对《保护用电流互感器暂态特性技术要求》国家标准的浅识
- 格式:pdf
- 大小:1.71 MB
- 文档页数:11
1、TPS级:低漏磁电流互感器:Low leakage flux current transformer for which performance is defined by the secondary excitation characteristics and turns ratio error limits.there is no limit for remanent flus.释义:二次绕组有低漏磁特性,且限定匝数比误差的电流互感器。
对剩磁不限制。
特点:铁心不带气隙。
不限制剩磁。
低漏磁。
严格的匝数比。
用途:当电流互感器严重饱和时切断一次电流,二次电流将随磁通由饱和状态快速降低到剩磁水平,即二次电流残余电流小,因此适用于对保护复归时间要求严格的断路器失灵保护的电流起动元件;另一方面,此类电流互感器励磁阻较高,汲出电流小,适用于电流互感器并接的场合。
2、TPX级:准确限值规定为在指定的暂态工作循环中的峰值瞬时误差,无剩磁限值。
Accuracy limit defined by peak instantaneous error () during specified transient duty cycle.there is no limit for remanent flux.释义:准确限值规定了为在指定的瞬态周期内的峰值瞬时误差。
对剩磁不限制。
特点:铁心不带气隙。
不限制剩磁。
用途:基本同TPS级。
3、TPY,是暂态型电流互感器,Accuracy limit defined by peak instantaneous error () during specified transient duty cycle.remanent flux does not exceed 10% of the saturation flux.释义:准确限值规定了为在指定的瞬态周期内的峰值瞬时误差。
对剩磁有限制,要求剩磁不超过饱和量的10%。
电流互感器一.基本概念和基本原理1.基本概念互感器:一种变压器,供测量仪器、仪表、继电器和其它类似电器用。
电流互感器:一种互感器,在正常使用条件下其二次电流与一次电流实质上成正比,而其相位差在联结方法正确时接近于零的互感器。
电流互感器主要分为两大类:测量级互感器和保护级互感器。
电力线路中的电流各不相同,通过电流互感器一、二次绕组匝数比的配置,可以将不同的线路电流变换成较小的标准电流值,一般是5A或1A,这样可以减小仪表和继电器的尺寸,简化其规格,有利于这些设备的小型化、标准化,所以说电流互感器的主要作用是:a. 传递信息供给测量仪表、仪器或继电保护、控制装置;b. 使测量、保护和控制装置与高电压相隔离;c.有利于测量仪器、仪表和保护、控制装置的小型化、标准化。
测量级互感器:专门用于测量电流和电能的电流互感器。
如:3、1、0.5、0.2、0.1、0.5S、0.2S、0.1S、0.3、0.6、1.2、1M、2M保护级互感器:专门用于继电保护和自动控制的电流互感器。
如:5P、10P、C类互感器(如C800)、5PR、10PR、PX、X、PS、PL 、TPX、TPY、TPS铁心开气隙的目的:控制剩磁铁心需开气隙的电流互感器:5PR、10PR、TPY执行标准:国标:GB 1208-2006 电流互感器GB 16847-1997 保护用电流互感器暂态特性技术要求国际标准:IEC 60044-1、IEC 60044-6其它国家标准:IEEE/C57.13、CAN3-C13、AS 60044.1、BS等600/1A的CT二次匝数为600÷1=6003.套管型电流互感器的基本参数及基本常识3.1 额定电流比:例1:300-400-600/5A,即表示此互感器有三个变比,其额定一次电流分别为300、400及600A,额定二次电流为5A,二次匝数应分别为60、80及120匝。
S1-S2:300/5、60匝S1-S3:400/5、80匝S1-S4:600/5、120匝例2:600/5MR、C800 (美国标准IEEE Std C57.13-1993)MR:多变比C类互感器:相当于10P20800:二次端电压(V)C800:相当于10P20、200V A出线标记――X2-X3 50/5 10匝X1-X2 100/5 20匝X1-X3 150/5 30匝X4-X5 200/5 40匝X3-X4 250/5 50匝X2-X4 300/5 60匝X1-X4 400/5 80匝X3-X5 450/5 90匝X2-X5 500/5 100匝X1-X5 600/5 120匝20匝10匝50匝40匝X1X2X3X4X53.2 准确级要求3.2.1保护级互感器:3.2.1.1标准准确限值系数ALF:5、10、15、20、30、40等。
电流互感器的相关知识点总结
什么是电流互感器?
电流互感器(Current Transformer,简称CT)是一种用于测量大电流的电力测量仪器,它能够将高电流变换成低电流,从而方便进行测量、保护和控制。
电流互感器的工作原理
电流互感器基于电磁感应原理工作。
当被测电流通过互感器的一侧主绕组时,通过变压器的作用,产生在另一侧副绕组上一个与被测电流成比例的次级电流。
电流互感器的特点
•具有较高的准确度和稳定性。
•能够将高电流变换成标准化的次级电流。
•具备绝缘和防护功能,确保安全操作。
•适用于交流电力系统的测量、保护和控制。
电流互感器的应用领域
电流互感器广泛应用于以下领域:
•电力系统中的电能计量和监测。
•电力系统中的继电保护和自动化装置。
•电力系统中的故障录波和分析。
•工业控制系统中的电流测量和监控。
常见问题
以下是一些关于电流互感器的常见问题:
•问题1:什么是变比误差?
变比误差是指实际变比与理论变比之间的差异。
它会导致测量误差的产生。
•问题2:电流互感器的标定方法有哪些?
常见的标定方法包括比较式标定法、电阻箱标定法和标准电流比差法等。
•问题3:如何确保电流互感器的安全使用?
应严格按照操作手册进行安装、维护和测试。
同时,注意保持良好的绝缘和防护措施,以确保安全使用。
保护用电流互感器的误差限值
在一定的过电流下,误差应在一定限值内,以保证继电保护装置正确和可靠动作,这是对保护用电流互感器的基本要求之一。
根据电力系统要求切除短路故障和继电保护动作时间的快慢.对保护用电流互感器的误差条件提出了不同的要求。
(1)如继电保护动作时间相对较长,电流互感器在稳态下的误差就能满足使用要求,这种电流互感器称为一般保护用电流互感器。
(2)若继电保护动作时间短,则需对电流互感器提出保证稳态误差的要求,这种电流互感器称为稳态保护用电流互感器。
(3)电流互感器在过电压情况下工作时,由于电流波形畸变,不能用电流误差和角误差来规定其误差特性,需用复合误差来规定其误差特性。
保护用电流互感器的误差性能指标是:
1)规定其复合误差的大小。
2)保证复合误差不超过规定值时的一次电流倍数,这个倍数称为准确限值系数。
(4)准确限值系数是额定准确限值一次电流与额定一次电流之比,而额定准确限值一次电流是互感器能满足复合误差要求的最大一次电流值。
用于继电保护的电流互感器,为了满足继电器灵敏度和选择性的要求,应按照电流互感器的10%倍数曲线进行校验。
(5)保护用电流互感器的准确级标称方法,是以该准确级的额定准确限值一次电流下所规定的最大允许复合误差百分数标称的,并在其后标上字母“P”以表示保护用。
GB 1208规定保护用电流互感器的标准准确级有5P和10P两种(也有用“D”表示的)。
它们在额定频率和额定负荷情况下的误差限值如表所示。
表保护用电流互感器的误差限值。
---------------------------------------------------------------范文最新推荐------------------------------------------------------ 电流互感器的特性及其对保护的影响摘要电流互感器是电力系统中较为重要的高压电气设备之一,它被广泛地应用于继电保护、电流测量和电力系统分析应用中,其一次侧与一次系统串联,二次侧接测量仪表与或者继电保护,为测量仪表、继电保护等二次电气设备获取一次回路的信息。
电流互感器在正常运行时,它能够准确的传变一次系统的电流量。
但由于电流互感器主要是由非线性的电磁元件组成的,当故障发生时,非线性元件会使互感器的铁心饱和,导致电流互感器的二次侧电流无法真实的反映一次侧电流的变化情况。
本主要对电流互感器的稳态和暂态特性进行分析,并通过建模仿真来观察饱和电流互感器的特性及其对电流速断和电流差动保护的影响,最后提出几种降低电流互感器饱和影响的措施。
12330关键词电流互感器稳态暂态保护建模仿真影响措施1/ 20毕业设计说明书(论文)外文摘要TitleThe Characteristics of Current Tansfomers and its impact on ProtectionsAbstractCurrent transformers are one kind of important high voltage electrical equipment in power system,they are widely used in relay protection、current measurement and analysis applications of power system. Their primary sides are connected with primary systems, and their second sides are connected with measuring instruments or protection equipments, obtaining the primary information for those second electrical equipments,such as measuring instruments and relay protections.When current transformer work in normal operation, they can transmit the current of the primary system accurately. Since a current transformer is mainly composed of nonlinear electromagnetic elements, when a fault occurs, the nonlinear elements may make the transformer core---------------------------------------------------------------范文最新推荐------------------------------------------------------saturated, and then result in that the current of the second side cannot reflect the real current changes of the primary side of the current transformer. This paper primary analysises the steady state and transient characteristics of a current transformer,then observes the characteristics of a saturation current transformer and its influence on instantaneous overcurrent protection and current comparison protection by moldeling and simulating,finally recommend some methods to reduce the influence of its saturation.4.1.3电流速断保护的动作仿真284.2电流互感器对差动保护的影响314.2.1电流差动保护整定计算324.2.2电流互感器对电流差动保护的影响343/ 204.2.3电流差动保护的动作仿真374.3电流互感器对其他保护的影响424.4降低电流互感器饱和对继电保护影响的措施43 结论44致谢45参考文献461绪论近年来,随着电力技术的飞速发展,电力系统各电气设备的额定电压和额定电流都得到大大的提高。
不同原理的保护用电流互感器暂态特性对比分析
杨忠州;冯建华;谢婷婷;王露;郝海鹏;姚梦珏;王博;张媛;郭晗
【期刊名称】《高压电器》
【年(卷),期】2018(54)10
【摘要】在现代智能电网的智能化变电站中,电子式电流互感器逐渐取代传统的电磁式电流互感器,得到越来越广泛的应用。
暂态特性是保护用电流互感器的重要性能,文中针对不同原理的电流互感器的暂态特性进行了相关的试验研究。
首先概述了电磁式电流互感器的暂态保护TPY级和电子式电流互感器暂态保护TPE级的定义及试验要求,然后通过实际的试验,对不同原理的多台电流互感器的暂态特性进行比对,得到多组比对试验数据。
试验结果表明:电子式和传统电磁式的电流互感器都能达到标准要求的暂态性能指标,对用户的选型及生产厂家的设计均有指导意义。
【总页数】8页(P234-240)
【关键词】电磁式电流互感器;电子式电流互感器;暂态误差;比对试验
【作者】杨忠州;冯建华;谢婷婷;王露;郝海鹏;姚梦珏;王博;张媛;郭晗
【作者单位】西安高压电器研究院有限责任公司;西电宝鸡电气有限公司
【正文语种】中文
【中图分类】TM452
【相关文献】
1.电压互感器和电流互感器暂态特性对距离保护算法的影响
2.保护用小功率电流互感器暂态特性分析和改进
3.直流偏磁和剩磁同时作用下保护用电流互感器的暂态特性研究
4.TP级保护用电流互感器的暂态特性分析
因版权原因,仅展示原文概要,查看原文内容请购买。
标准电流互感器电流互感器是一种用来测量电流的电气设备,广泛应用于电力系统中。
标准电流互感器是一种特殊类型的电流互感器,其具有一定的标准化要求,以确保其性能和精度符合国际标准。
本文将对标准电流互感器的工作原理、结构特点以及应用领域进行介绍。
首先,标准电流互感器的工作原理是基于电磁感应原理。
当被测电流通过互感器的一侧线圈时,会在另一侧线圈中感应出相应的电流信号。
通过测量这个感应电流信号的大小,就可以准确地得到被测电流的数值。
标准电流互感器通常采用铁芯和线圈的结构,以提高其灵敏度和准确性。
其次,标准电流互感器具有一些特点。
首先,它具有一定的额定电流范围,能够适应不同电力系统中的电流测量需求。
其次,标准电流互感器的精度高,能够满足精密测量的要求。
此外,它还具有良好的线性特性和频率响应特性,能够在不同频率下保持稳定的测量性能。
另外,标准电流互感器还具有较好的抗干扰能力,能够在复杂电磁环境下稳定工作。
标准电流互感器在电力系统中有着广泛的应用。
首先,它常用于电能计量,通过测量电流大小来计算电能的使用量,为电力系统的管理和运行提供重要的数据支持。
其次,标准电流互感器还常用于电力负荷监测和故障检测,能够及时发现电力系统中的异常情况,并采取相应的措施进行处理。
此外,它还常用于电力设备的保护和控制,能够实现对电力设备的精确控制和保护。
总的来说,标准电流互感器是电力系统中不可或缺的重要设备,其准确性和稳定性对于电力系统的安全运行具有重要意义。
随着电力系统的不断发展和升级,标准电流互感器的技术水平也在不断提高,将为电力系统的智能化和高效化发展提供更加可靠的技术支持。
希望本文能够为读者对标准电流互感器有一个清晰的认识,同时也希望能够对电力系统工程技术人员提供一定的参考价值。
标准电流互感器作为电力系统中的重要组成部分,其稳定可靠的性能将为电力系统的安全运行和高效管理提供重要的保障。
电流互感器的工作原理及特性
一、工作原理
电流互感器的工作原理与一般变压器相像。
如图中,当一次侧流过电流I1时,在铁芯中产生交变磁通,此磁通穿过二次绕组,产生电动势,在二次回路中产生电流I2。
电流互感器的一、二次额定电流之比,称为额定电流比,用Ki表示。
依据磁动势平衡原理,忽视励磁电流时,可以认为:
Ki=IN1/IN2≈N2/N1=KN
式中,IN1、IN2为一、二次绕组的额定电流;N1、N2为一、二次绕组匝数;KN为匝数比。
可见,由测量出的二次电流I2乘以额定电流比Ki即可测得一次实际电流I1。
二、特性
与一般变压器相比,电流互感器有如下特点:
1、一次电流的大小打算于一次负载电流,与二次电流大小无关。
2、正常运行时,由于二次绕组的负载是测量仪表和继电器的电流线圈,阻抗很小,二次绕组近似于短路工作状态。
3、运行中的电流互感器二次回路不允许开路,否则会在开路的两端产生高电压危及人生平安,或使电流互感器发热损坏。
所以,二次侧不允许安装熔断器,且二次连接导线应采纳截面积不小于2.5平方毫米的铜芯截面。
运行中当需要检修、校验二次仪表时,必需先将电流互感器的二次绕组或回路短接,再进行拆卸操作。
低压电流互感器技术要求
1.低压电流互感器是一种重要的电力测量仪器,其技术要求包括以下几个方面:
2. 测量精度:低压电流互感器的测量精度应符合国家标准和行业标准的要求,通常为0.5级或0.2级。
3. 频率特性:低压电流互感器的频率特性应符合国家标准和行业标准的要求,通常为50Hz或60Hz。
4. 线性度:低压电流互感器的线性度应符合国家标准和行业标准的要求,通常为0.2%。
5. 绝缘性能:低压电流互感器的绝缘性能应符合国家标准和行业标准的要求,通常为4000V。
6. 温度特性:低压电流互感器的温度特性应符合国家标准和行业标准的要求,通常为-25℃至+55℃之间。
7. 防护等级:低压电流互感器的防护等级应符合国家标准和行业标准的要求,通常为IP20或IP67。
8. 外观质量:低压电流互感器的外观质量应符合国家标准和行业标准的要求,通常应具有良好的外观和结构,表面应无明显划痕和凹陷。
9. 安全性能:低压电流互感器的安全性能应符合国家标准和行业标准的要求,通常应符合IEC60044-1标准和GB1208标准的相关规定。
10. 使用寿命:低压电流互感器的使用寿命应符合国家标准和行
业标准的要求,通常为10年以上。
11. 维护保养:低压电流互感器的维护保养应符合国家标准和行业标准的要求,通常应按照产品说明书和相关规定进行维护保养。