表 H-421项目:母线安装记录Project 装置:Bus installation record Unit工号:Section 名称施工日期Name Date电压等级kV 图号Voltage Drawing No.母线型号、规格套管、绝缘子型号Bus model and spec.Bushing insulator model1、一般安装检查:General installation inspection序号检查调整项目安装检查结果No.Inspection and adjustment item Inspection result1母线型号、规格、材质核对型号□规格□材质□Bus model, spec, and mat. Inspection Model Specification Material2绝缘子、穿墙套管检查型号规格□油位、密封□绝缘□Insulator and lead-in insulator Model Oil level, seal Insulation3母线支架制作安装规格□安装尺寸□防腐□Bus support fabrication and installation Spec.Dimension Anti-corrosion4母线安装检查排列、相色□弯曲倍率□伸缩节□Bus installation Arrangement, color Curve radius Expansion joint5连接螺栓、垫圈检查规格□热镀锌□露出长度□Bolt and washer inspection Spec.Galvanization Left length6母线接触面光洁平整□搪锡□电力复合脂□Bus contact area inspection Smooth.Enam.Polymer7硬母线焊接检查焊工合格证号Rigid bus welding inspection Weldor No.软母线、组合母线安装8Flexible and combine bus installation 2、母线接触面连接紧密检测:Bus contact. Tightness inspection螺栓规格实测力矩值( N.m )螺栓规格实测力矩值( N.m)螺栓规格实测力矩值( N.m)Actual torque Actual torque Actual torque( mm)( mm)( mm)最小值最大值最小值最大值最小值最大值Bolt spec.Bolt spec.Bolt spec.Min.Max.Min.Max.Min.Max.3、软母线弛度:Flexible bus sag inspection软母线名称Flexible bus name设计弛度( mm)Design sag实测弛度(mm)Actual sag4、母线相同、对地最小距离检测:Bus phase and phase to earth min. Distance measure母线类别主母线分支母线Bus type Main Branch实测最小相间距离(mm)Min. Phase to phase distance实测最小对地距离Min. Phase to earth distance备注:Remarks结论:Conclusion技术负责人施工人Check Operator表 H-422项目:蓄电池充(放)电记录Project 装置:Storage battery charging/Discharging record Unit工号:Section 名称型号出厂日期Name Model Manuf. Date电压V 容量Ah电池总数Voltage capacity Number of battery电解液Electrolyte电解液化验单或合格证号蒸馏水化验单或合格证号Electrolyte report or certification No.Distilled water report or certification No.注入时电解液温度℃电解液比重Electrolyte temp. at filling Specific gravity of electrolyte开始注入时间结束时间Filling start time End time初充电First charging充电开始时间结束时间Charging start time End time单独补充充电的电池编号Separately charged cell No.放电Discharging放电开始时间结束时间Discharge start time End time放电电流Discharge current放电容量Discharging capacity为额定容量的%(换算到 25℃时)% of rated capacity (at 25℃)充(放)电特性曲线图:(充放电记录见附表)Charging/Discharging characteristic curve备注:Remarks结论:Conclusion技术负责人施工人Check Operator表 H-424项目:电机抽芯检查记录Project 装置:Motor loose-core inspection record Unit工号:Section 名称位号Name Tag. No.型号额定容量Type Rated capacity额定电流A 接法Rated current Connection 转速转子结构r/minRotor structure Rotation speed出厂编号制造厂Manufacturer No.Manufacturer检查内容Installation contents铁芯轴颈无伤痕锈蚀No Damage & corrosion on surface of core shaft滑环和换向器无伤痕、锈蚀No Damage & corrosion on surface of commutator and slip-ring绕组绝缘层完好,绑线无松动Winding insulation coating and fixing inspection绕组连接正确,焊接良好Winding connection and welding inspection绕组电阻检测合格Winding resistance inspection定子槽楔无断裂凸出及松动,端部槽楔牢固Stator slot wedge inspection转子平衡块紧固,平衡螺丝锁车Rotor balance block and bolt fixing inspection风扇完好,方向正确Fan inspection磁极及铁轭固定良好Magnetic pole and hub fixing inspection励磁绕组紧固Exciter winding fixing inspection鼠笼式电机转子导电条和端环焊接良好,浇铸无裂纹Rotor conductor and end link of squirrel-cage motor轴承滚动体与内、外圈转动灵活无松动、卡涩Bearing rotating flexibility inspection加入轴承内的润滑脂已填满内部空间的三分之二Internal space of bearing is filled with lubrication grease电机机部清洁无杂物Motor internal cleanliness inspection结论:Conclusion检查日期Inspection DatekW额定电压kV Rated voltage绝缘等级Insulation class防爆等级Explosion proof class防护等级Prevention class标记备注Mark Remark□□□□□□□□□□□□□□技术负责人施工人Check Operator表 H-425项目:电机干燥记录Project 装置:Motor drying record Unit工号:Section名称位号干燥日期Name Tag. No.Drying Date型号额定容量kW 绝缘等级Type Rated capacity Insulation class定子电压V 转子电压V制造厂Stator voltage Rotor voltage Manufacturer定子电流A 转子电流A出厂日期Stator current Rotor current Manuf. Date接线转速r/min 出厂编号Connection Rotation speed Manufacturer No.干燥方法简述Brief discription of drying method干燥开始时间年月日时分Drying start time Date干燥结束时间年月日时分Drying end time Date干燥过程最高温度定子℃转子℃Max. drying temp.Stator Stator干燥后绝缘电阻及吸收比Insulation resistance and absorptance after drying.测试部位定子对地转子对地Test position Stator to earth Rotor to earth电机温度(℃)R15"(M Ω)R60"( M Ω)K R15"( M Ω)R60" (M Ω)K Motor temperature备注:Remarks结论:Conclusion技术负责人施工人Check Operator电机干燥记录附表Attached table for motor drying record温度(℃)定子绝缘电阻时间Temp.(M Ω)Time23456Stator ins. resistance 1测温点位置: nTemp. measure position1.;2.表 H-426项目:Project装置:Unit工号:Section转子绝缘电阻干燥电流备注(MΩ)(A)Remark Rotor ins. resistance Drying current;3.;4.;5.;6.;技术负责人Check电机名称或序号位号No. Motor nameor tag. No.备注:Remarks结论:Conclusion施工人日期Operator Date表 H-427项目:电机试车记录Project装置:Motor test run record Unit工号:Section额定数据 Rated data试车记录数据 Test run record data环境绝缘空载负载电机轴承温度(℃)温度试车容量电压绝缘电压电流(℃)电流电阻电流温度Bearing temp.日期(kW)(V)等级(V)(A)Envi-ro(A)(M Ω)(V)(A)Date Capa Vol-t Ins.Vol-ta No-Lo nment Curr.Ins.Vol-t Motor前后-city age class ge ad temp.resis.age temp.Front Rearcurr.技术负责人施工人Check Operator项目:架空线路施工记录Project 装置:Overhead line stringing record Unit工号:Section 线路名称施工日期Line name Date 线路电压线数线路长度Voltage Line number Length 线路起点线路终点Start place End place施工记录Stringing record电杆型号、规格及数量拉线材料及组数Pole model, spec. Quantity Stay material and quantity 导线型号及规格路灯型号及数量Line model and spec.Road lamp model and quantity绝缘子型号及规格路灯线型号及规格Insulator model and spec.Road line model and spec.弛度Sag耐张杆号(号一号)Anchor pole (No. — No.)设计弛度( mm)Design sag实测驰度( mm)Real sag环境温度(℃)Environment temp.对地、交叉跨越距离测量:Line to earth and to cross-over objects distance measurement跨越杆号被跨越物名称被跨越物对最近杆、塔的水平距离(m)导线对被跨越物的最小垂直距离号一号(m)Cross-over object The nearest distance between crossoverCross-over Min. Vertical distance from line to name object and polepole No.-N0.cross-over object 表 H-428温度(℃)Temp.线中绝缘电阻( MΩ) A —B ,C,E,O B—A ,C,E,O C—A ,B,E,O Line insulation resistance相位检查Phase sequence inspection备注:Remarks结论:Conclusion技术负责人施工人Check Operator表 H-429项目:避雷、接地装置安装记录Project装置:Lightning conductor and earthing device Unitinstallation record工号:Section 名称施工图号Name Drawing No.1.绘图或简述避雷及接地装置情况(种类、材质、规格、长度、埋入深度、数量、连接方法、尺寸及防腐等)Drawing or brief discription of the lightning conductor and earthing device (kind, material, specification, buried length, quantity, connection, dimension and anti-corrosion, etc.)2.接地电阻测量记录Grounding resistance measurement record序号测试位置接地电阻(Ω)试验日期当天及三天前天气情况No.Measure position Ground. resistance Measure date Weather of the day and three days ago备注:Remarks结论:Conclusion技术负责人施工人试验人Check Operator Tester表 H-430项目:电气安装记录Project 装置:Electrical installation record Unit工号:Section技术负责人施工人Check Operator表 H-431项目:交流电机试验报告ProjectAC Motor test report 装置:Unit工号:Section名称位号试验日期Name Tag. No.Test Date额定容量(kW )型号出厂编号绝缘等级Rated capacity Model Manuf. No.Insulation class定子电压V 定子电流A额定转速r/min接线方式Stator voltage Stator current Rated rpm Connect mode转子电压V 转子电流A相数防爆等级Rotor voltage Rotor current Phase number E. P. class 直流电阻测量 DC Resistance measure温度 Temp.℃定子绕组相别Stator phase直流电阻(Ω)DC Resistance转子绕组相别(Ω)Rotor phase直流电阻(Ω)DC Resistance各相直流电阻差别定子 Stator%;定子绕组极性DC Resistance deviation转子 Rotor%;Stator wind, polar.绝缘试验Insulation test绝缘电阻吸收比交流耐压电压( kV )时间直流耐压电压直流泄漏电流(μ绕组名称(kV )时间A)( MΩ)Absorp-ta AC Withstanding(mm )( mm)Wind name DC Withstanding DC Leakage Ins. resis nce voltage Time Timevoltage current定子绕组Stator wind转子绕组电机轴承绝缘电阻( M Ω)Rotor wind Bearing ins. resistance附属设备检查Auxiliary device test设备名称绝缘电阻( M Ω)直流电阻(Ω)Device name Insulation resistance DC Resistance起动电阻器Start-up resistor可变电阻器Variable resistor灭磁电阻器Magnetic extinguisher备注:Remarks结论:Conclusion技术负责人试验人Check Operator表 H-432项目:直流电机试验报告ProjectDC motor test report装置:Unit工号:Section名称位号试验日期Name Tag. No.Test Date额定容量kW 型号出厂编号励磁方式Rated capacity Model Manuf. No.Excite mode额定电压V 额定电流A额定转速工作率Rated voltage Rated currentr/minWork ratio Rated rpm励磁电压V 励磁电流AExcite voltage Excite current1.试验与检查 Test and inspection环境温度: Environment temp.℃励磁绕组的绝缘电阻及交流耐硬度试验M ΩkV minExcite wind. Ins. R & AC withstanding voltage test电枢的绝缘电阻及交流耐压试验— M ΩkV minArmtr. Ins. R & AC withstanding voltage test励磁绕组的直流电阻ΩExcite wind DC resistance电枢整流片间的直流电阻ΩArmtr. Back-to-back DC resistance励磁可变电阻器的直流电阻ΩDC R of Excite variable resistor绕组极性及其接线检查Wind. Polar. & connection碳刷位置检查Brush position inspection2.发电机的空载特性Generator no-Load characteristics励磁电流( A )Excite current电压( V)Voltage备注:Remarks结论:Conclusion技术负责人试验人Check Operator表 H-433项目:变压器试验报告Project 装置:Transformer test report Unit工号:Section名称位号试验日期Name Tag. No.Test Date额定容量kVA 型号出厂编号接线组别Rated capacity Model Manuf. No.Connection额定电压kV 额定电流阻抗%冷却方式Rated voltage Rated current ACool. mode Resistance直流电阻测量: AC Resistance measure温度:℃ Temp.高压侧Ⅰ(Ω)Ⅱ(Ω)Ⅲ(Ω)Ⅳ(Ω)Ⅴ(Ω)低压侧电阻(Ω)HV side LV side ResistanceA aB bC c误差%Error变压比检查:Transformer rate inspection高压侧电压 /低压侧电压实测变压比变压比误差( %)分接开关位置标称变比HV/LV Real rate Rate error Tap position Nominal rate UAB/Uab UBC/Ubc UCA/UcaAB BC CA ABBCCA(V )(V )(A)ⅠⅡⅢⅣⅤ绝缘试验:Insulation test绝缘电阻及吸收比交流耐压试验直流泄漏试验介质损失角正切值Ins. R and Absorbt AC withstanding voltageDC leakage test Loose tgδ项目R60"/R15"testItem R60"/吸收比电压时间电压电流tgδ温度Absorb-ta(kV )( min)(kV )(μ A )(℃)R15"(%)nce Voltage Time Voltage Current Temp.高压—低压及地HV —LV/Earth低压—高压及地LV —HV/Earth绝缘油试验:油号#;五次击穿电压平均值:kV接地组别或极性检查Ins. Oil test: oil No. , average voltage for 5 break down is Connection inspection备注:Remarks结论:Conclusion技术负责人试验人Check Operator表 H-434项目:断路器试验报告Project 装置:Circuit breaker test report Unit工号:Section名称位号试验日期Name Tag. No.Test Date型号额定电压kV 额定电流A开断电流kAModel Rated voltage Rated current M. current操动机构型号操作电压出厂编号Operation Oper. voltage Manuf. No.mechanism导电回路直流电阻测量真空断路灭弧室真空度检查六氟化硫断路器气体压力DC Resistance of primary circuit Vacuum insp. for vacuum breaker Gas press. Insp. for SF6 breaker相别主触头(μΩ)灭弧触头(μΩ)相别电压时间相别压力( Mpa)( kV )(min )Phase Main contact Arc-Extinguishing contact Phase Phase PressureVoltage TimeA A AB B BC C C机械特性:Mech. Characteristic最低合闸电压最低分闸电压合闸时间分闸时间合闸时间分闸时间Min. close voltage Min. openn voltage Close time Open time Close time Open time V V s s m/s m/s线圈试验:绝缘试验:Coil test Insulation. Test项目合闸接触器合闸线圈分闸线圈相别绝缘电阻交流试验电压时间(M Ω)(kV )(min )Item Close contact Close coil Open coil PhaseIns. resis.AC test voltage Time 直流电阻ΩΩΩ A —DC Resis.B —绝缘电阻MΩM ΩM ΩIns. resis.C—断路器在额定操作电压下分合闸次,动作良好。