隔离式安全栅原理 ..............................................................1外形尺寸 .....................................................................1隔离栅的优点 .................................................................2隔离栅选型 ...................................................................3EKZ9718-111 一进一出,开关量输入式隔离栅 ...................................4EKZ9718-121 一进二出,开关量输入式隔离栅 ....................................4EKZ9718-221 二进二出,开关量输入式隔离栅 ....................................4EKZ9718-112 一进一出,开关量输入式隔离栅 ....................................6EKZ9718-122 一进二出,开关量输入式隔离栅 ....................................6EKZ9718-222 二进二出,开关量输入式隔离栅 ....................................6EKZ9720 一进一出,开关量输出式隔离栅 .........................................8EKZ9721-11 一进一出,开关量输出式隔离栅 .....................................9EKZ9721-21 二进二出,开关量输出式隔离栅 .....................................9EKZ9721 一进一出,开关量输出式隔离栅 ....................................10EKZ9721-22 二进二出,开关量输出式隔离栅 ....................................10EKZ9721-13 一进一出,开关量输出式隔离栅 ....................................11EKZ9721-23 二进二出,开关量输出式隔离栅 ....................................11EKZ9741/ EKZ9741R 一进一出,输入检测端隔离栅 ..............................12EKZ9743/ EKZ9743R 一进二出,输入检测端隔离栅 ..............................12EKZ9744/EKZ9744R 二进二出,输入检测端隔离栅 ...............................13EKZ9745/9745R 一进一出,输入检测端隔离栅(带智能通讯) .......................14EKZ9745P 一进一出,输入检测端隔离栅 ........................................15EKZ9742 一进一出,输出操作端隔离栅 ..........................................16EKZ9749 二进二出,输出操作端隔离栅 ..........................................16EKZ9740 二进二出,检测/操作一体化隔离栅 .....................................17EKZ9755 一进一出,输出操作端隔离栅/输入检测端隔离栅 ........................18EKZ9756 二进二出,输出操作端隔离栅/输入检测端隔离栅 ........................18EKZ9771 一进一出,智能型热电偶输入式隔离栅 .................................20EKZ9771A 毫伏信号、热电偶输入式隔离栅 ......................................21EKZ9772 热电阻输入式隔离栅 .................................................22EKZ9772A 热电阻输入式隔离栅 ..............................................23EKZ9773 智能型热电阻输入式隔离栅 ............................................24EKZ9716 频率量输入隔离栅 ....................................................25EKZ9717 频率量输入隔离栅 ....................................................26隔离栅防爆合格证 . (27)目录EKZ9000系列 隔离式安全栅1EKZ9000系列 隔离式安全栅隔离式安全栅原理带有电流隔离功能的安全栅,被称为隔离式安全栅,简称隔离栅。
SWP7035-Ex隔离式安全栅使用说明书注意事项❝请核对产品外包装,产品标签的型号、规格是否与订货合同一致;❝隔离式安全栅安装、使用前应仔细阅读本说明书,或有疑问,请与本公司技术支持部联系;❝隔离式安全栅应安装在安全场所,安装后,务必再次核对产品型号、端子接线及电源和信号极性是否正确;❝仪表供电24V直流电源,严禁使用220V 交流电源;❝严禁私自拆装仪表,防止仪表失效或发生❝故障。
概述SWP7035-Ex模拟量输入式隔离栅,给危险区的二线制4/20mA变送器提供一个完全浮空的直流电源,变送器产生的4/20mA电流信号,从危险侧隔离传送到安全侧,去驱动安全区负载。
主要技术参数❝通路数:单入双出,完全浮空❝变送器所处场合:0区、1区、2区;ⅡA、ⅡB、ⅡC、T4 - T6危险区❝安全区输出:信号范围:4-20mA或(1-5V);负载电阻:≤550Ω(电流输出),≥10KΩ(电压输出);(用户在订货时右选择电流或电压输出)❝危险区输入:信号范围:4-20mA;配电电压:20mA时>15.5V,开路时≤26V❝转换精度:0.1%❝温度漂移(-20~60℃):< 0.1μA/℃❝发光二极管显示:绿色:电源指示❝电源:20- 35Vdc❝功耗:24V,120mA❝最高电压Um:250V❝防爆标志:[Ex ia Ga]ⅡC❝安全参数:端子(9-10-11间)Uo=28V,Io=93mA,Po=0.66WⅡC:Co=0.083μF,Lo=4.2mHⅡB:Co=0.366μF,Lo=12.6mHⅡA:Co=1.016μF,Lo=33.6mH使用环境❝安全隔离:安全侧与危险侧隔离电压250V,ac❝绝缘强度:2500V,ac.;1min(本安端与非本安端)❝环境温度:连续使用:-20℃ ~ +60℃贮存:-40℃ ~ +80℃❝相对湿度:10% – 90%RH❝大气压:80 – 110Kpa❝工作场所要求:安全栅应安装在安全区不含爆炸性气体的安全环境中,并不得有振动及冲击,无大电流和火花等电磁感应影响及周围环境中无强烈腐蚀的场所。
SIHD5-PTCH-00B1隔离式安全栅HD5500系列产品选型手册概 述电气隔离技术能够实现输入/输出信号的完全隔离,从而显著提升电子系统的抗干扰性和可靠性,越来越多的工业控制对现场设备和控制室设备之间提出了采用隔离接口单元的要求。
HD5500系列隔离式安全栅通过光、电、磁等隔离技术对供电电源、输入端信号和输出端信号进行相互隔离,从而实现现场的本质安全设备和控制室设备之间数字/模拟信号的隔离传输,是现场的本质安全设备和控制室设备之间理想的隔离接口单元。
HD5500系列隔离式安全栅的设计遵循最新的国家标准GB3836.1-2010、GB3836.4-2010,符合本质安全防爆要求,具备严格的隔离及能量限制能力,可与安装在危险场所的本质安全设备共同组成本质安全防爆系统,通过内部综合性的限压、限流设计来限制流向危险区的电能量,从而保证危险场所的电器设备及人身安全。
HD5500全系列隔离式安全栅涵盖了以下设备功能:热电阻温度信号变送器、热电偶温度信号变送器、毫伏信号变送器、配电器、信号分配器以及中间驱动继电器等。
特 点∙ [Ex ia Ga]ⅡC 防爆等级,适用于最危险的0区危险场所及最危险介质。
∙ 隔离故障点,将调试维护过程中可能出现的故障限制在单侧,即使遭受如雷击等意外。
∙ 输入/输出信号及电源三端口隔离,构成完全浮空的系统,从而消除工业现场复杂的工频干扰、共模干扰等影响,极大地简化现场问题的处理。
∙ 三重冗余电路设计。
∙ 完善的线路故障指示,便于现场故障点的快速定位、查找。
∙ 无须接地,相关现场设备可视情况接地或不接地,消除接地回路带来的干扰。
∙ 低功耗及有效的散热结构设计,有效地降低密集安装条件下机柜的温升,提高产品可靠性,延长使用寿命。
∙ 高转换精度。
∙ 功能系列化,可满足信号隔离、配电、信号变送等过程控制中最广泛的功能需求。
∙ 12.5mm 超薄设计,顺应现代控制密集安装要求,节省机柜空间,提高装置的集成度。
关于优倍安全栅国家标准主编单位中石化安全栅框架协议单位工信部两化融合贯标单位工信部智能工厂标准化示范验证单位江苏省电涌保护器工程技术研究中心南京优倍电气有限公司成立于2002年,江苏省高新技术企业。
公司致力于安全栅、隔离器、温度变送器、电涌保护器、安全继电器等工业信号接口仪表的研发制造,并为以上产品国标组组长单位,主持起草《隔离式安全栅》等国家标准。
优倍电气是国内该专业市场的主要供应商之一,品牌及品质享受盛誉。
公司为工信部两化融合体系贯标试点单位、工信部智能工厂标准化示范验证单位、江苏省、南京市首批示范智能工厂。
先后被江苏省省委、省政府授予百家江苏省优秀企业、江苏制造突出贡献奖优秀企业、江苏科技小巨人企业等光荣称号。
公司总部及新建并投产运营的优倍智造园均位于南京江宁经济技术开发区,占地面积30亩,全公司现有员工160余名,建有江苏省研究生工作站、江苏省电涌保护器工程技术研究中心、南京市工程应用研究中心,在工业测控领域有着深厚的科研基础及广泛的应用经验,产品获得多项国内、国际认证。
SILIEC 61508目录G系列隔离式安全栅(端子供电)通用型温度变送(常用产品型号)NPEXA-G01 (单通道,1路4 ~ 20mA输出,智能型)NPEXA-G011 (单通道,2路4 ~ 20mA输出,智能型)NPEXA-G0D11 (双通道,2路有源/无源4 ~ 20mA输出,智能型)热电偶输入(常用产品型号)NPEXA-G11 (单通道,1路4 ~ 20mA输出,智能型)NPEXA-G111 (单通道,2路4 ~ 20mA输出,智能型)NPEXA-G1D11 (双通道,2路有源/无源4 ~ 20mA输出,智能型)NPEXA-G11L (单通道,1路4 ~ 20mA输出,回路供电,智能型)热电阻输入(常用产品型号)NPEXA-G21 (单通道,1路4 ~ 20mA输出,智能型)NPEXA-G211 (单通道,2路4 ~ 20mA输出,智能型)NPEXA-G2D11 (双通道,2路有源/无源4 ~ 20mA输出,智能型)NPEXA-G27 (单通道,1路1:1电阻输出,智能型)NPEXA-G277 (单通道,2路1:1电阻输出,智能型)NPEXA-G21L (单通道,1路4 ~ 20mA输出,回路供电,智能型)电流输入(常用产品型号)NPEXA-GM31 (单通道,1路4 ~ 20mA输出,HART通过型)NPEXA-GM311 (单通道,2路4 ~ 20mA输出,HART通过型)NPEXA-GM3D11 (双通道,2路有源/无源4 ~ 20mA输出,HART通过型) NPEXA-G31 (单通道,1路4 ~ 20mA输出,智能型)NPEXA-G311 (单通道,2路4 ~ 20mA输出,智能型)NPEXA-G3D11 (双通道,2路有源/无源4 ~ 20mA输出,智能型)NPEXA-GM31L (单通道,1路4 ~ 20mA输出,回路供电)NPEXA-GM3D11L (双通道,2路4 ~ 20mA输出,回路供电)NPEXA-G31L (单通道,1路4 ~ 20mA输出,回路供电,智能型)模拟量输出(常用产品型号)NPEXB-GM31 (单通道,1路4 ~ 20mA输出,HART通过型)01 01 0203 03 04 0506 06 07 08 08 0910 10 11 12 12 13 14 14 1516INPEXB-GM311 (单通道,2路4 ~ 20mA输出,HART通过型)NPEXB-GM3D11 (双通道,2路4 ~ 20mA输出,HART通过型)NPEXB-GM31L (单通道,1路4 ~ 20mA输出,回路供电)NPEXB-GM3D11L (双通道,2路4 ~ 20mA输出,回路供电)电压信号输入(常用产品型号)NPEXA-G41 (单通道,1路4 ~ 20mA输出,智能型)NPEXA-G411 (单通道,2路4 ~ ~20mA输出,智能型)NPEXA-G4D11 (双通道,2路有源/无源4 ~ 20mA输出,智能型)开关量输入NPEXA-G511 (单通道,1路继电器触点输出)NPEXA-G5111 (单通道,2路继电器触点输出)NPEXA-G5D111 (双通道,2路继电器触点输出)NPEXA-G512 (单通道,1路晶体管输出)NPEXA-G5122 (单通道,2路晶体管输出)NPEXA-G5D122 (双通道,2路晶体管输出)开关量输出NPEXB-G512 (单通道,1路45mA电流输出)NPEXB-G5D12 (双通道,2路45mA电流输出)NPEXB-G512L (单通道,1路45mA电流输出,回路供电)NPEXB-G5D12L (双通道,2路45mA电流输出,回路供电)频率量输入(常用产品型号)NPEXA-G61P2 (单通道,1路4 ~ 20mA输出)NPEXA-G611P2 (单通道,2路4 ~ 20mA输出)NPEXA-G67P2 (单通道,1路1:1频率输出)NPEXA-G677P2 (单通道,2路1:1频率输出)数字通讯输入(常用产品型号)NPEXA-G711Z (单通道,1路RS-485输入,1路RS-485输出,9V/140mA) NPEXA-G711 (单通道,1路RS-485输入,1路RS-485输出,可调配电) NPEXA-G713 (单通道,1路RS-485输入,1路RS-422输出,可调配电) NPEXA-G731 (单通道,1路RS-422输入,1路RS-485输出,可调配电) NPEXA-G733 (单通道,1路RS-422输入,1路RS-422输出,可调配电)16 16 17 1718 18 1920 20 21 22 22 2324 24 25 2526 26 27 2728 29 30 31 32II电位器输入NPEXA-G91 (单通道,1路4 ~ 20mA输出)NPEXA-G911 (单通道,2路4 ~ 20mA输出)G系列模块表(端子供电)温度变送器毫伏中继器电位器变送器模拟量输入隔离器信号智能隔离器开关量输入隔离器频率变送器频率中继器产品附录组态工具33 3334 37 38 40 42 46 47 4849III01*注:电压输出接线参照电流接线 5+、6-, 7+、8-。
隔离式安全栅的工作原理范本隔离式安全栅是一种常用于工业自动化领域的安全装置,用于保护工人安全。
它能够检测到人体或其他物体的存在,并及时采取措施停止机器或设备运行,以避免发生事故。
隔离式安全栅的工作原理如下:1. 光栅传感器的工作原理:隔离式安全栅通常由一对光电栅传感器组成。
光电栅传感器包括发射器和接收器。
发射器发射出红外光束,接收器接收到反射的光束。
当没有任何物体遮挡光束时,接收器会接收到完整的光束;当有物体遮挡光束时,接收器会接收到部分或完全遮挡的光束。
2. 安全控制器的工作原理:隔离式安全栅需要一个安全控制器来处理光电栅传感器的信号。
安全控制器通常包括输入模块、处理器以及输出模块。
输入模块接收光电栅传感器的信号,并将其转化为数字信号传送给处理器。
处理器通过算法判断出光栅传感器是否被遮挡。
如果光栅传感器被遮挡,则处理器会发送停机信号给输出模块,从而停止机器或设备运行。
3. 安全回路的工作原理:隔离式安全栅需要一个安全回路来确保安全控制器的正常工作。
安全回路包括电源、故障监测装置以及输出装置。
电源为安全控制器提供电力,确保其正常工作。
故障监测装置监测安全控制器的工作状态,一旦发现故障,会发送信号给输出装置,停止机器或设备运行。
输出装置负责停机信号的传达,通常是通过继电器或其它输出接口连接到机器或设备的控制系统中。
4. 安全栅的设置与维护:隔离式安全栅需要根据具体的工作场景进行正确设置和维护。
首先,确定光栅传感器的布置位置,以确保能够覆盖整个危险区域。
其次,调整光电栅传感器的灵敏度和延时参数,使其适应实际工作情况。
此外,需要定期检查和保养安全栅,以确保其正常工作。
总结:隔离式安全栅的工作原理是基于光栅传感器的信号检测和安全控制器的响应控制。
光栅传感器通过检测物体对红外光束的遮挡来发信号,安全控制器通过算法判断光栅传感器是否被遮挡,并发送停机信号给输出装置,从而停止机器或设备运行。
隔离式安全栅设置和维护的正确性对确保其安全性至关重要。
模拟量输入隔离式安全栅1范围本文件规定了模拟量输入隔离式安全栅的术语和定义、缩略语、分类、主要参数、型号、技术要求、试验方法、检验规则、标志、使用说明书、包装和贮存。
本文件适用于可接收现场危险区域信号或其它电流信号,经过隔离和线性化的处理,转换为线性化的模拟量信号输出至安全区的控制系统或其它单元组合仪表,同时支持数字信号传输的模拟量输入隔离式安全栅(以下简称“安全栅”)。
2规范性引用文件下列文件中的内容通过文中的规范性引用而构成本文件必不可少的条款。
其中,注日期的引用文件,仅该日期对应的版本适用于本文件;不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
GB/T191包装储运图示标志GB/T2408—2021塑料燃烧性能的测定水平法和垂直法GB/T2423.1电工电子产品环境试验第2部分:试验方法试验A:低温GB/T2423.2电工电子产品环境试验第2部分:试验方法试验B:高温GB/T2423.3环境试验第2部分:试验方法试验Cab:恒定湿热试验GB/T2423.4电工电子产品环境试验第2部分:试验方法试验Db交变湿热(12h+12h循环)GB/T3836.1爆炸性环境第1部分:设备通用要求GB/T3836.4爆炸性环境第4部分:由本质安全型“i”保护的设备GB/T3836.13爆炸性环境第13部分:设备的修理、检修、修复和改造GB/T3836.15爆炸性环境第15部分:电气装置的设计、选型和安装GB/T3836.16爆炸性环境第16部分:电气装置的检查与维护GB/T4208外壳防护等级(IP代码)GB/T4365电工术语电磁兼容GB/T9969工业产品使用说明书总则GB/T13384机电产品包装通用技术条件GB/T17626.2—2018电磁兼容试验和测量技术静电放电抗扰度试验GB/T17626.3—2016电磁兼容试验和测量技术射频电磁场辐射抗扰度试验GB/T17626.4—2018电磁兼容试验和测量技术电快速瞬变脉冲群抗扰度试验GB/T17626.5—2019电磁兼容试验和测量技术浪涌(冲击)抗扰度试验GB/T17626.8—2006电磁兼容试验和测量技术工频磁场抗扰度试验GB/T18271.2—2017过程测量和控制装置通用性能评定方法和程序第2部分:参比条件下的试验GB/T28471.1—2012GB/T28471.2工业过程测量和控制系统用隔离式安全栅第2部分:性能评定方法3术语和定 工业过程测量和控制系统用隔离式安全栅第1部分:通用技术条件义GB/T3836.1、GB/T3836.4、GB/T4365界定的以及下列术语和定义适用于本文件。
隔离式安全栅的基础知识采用了将输入、输出以及电源三方之间相互电气隔离的电路结构,同时符合本安型限制能量的要求。
与齐纳式安全相比,虽然价格略高,但它其它方面的突出优点却为用户应用带来了更大的受益:1.由于采用了三方隔离方式,因此无需系统接地线路,给设计及现场施工带来极大方便。
带配电隔离式安全栅[1]2.对危险区的仪表要求大幅度降低,现场无需采用隔离式的仪表。
3.由于信号线路无需共地,使得检测和控制回路信号的稳定性和抗干扰能力大大增强,从而提高了整个系统的可靠性。
4.隔离式安全栅具备更强的输入信号处理能力,能够接受并处理热电偶、热电阻、频率等信号,这是齐纳式安全栅所无法做到的。
5.隔离式安全栅可输出两路相互隔离的信号,以提供给使用同一信号源的两台设备使用,并保证两设备信号不互相干扰,同时提高所连接设备相互之间的电气安全绝缘性能。
因此,对比齐纳式和隔离式安全栅的特点和性能后可以看出,隔离式安全栅有着突出的优点和更为广泛用途,虽然其价格略高于齐纳式安全栅,但从设计、施工安装、调试及维护成本来考虑,其综合成本可能反而低于齐纳式安全栅。
在要求较高的工程现场几乎无一例外地采用了隔离式安全栅作为主要本安防爆仪表,隔离式安全栅已逐渐取代了齐纳式安全栅,在安全防爆领域得到了日益广泛的应用.本安设备标志定义其中:Ex—防爆标志(ia)—防爆等级ⅡC—气体组别本公司产品防爆级别:Ex(ia)ⅡCia:在正常工作状态下,1个故障或2个故障状态下都不会点燃危险气体,回路必须保证在两个故障同时出现时仍然保证安全特性。
“ia”类电气设备对易受干扰的元器件必须采用“三重化”设计。
“ib”类电气设备只能保证在1个故障状态下不会点燃危险气体。
气体组别Ⅰ组电气设备:用于易受甲烷影响的煤矿环境中。
Ⅱ组电气设备:可用于除煤矿以外的爆炸危险环境中。
Ⅱ组电气设备根据易燃性物质的不同点燃能量进一步细分。
各子组用大写英文子母区分,从下表中可以看出,C子组所需要的点燃能量最少,即在该组电气设备中,C组设备具备通用性。
使用说明书隔离式安全栅CZ.GS8552-EX.11(S)-3.1/17.05接线安装拆卸⑴ 用螺丝刀(刀口宽度≤6mm)插入仪表下端的金属卡锁; ⑵ 螺丝刀向上推,把金属卡锁向下撬; ⑶ 仪表向上拉出导轨。
维护⑴ 隔离式安全栅进行通电调试前,必须再次检查隔离式安全栅的型号及防爆等级是否与设计和使用环境相符,必须再次检查安全侧与危险侧的接线以及它们电源和信号的极性是否正确;⑵ 严禁用兆欧表测试隔离式安全栅端子之间的绝缘性。
若要检查系统线路绝缘性时,应先断开全部隔离式安全栅接线,否则会引起内部快速熔断器熔断;⑶ 产品在出厂前均经过严格检验和质量控制,如发现工作不正常,怀疑内部模块有故障,请及时同最近的代理商或直接与技术支持热线联系;⑷ 产品从发货之日起五年以内,正常使用过程中出现产品质量问题均由辰竹免费维修。
辰竹官方微信地址:上海市民益路201号漕河泾开发区松江新兴产业园6号楼邮编:201612 总机:021-******** 传真:021-********销售服务:021-******** 技术支持:400 881 0780邮箱:chenzhu @chenzhu -inst .com 54⑴ 仪表接线采用可拆卸的接线端子,方便使用。
本安端(蓝色插头)为通向危险侧的信号接线端,非本安端(绿色插头)为通向安全侧的信号接线端;⑵ 本安侧的配线应选用有蓝色标记的本安导线,导线的软2铜截面积必须大于0.5mm 绝缘强度应大于500V;⑶ 隔离式安全栅本安端和非本安端的配线导线在汇线槽中应分开铺设、各自采用保护套管;⑷ 导线裸露长度约为8mm 由M3螺钉锁紧,,(电源总线插头端子由M2螺钉锁紧)。
使用产品前请仔细阅读本使用说明书,并请妥善保管GS8552-EX.11GS8552-EX.22(防爆合格证号:GYB15.1729)隔离式安全栅应安装在安全场所, 同时还要遵守GB3836.13-2013“爆炸性环境 第13部分:设备的修理、检修、修复和改造”、GB3836 .15-2000“爆炸性气体环境用电气设备第 1 5 部分:危险场所电气安装(煤矿除外)”、GB3836.16-2006“爆炸性气体环境用电气设备第 1 6 部分:电气装置的检查和维护(煤矿除外)和GB50257-1996“电气装置安装工程爆炸和火灾危险环境电气装置施工及验收规范”的有关规定。