(Kd * Pn * tgΦ)=128.51(kvar)Sc = √(Pc * Pc + Qc * Qc)=243.95(kVA)Ic = Sc / (√3 * Ur)=370.65(A)AP2.AP3:负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ) Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 66.72无功功率Qc: 67.40视在功率Sc: 94.84有功同时系数kp:0.80无功同时系数kq:0.80计算电流Ic: 144.09总功率因数: 0.70【计算过程(不计入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=66.72(kW)Qc = kq * ∑(Kd * Pn * tgΦ) =67.40(kvar)Sc = √(Pc * Pc + Qc * Qc) =94.84(kVA)Ic = Sc / (√3 * Ur)=144.09(A)JXS:负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ) Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 104.00无功功率Qc: 64.46视在功率Sc: 122.36有功同时系数kp:0.75无功同时系数kq:0.75计算电流Ic: 185.90总功率因数: 0.85【计算过程(不计入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=104.00(kW)Qc = kq * ∑(Kd * Pn * tgΦ) =64.46(kvar)Sc = √(Pc * Pc + Qc * Qc) =122.36(kVA)Ic = Sc / (√3 * Ur)=185.90(A)。
用电负荷计算书工程名:《民用建筑电气设计规范》JGJ 16-2008:参考手册:《工业与民用配电设计手册》第三版:用电负荷统计表:变压器S1的回路:北教学楼、综合楼、南教学楼、实验楼、室外、消防设备、中心机房用电S1负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ)Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 333.45无功功率Qc: 158.77视在功率Sc: 369.32有功同时系数kp:0.90无功同时系数kq:0.97计算电流Ic: 561.12总功率因数: 0.83有功负荷系数α:0.80无功负荷系数β:0.80补偿前功率因数COSφ1: 0.83补偿后功率因数COSφ2: 0.92计算补偿容量QC1: 66.87(kvar)实际补偿容量QC2: (kvar)【计算过程(加入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=333.45(kW)Qc = kq * ∑(Kd * Pn * tgΦ) - QC1 =158.77(kvar)Sc = √(Pc * Pc + Qc * Qc)=369.32(kVA)Ic = Sc / (√3 * Ur)=561.12(A)【补偿容量】:COSφ1 =1/√[1+(β* Qc/α* Pc)2] =0.83COSφ2=0.92QC1=α* Pc*(tgφ1- tgφ2)=66.87【变压器容量】:变压器系列:SCB11 10系列负荷率:70额定容量:630(kW)负荷计算表变压器S1的回路:S1负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ)Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 395.44无功功率Qc: 192.20视在功率Sc: 439.68有功同时系数kp:0.80无功同时系数kq:0.80计算电流Ic: 668.02总功率因数: 0.85有功负荷系数α:0.85无功负荷系数β:0.80补偿前功率因数COSφ1: 0.86补偿后功率因数COSφ2: 0.92计算补偿容量QC1: 52.87(kvar)实际补偿容量QC2: (kvar)【计算过程(加入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=395.44(kW)Qc = kq * ∑(Kd * Pn * tgΦ) - QC1 =192.20(kvar)Sc = √(Pc * Pc + Qc * Qc)=439.68(kVA)Ic = Sc / (√3 * Ur)=668.02(A)【补偿容量】:COSφ1 =1/√[1+(β* Qc/α* Pc)2] =0.86COSφ2=0.92QC1=α* Pc*(tgφ1- tgφ2)=52.87【变压器容量】:变压器系列:S11 10系列负荷率:80额定容量:630(kVA)。
配电箱负荷计算书目的针对某甲公司XX工厂电缆配套工程中的配电箱负荷进行计算,确定配电箱数量及型号规格,确保电力供应可靠、安全、稳定。
计算方法按照《规划设计电气工程基础规范》(GB 50052-2019)中标准规定,配电箱的负荷计算应按照以下步骤进行:1.确定用电设备的视在功率对于每个用电设备,根据其使用说明书或者电气参数确定其视在功率,单位为千伏安(kVA)。
如下表所示:设备名称视在功率(kVA)设备110设备220设备352.计算负载总视在功率将所有用电设备的视在功率相加,得到负载总视在功率,记做S。
S = 10 + 20 + 5 = 35 kVA3.计算负载总有功功率根据功率因数和负载总视在功率计算负载总有功功率,记做P。
选择功率因数为0.8,有功功率因数修正系数Kp = 1,无功功率因数修正系数Kq = 1。
P = Kp * S= 1 * 35 = 35 kW4.选取配电箱型号和数量根据计算结果,选取适当的配电箱型号和数量,保证其额定电流大于等于所需有功功率和所需无功功率对应的电流值,同时符合现场使用和规范标准要求。
根据工厂的实际情况,选取品牌为ABB,型号为MA-E250G和MA-E125G两款配电箱。
MA-E250G型号的额定电流为250A,最大容纳40个开关-c灭弧室插件或20个断路器;MA-E125G型号的额定电流为125A,最大容纳10个开关-c灭弧室插件或5个断路器。
根据以上信息,选择MA-E250G型号1个,MA-E125G型号2个。
结论针对某甲公司XX工厂电缆配套工程中的配电箱负荷进行计算,确定需要1个MA-E250G型号配电箱和2个MA-E125G型号配电箱,可以满足所需负载的安全、稳定、可靠供电要求。
参考文献•《规划设计电气工程基础规范》(GB 50052-2019)备注本文档是计算书格式范例,具体计算必须依据实际情况进行,仅供参考。
1、确定用电负荷:(1)、插入式振动器K x = 0.3 Cos y = 0.7 tg y = 1.02P js= 0.3X18 = 5.4 kWQ js= P js X tg y=5.4x1.02 = 5.508 kvar(2)、电焊机:(取暂载率J1=0.60 功率因素COS W =0.87)P电焊=si* J EC OS W X 10二20X7060X0.87X4=28.9KWK x = 0.65 Cos y = 0.7 tg y = 1.02P js= 0.65X28.9 = 18.785kWQ js= P js X tg y=18.785x1.02 = 19.161 kvar(3)、木工圆锯机K x = 0.65 Cos y = 0.7 tg y = 1.02P js = 0.65X1.5 = 0.975 kWQ js= P js X tg y=0.975x1.02 = 0.995 kvar(4)、钢筋弯曲机K x = 0.65 Cos y = 0.7 tg y = 1.02P js = 0.65X5.5 = 3.575 kWQ js = P js X tg y=3.575X1.02 = 3.647 kvar(5)、钢筋套丝机K x = 0.65 Cos y = 0.7 tg y = 1.02P js = 0.65X8 = 5.2 kWQ js = P.s X tg^=2.6X1.02 = 5.304 kvar (6)、钢筋切断机K x = 0.65 Cos y = 0.7 tg y = 1.02P.s = 0.65X15 = 9.75 kWQ js = P.s X tg y=9.75X1.02 = 9.945 kvar(7)、钢筋调直机K x = 0.65 Cos y = 0.7 tgy = 1.02P js = 0.65X15 =9.75 kWQ js = P js X tg y=9.75x1.02 = 9.945 kvar (8)、卤化灯K x = 1.0 Cos y = 0.7 tg y = 1.02P js = 1.0X20=20 kWQ js = P js X tg y=20x1.02 = 20.4 kvar (9)、三相污水泵K x = 0.65 Cos y = 0.7 tg y = 1.02P js= 0.65X3 =1.95 kWQ js = P js X tg y=1.95x1.02 =1.989 kvar (10)、其他K x= 0.65 Cos y = 0.7 tg y = 1.02P js= 0.65X10 =6.5kWQ js = P js X tg y=6.5x1.02 =6.63 kvar(11)总的计算负荷计算,总配电箱同期系数取Kx = 0.9总的有功功率:Pjs = KxX Z Pjs =0.9x(5.4+18.785+0.975+3.575+5.2+9.75+9.75+20+1.95+6.5)=73.70 kW总的无功功率Q js二K x X Z Q.s =0.9x(5.508+19.161+0.995+3.647+5.304+9.945+9.945+20.4+1.989+6.63) = 75.08 kvar总的视在功率S js= ( P js2+Q js2 )1/2 = (73.702+75.082)1/2 = 105.208KVA总的计算电流计算I js= S j s/(1.732XU e)= 105.208/(1.732X0.38) = 159.85A2、第一项目部1#总配电线路上导线截面及分配箱、开关箱内电气设备选择:2.1用电设备到开关箱及分配箱内电器设备选择在选择前应对照平面图和系统图先由用电设备至开关箱计算,再由开关箱至分配箱计算,选择导线及开关设备。
1现场用电负荷计算1.1设备投入情况及总用电负荷计算注:上表中功率单位未注的均为KW总电力负荷计算式:P=1.05~1.10(K1∑P1/Cosφ+ K2∑P2+ K3∑P3+ K4∑P4)式中:P—总的电力负荷(总需容量,KVA)P1—电动机额定功率(KW)P2—电焊机额定功率(KVA)P3—室外照明(KW)P4—办公区用电(Kw)COSφ—电动机平均功率因数(一般取为0.8)K 1、K2、K3、K4、K5—需要系数。
( K1:0.5-0.7,电动机为3-10台时取0.7,11-30台取0.6,30台以上取0.5;K2:0.5-0.6,电焊机为3-10台时取0.6,10台以上取0.5;K3:1.0;K4:1.0)结合计算结果,现场总负荷为1747.6KVA,现场需提供至少1800KVA的变压器,方可满足现场施工用电。
根据计算结果,在结构阶段现场总用电量最大为1747.6KVA,考虑到地下室完工后降水井大部分将会停用,故从临近地铁和泵站借用的一台630KVA、400KVA 和500KVA的变压器容量能满足施工要求。
根据变压器的位置,为了合理使用变压器的容量,也根据我方施工组织的施工要求,采取变压器分区、分段向现场供电。
1.2各回路分布说明及用电负荷计算根据现场平面布置图,3台箱变位于现场东南角和西南角,根据现场的场地情况和负荷分布,同时考虑到实用性和经济性的需要,我方决定由630KVA箱变1为A区施工及生活区供电,由400KVA箱变2为C和D区施工供电,500KVA箱变3为B和D区施工供电,根据现场的平面布置及建筑物的分布情况,我方从变压器1引出4个一级回路做为总配电室(分别为1#、2#、3#),由3个总配电室引出11条二级回路,分别为生活办公区和施工区的5台塔机及3套钢筋加工设备和4栋塔楼供电,从箱式变压器2引出2个一级回路做为总配电室(分别为4#、5#),由2个总配电室引出9条二级回路分别为住宅区的3台塔机和2栋塔楼及相应的钢筋加工设备供电,从变压器3引出4个一级回路做为总配电室(分别为6#、7#、8#、9#),由4个总配电室引出20条二级回路,分别为施工区的6台塔机及3套钢筋加工设备及5栋塔楼供电,。
用电负荷计算书
工程名:
计算者:
计算时间:
参考手册:《民用建筑电气设计计算及示例》12SDX101-2
《民用建筑电气设计规范》JGJ 16-2008:
《工业与民用配电设计手册》第四版等
【计算公式(不加入补偿容量)】:
负荷容量:若不全为三相且不存在单相且进线相序为三相且∑(单相、L1相、L2相、L3相的负荷) <= 0.15 * ∑(三相的负荷),则计算负荷= ∑(三相的负荷) +∑(单相、L1相、L2相、L3相的负荷),否则计算负荷= ∑(三相的负荷) + max(∑(L1相的负荷),∑(L2相的负荷),∑(L3相的负荷)) * 3。
有功功率Pc = K∑p * ∑(Kd * Pn)
无功功率Qc = k∑q * ∑(Kd * Pn * tgΦ)
视在功率Sc = √(Pc * Pc + Qc * Qc
计算电流Ic = Sc / (√3 * Ur)
补偿前功率因数COSφ1 = 1/√{1+[(βav* Qc)/(αav* Pc)]²}
【已知参数】:
进线相序 : 三相
有功同时系数k∑p:1.00
无功同时系数k∑q:1.00
有功负荷系数αav:0.75
无功负荷系数βav:0.80
负荷:
【计算过程(不加入补偿容量)】:
计算负荷: 71.00
有功功率Pc = K∑p * ∑(Kd * Pn)
= 56.80
无功功率Qc = k∑q * ∑(Kd * Pn * tgΦ)
= 42.60
视在功率Sc = √(Pc * Pc + Qc * Qc
= 71.00
计算电流Ic = Sc / (√3 * Ur)
= 107.87
补偿前功率因数COSφ1 = 1/√{1+[(βav* Qc)/(αav* Pc)]²} = 0.78。