智能数字显示液位控制仪说明书本厂产品是以单片微型计算机为核心、大规模集成电路为外围部件组成的高精度测控仪表,软、硬件采用多种抗干扰技术,采用EEPROM存储现场的工作数据,具有停、掉电数据不丢失,使用可靠性高的特点。
该仪表可与任何液位变送器配接组成液位测控系统。
功能简介:◆显示测量值◆设定液位控制值及输出控制方式◆可自由设定显示量程及小数点位数◆测量值变送输出,自由设定变送输出量程范围(可选功能)◆通过输入被测液体密度值实现不同液体液位的测量技术指标:◆开口尺寸:76*152;152*76;92*92;68*68;92*44共5种◆输入信号:线性电流信号或线性电压信号◆精度等级:0.5级◆采样速度:3次/秒◆电源电压:AC220V-10%--AC220V+10% ◆消耗功率:<=9W◆继电器触电容量:3A/220V(无感性负载)名词解释:二位式调节表(上限调节并带回差):仪表内只有一个上限继电器,当测量值高于设定值加P(P为上限回差值;后同)时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于设定值减P时,上限继电器中低通,同时指示灯“HA”灭.三位式调节表(上下限调节表):仪表内有两个继电器,可分别设定上限下限两个控制点; 当测量值高于上限设定值时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于上限设定值时,上限继电器中低通,同时指示灯“HA”灭. 当测量值高于下限设定值时,下限继电器中低通,同时指示灯“LA”灭; 当测量值低于下限设定值时,下限继电器中高通,同时指示灯“HA”亮范围调节表: 仪表内只有一个上限继电器,用此继电器可将被测量控制在设定的范围内,此种控制广泛用于不允许设备频繁启动的场合如控制水泵.控制过程如下:当测量值小于下限值时上限继电器中低通,“LA”灯亮;当测量值大于上限值时上限继电器中高通,“HA”灯亮;当测量值在上限值与下限值之间时,“LA”“HA”均灭,上限继电器维持原状态即:当测量值由下限值向上限值变化时,上限继电器维持中低通的状态; 当测量值由上限值向下限值变化时,上限继电器维持中高通的状态.上下限分别带回差调节表:在上限调节带回差表基础上增加下限调节并带回差,下限回差值用“A”表示; 当测量值高于上限设定值加P(P为上限回差值;后同)时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于上限设定值减P时,上限继电器中低通,同时指示灯“HA”灭;当测量值高于下限设定值加A(A为上限回差值;后同)时,下限继电器中低通,同时指示灯“LA”灭; 当测量值低于下限设定值减P时,下限继电器中高通,同时指示灯“LA”亮.仪表的操作:三个按键功能说明:“—”键设定/确认/提取键.该键的作用时进入仪表的设定状态,提取出原存的设定值,,待新的设定值修改完成后按该键确认修改有效并存入仪表内存,同时提取出下一个设定值.“∧”键显示数据加1功能键,单次按此键时数据加1;按住该键不动,显示数值将快速增加,松手后停止.“∨”键显示数据减1功能键,单次按此键时数据减1;按住该键不动,显示数值将快速减小,松手后停止.操作顺序:输入修改密码∶在测量状态下按一下“—”键,仪表即刻进入设定状态。
智能数字显示液位控制仪说明书本厂产品是以单片微型计算机为核心、大规模集成电路为外围部件组成的高精度测控仪表,软、硬件采用多种抗干扰技术,采用EEPROM存储现场的工作数据,具有停、掉电数据不丢失,使用可靠性高的特点。
该仪表可与任何液位变送器配接组成液位测控系统。
功能简介:◆显示测量值◆设定液位控制值及输出控制方式◆可自由设定显示量程及小数点位数◆测量值变送输出,自由设定变送输出量程范围(可选功能)◆通过输入被测液体密度值实现不同液体液位的测量技术指标:◆开口尺寸:76*152;152*76;92*92;68*68;92*44共5种◆输入信号:线性电流信号或线性电压信号◆精度等级:0.5级◆采样速度:3次/秒◆电源电压:AC220V-10%--AC220V+10% ◆消耗功率:<=9W◆继电器触电容量:3A/220V(无感性负载)名词解释:二位式调节表(上限调节并带回差):仪表内只有一个上限继电器,当测量值高于设定值加P(P为上限回差值;后同)时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于设定值减P时,上限继电器中低通,同时指示灯“HA”灭.三位式调节表(上下限调节表):仪表内有两个继电器,可分别设定上限下限两个控制点; 当测量值高于上限设定值时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于上限设定值时,上限继电器中低通,同时指示灯“HA”灭. 当测量值高于下限设定值时,下限继电器中低通,同时指示灯“LA”灭; 当测量值低于下限设定值时,下限继电器中高通,同时指示灯“HA”亮范围调节表: 仪表内只有一个上限继电器,用此继电器可将被测量控制在设定的范围内,此种控制广泛用于不允许设备频繁启动的场合如控制水泵.控制过程如下:当测量值小于下限值时上限继电器中低通,“LA”灯亮;当测量值大于上限值时上限继电器中高通,“HA”灯亮;当测量值在上限值与下限值之间时,“LA”“HA”均灭,上限继电器维持原状态即:当测量值由下限值向上限值变化时,上限继电器维持中低通的状态; 当测量值由上限值向下限值变化时,上限继电器维持中高通的状态.上下限分别带回差调节表:在上限调节带回差表基础上增加下限调节并带回差,下限回差值用“A”表示; 当测量值高于上限设定值加P(P为上限回差值;后同)时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于上限设定值减P时,上限继电器中低通,同时指示灯“HA”灭;当测量值高于下限设定值加A(A为上限回差值;后同)时,下限继电器中低通,同时指示灯“LA”灭; 当测量值低于下限设定值减P时,下限继电器中高通,同时指示灯“LA”亮.仪表的操作:三个按键功能说明:“—”键设定/确认/提取键.该键的作用时进入仪表的设定状态,提取出原存的设定值,,待新的设定值修改完成后按该键确认修改有效并存入仪表内存,同时提取出下一个设定值.“∧”键显示数据加1功能键,单次按此键时数据加1;按住该键不动,显示数值将快速增加,松手后停止.“∨”键显示数据减1功能键,单次按此键时数据减1;按住该键不动,显示数值将快速减小,松手后停止.操作顺序:输入修改密码∶在测量状态下按一下“—”键,仪表即刻进入设定状态。
水位计使用说明书一、产品概述水位计是一种用来测量液体水位高低的仪器,它通常由浮子、测量杆、计量尺等组成。
本说明书详细介绍了水位计的使用方法、注意事项以及维护保养等相关信息。
二、产品规格1. 测量范围:0~10米2. 测量精度:±5毫米3. 工作温度:-20℃~60℃4. 材质:不锈钢三、使用方法1. 安装水位计根据实际需要选择合适的安装位置,确保测量杆能够自由浮动,并且不受外界干扰。
将测量杆固定在要测量液体的侧壁上,并确保与液面平行。
2. 示数读取当水位发生变化时,测量杆会跟随液位升降,并通过计量尺上的刻度进行示数。
用户可以根据刻度读取液位高度。
3. 准确性调校在初次使用或长时间未使用后,需要进行准确性调校。
具体方法如下:a. 确保测量杆在没有液位的情况下,指示器指向零刻度。
b. 将测量杆完全插入液体,等待一段时间使浮子稳定,记录此时的示数。
c. 比较示数与实际液位的差异,并将差异通过调校开关进行调整。
四、注意事项1. 防止震动:水位计安装时应尽量避免受到外界震动,以免干扰浮子的浮动和精度读取。
2. 防止污染:水位计应安装在无腐蚀性和污染性物质的环境中,以确保产品的正常使用寿命。
3. 防止冻结:在低温环境下使用水位计时,应采取相应的防冻措施,以免影响仪器的正常工作。
4. 维护保养:定期对水位计进行清洁和检查,确保测量杆的自由浮动和刻度的清晰可读。
五、故障排除在使用过程中,如果发现水位计出现异常现象,如示数异常、测量杆卡住等情况,请及时进行故障排除。
可参考以下方法:1. 检查是否有外界干扰物体,有则及时清除。
2. 检查测量杆是否被固定在液体表面。
3. 检查刻度盘是否清晰可读,若不清晰可参照维护保养部分进行清洁。
六、维护保养1. 定期清洁:使用软布蘸取清水擦拭水位计表面,不要使用有腐蚀性的溶剂或刷子清洁。
2. 定期检查:检查测量杆和刻度尺是否有损坏或变形情况,如有问题及时更换。
3. 存放注意:长期不使用时,请将水位计放置在干燥通风的地方,避免受潮或霉变。
智能数字显示液位控制仪说明书本厂产品是以单片微型计算机为核心、大规模集成电路为外围部件组成的高精度测控仪表,软、硬件采用多种抗干扰技术,采用EEPROM存储现场的工作数据,具有停、掉电数据不丢失,使用可靠性高的特点。
该仪表可与任何液位变送器配接组成液位测控系统。
功能简介:◆显示测量值◆设定液位控制值及输出控制方式◆可自由设定显示量程及小数点位数◆测量值变送输出,自由设定变送输出量程范围(可选功能)◆通过输入被测液体密度值实现不同液体液位的测量技术指标:◆开口尺寸:76*152;152*76;92*92;68*68;92*44共5种◆输入信号:线性电流信号或线性电压信号◆精度等级:0.5级◆采样速度:3次/秒◆电源电压:AC220V-10%--AC220V+10% ◆消耗功率:<=9W◆继电器触电容量:3A/220V(无感性负载)名词解释:二位式调节表(上限调节并带回差):仪表内只有一个上限继电器,当测量值高于设定值加P(P为上限回差值;后同)时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于设定值减P时,上限继电器中低通,同时指示灯“HA”灭.三位式调节表(上下限调节表):仪表内有两个继电器,可分别设定上限下限两个控制点; 当测量值高于上限设定值时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于上限设定值时,上限继电器中低通,同时指示灯“HA”灭. 当测量值高于下限设定值时,下限继电器中低通,同时指示灯“LA”灭; 当测量值低于下限设定值时,下限继电器中高通,同时指示灯“HA”亮范围调节表: 仪表内只有一个上限继电器,用此继电器可将被测量控制在设定的范围内,此种控制广泛用于不允许设备频繁启动的场合如控制水泵.控制过程如下:当测量值小于下限值时上限继电器中低通,“LA”灯亮;当测量值大于上限值时上限继电器中高通,“HA”灯亮;当测量值在上限值与下限值之间时,“LA”“HA”均灭,上限继电器维持原状态即:当测量值由下限值向上限值变化时,上限继电器维持中低通的状态; 当测量值由上限值向下限值变化时,上限继电器维持中高通的状态.上下限分别带回差调节表:在上限调节带回差表基础上增加下限调节并带回差,下限回差值用“A”表示; 当测量值高于上限设定值加P(P为上限回差值;后同)时,上限继电器中高通,同时指示灯“HA”亮; 当测量值低于上限设定值减P时,上限继电器中低通,同时指示灯“HA”灭;当测量值高于下限设定值加A(A为上限回差值;后同)时,下限继电器中低通,同时指示灯“LA”灭; 当测量值低于下限设定值减P时,下限继电器中高通,同时指示灯“LA”亮.仪表的操作:三个按键功能说明:“—”键设定/确认/提取键.该键的作用时进入仪表的设定状态,提取出原存的设定值,,待新的设定值修改完成后按该键确认修改有效并存入仪表内存,同时提取出下一个设定值.“∧”键显示数据加1功能键,单次按此键时数据加1;按住该键不动,显示数值将快速增加,松手后停止.“∨”键显示数据减1功能键,单次按此键时数据减1;按住该键不动,显示数值将快速减小,松手后停止.操作顺序:输入修改密码∶在测量状态下按一下“—”键,仪表即刻进入设定状态。
水位测控仪使用说明书V2.0济南智泽贸易有限公司目录1、概述 (2)2、技术指标 (2)3、工作原理 (3)4、面板布置及使用方法 (4)5、安装与调整 (6)6、注意事项 (11)7、低功耗说明 (11)8、质保与售后 (12)9、联系方式 (12)10、免责声明 (12)一、概述水位测控仪,是根据水利工程的实际需要而制造的,它和模拟量输入的液位传感器(如投入式或超声波传感器)相配合组成水位测控系统。
水位测控仪采用微电脑控制技术,具有测量值和设定值数码显示;输入输出电路采用光电隔离技术;三个继电器动作(上限、下限、设定点三个预置点);4-20mA标准模拟量输出,RS485串行通讯接口等。
继电器动作预置由仪表面板的按键完成,继电器动作时相应的指示灯点亮、蜂鸣器发出报警(静、响可控)功能。
该仪表通过内部设定可完成:海拔基值的设定、测量数据的修正系数、4-20mA对应满量程调整等。
传感器相对零点,用户可轻松地查看和设置等,可选择显示相对水位和设定水位或显示相对水位和绝对水位(含海拔基值),是理想的水位测控仪表。
下图为水位测控仪系统结构示意图:二、技术指标1、相对测量范围:0~65000cm(或0~65000mm)2、绝对测量范围:海拔基值~99999cm(或海拔基值~99999mm)3、分辨率:1cm(或1mm)4、修正系数:(1~65000)/10000用户可自行调节5、精度;±0.1%×量程±1cm(或±1mm)微处理器4-20mA输出RS485接口声光报警继电器输出设定值LED显示测量值LED显示6、海拔基值设定:-9999~99999cm (或-9999~99999mm)7、输出接点:●上限:测量值大于等于上限值,声、光报警,上限继电器动作;●下限:测量值小于等于下限值,声、光报警,下限继电器动作;●设定:测量值大于等于设定值,声、光报警,设定继电器动作;●触点容量:AC220V/5ADC125V/5A8、输入信号:4-20mA 标准模拟量信号9、输出信号(光电隔离):4-20m 标准模拟量输出(对应值用户可自行调节)(选配)10、通讯接口:RS485接口(支持MODBUS-RTU 协议)11、工作环境:无剧烈振动防尘场所;温度:-20—60℃湿度:≤95%12、工作电压:AC220V ±10%50HZ13、机箱尺寸∥(开口尺寸)(单位mm):高80×宽160×深120∥高76×宽152三、工作原理水位变化带动传感器变化,将变化的水位转变为4-20mA 模拟信号后,输入到测控仪,经微处理器处理后,以数字显示其水位值,同时按照不同的设定值及上限、下限控制继电器触点输出状态,提供控制信号。
Water Tank Level MonitorINSTRUCTION MANUALMODEL NO: WTL001Table of Contents1. INTRODUCTION (2)1.1 Package Contents (2)1.2 Features (2)2. INSTALLATION (3)2.1 Water Tank Sensor Battery Installs (3)2.2 Set Up Sketch (3)2.3 Installation Notes (4)2.4 Indoor Receiver Battery Install (4)2.5 Initial Set Up (4)3. OVERVIEW (5)4. PROGRAM MODE (6)4.1 SET TANK DEPTH (6)4.2 SET AIR GAP (7)4.3 SET TIME (8)4.4 SET TEMPERATURE UNIT (8)4.5 SET TANK LEVEL UNIT (8)4.6 CHECK AND RESET MIN/MAX VALUE (9)4.7 TANK LEVEL AND TANK TEMPERATURE SWITCH (9)4.8 ALARM (9)4.8.1 SET ALARM TIME (9)4.8.2 SET TANK LEVEL HIGH AND LOW ALARM (10)4.8.3 ENABLE OR DISABLE ALARM BUZZER (10)4.8.4 EMPTY ALERT (10)5. DEFAULT VALUE (10)6. SPECIFICATIONS (11)This Operation Manual is part of this product and should be kept in a safe place for future reference. It contains important notes on setup and operation.1. INTRODUCTIONPlease read this instruction manual thoroughly to fully understand the correct operation of your Water Tank Level Monitor. The following user guide provides step by step instructions for installation, operation and troubleshooting.1.1 Package Contents● 1 x Indoor receiver● 1 x Water tank transmitter● Mounting screws● Instruction manual1.2 Features● 12/24 hour time display● Time alarm● Indoor temperature● Tank temperature● Monitors water tank level● Level displayed on a 10 element LCD bar graph for water level● Records min. and max. for indoor and tank temperature/level● TANK level high/low alarm mode● All alarm ON/OFF option system● TANK empty alert● Transmitter low battery indicator● Tank level updated 30 seconds or 3 minutes2. INSTALLATION1) Open the battery door, remove the battery box ;2) Insert 6 x AAA 1.5V alkaline batteries into the battery box, observing the correct polarity. Then put back the battery box according to the marking direction.2.2. Set Up SketchThe following picture illustrates transmitter installation:1. Antenna2. Balance bubble3. Screw4. Bracket5. Sensor6. TankNOR(m) H3(m) 10.1 ≤1 20.2 ≤3 30.3 ≤5 40.5 ≤10 5 0.8 ≤15H3: The exact distance sensor can measure.R: The sensor from the tank wall distance.Note: the sensor from the tank wall distance will affect themeasurement range and precision of depthPlease pay attention to the following issues in installation:1) The distance between transmitter bottom and highest water surface must be 0.5m (1.64ft) or more.2) The maximum depth the unit can measure is 15m (49.2ft).3) Observe the balance bubble on the sensor to ensure it is installed at a level horizontal position.2.3 Examples of Wrong Installation1 2 3 41) The sensor is not installed at a level horizontal position.2) The sensor is too close to the TANK wall.3) There are solid objects in the tank.4) The transmitter bottom is dipped in the water (or other liquids in tank)2.4 Indoor Receiver Battery Installation2.5FRONT VIEW BACK VIEWOpen the base station’s battery cover located at the back of the unit and insert2 x AA, 1.5V alkaline batteries into the battery compartment and close the battery cover.2.5 Initial Set upFirst, insert the batteries into the wireless outdoor transmitter (6 x AAA) and then insert batteries immediately into the LCD display monitor (2 x AA). Once the batteries are in place, all segments of the LCD will light up briefly.3. OVERVIEWThe following illustration shows a normal LCD display for description purposes only1. Value display area (Fig. 1 & 2)Fig.1 Fig.22. Tank temperature and water level icon3. Water level unit4. Tank temperature unit (ºC/ºF)5. Outdoor low battery indicator6. Alarm activation icon7. Min. and max. indicator icon8. Empty alert icon9. RF signal indicator10. Tank level high and low alarm indicator11. Water tank depth icon12. Time alarm indicatorFig.313、Time and alarm value area ( Fig 3 )14、Time icon15、Indoor temperature value display area16、Indoor temperature unit4. PROGRAM MODE4.1 SET TANK DEPTHWhen the display unit is powered up, the LCD display activates for 3 seconds and makes a ”Beep”. The unit is now in Set Tank Depth mode and displays the tank depth value as a flashing "0.00" as well as a flashing empty tank icon(Fig.4).Press +/MAX/MIN key or -/TANK key to increase or decrease tank depth. Pressing and holding the keys will change the value at a much faster rate. Press the SET key to save the Tank Depth value. The LCD monitor now enters into Set Air Gap mode.●NOTE: To record correct measurement of tank depth (see H1+H2 in sketch of 2.2 on page 3), calculate from the bottom of the tank transmitter to bottom of your tank. Distance: 0.5m (min) - 15.0m (max) or1.64” (min) - 49.2” (max)4.2 SET AIR GAPThe monitor is now in Set Air Gap mode and displays "0.00" and full tank icon flashing(Fig.5). Press +/MAX/MIN key or -/TANK key to increase or decrease air gap. Hold +/MAX/MIN key or -/TANK key to increase or decrease air gap at greater step. Press the SET key to exit depth settingFig.5Display of "0.00" and full tank icon flashes(Fig.5). Press +/MAX/MIN key or -/TANK key to increase or decrease air gap. Pressing and holding the keys will change the value at a much faster rate. Press the SET key to save the Air Gap value.●NOTE: To record correct measurement of Air Gap (see H1 in sketch of 2.2 on page 3), calculate from the bottom of the tank transmitter to the maximum fluid level of tank. Distance: 0.5m (min) - 15.0m (max) or 1.64” (min) - 49.2” (max)If there’s no key operation in depth setting mode for longer than 15 seconds the unit will switch to normal display mode automatically. (There will be measurement errors if the tank depth and air gap are not set correctly).If you miss this step, Tank Depth and Air Gap can be set later.In normal operation mode, press and hold SET and ALARM keys for 5 seconds to set Tank Depth and Air Gap values. The setting steps are the same as above described.4.3 SET TIMEIn normal display mode press SET key for 3 seconds to enter SET mode.●12/24H: 12Hr or 24Hr will flash. Press +/MAX/MIN or -/TANK key to select 12H or 24H. Press SET key to move to hour setting.●HOUR: Hour value will flash. Press +/MAX/MIN or -/TANK key to increase or decrease hour value. When hour value is set press SET key to set minute value.●MINUTE:Minute value will flash. Press +/MAX/MIN or -/TANK key to increase or decrease minute value. When minute value is set press SET key to set temperature unit.4.4 SET TEMPERATURE UNIT●Temperature unit will flash. Press+/MAX/MIN or -/TANK key to select temperature unit of ºC or ºF. After temperature unit is set press SET key to set tank level unit.4.5 SET TANK LEVEL UNIT●Tank level unit will flash. Press +/MAX/MIN or -/TANK key to select water level unit of M (metre) or FEET. After tank level unit is set press SET key to exit.4.6 CHECK AND RESET MIN/MAX VALUE●In normal display mode press +/MAX/MIN key once to check the max value of indoor temperature and tank level or tank temperature.●Press +/MAX/MIN key again to check the min value of indoor temperature and tank level or tank temperature.●Press +/MAX/MIN key again to exit.●In the MIN/MAX mode press SET key, the min or max icon and value will flash. Press the +/MIN/MAX key once, the displayed minimum or maximum record will be reset to current value. Press SET key to reset the next minimum or maximum record.4.7 TANK LEVEL AND TANK TEMPERATURE SWITCH●In normal display mode press -/TANK key to switch from tank level display to tank temperature display or switch from tank temperature display to tank level display.●NOTE: If the tank level and tank temperature display “--.--“, this means the transmission signal is lost and needs to be reconnected to the LCD monitor. Press the -/TANK key for 5 seconds. The tank transmitter icon with double-ended arrow will be displayed on the LCD monitor indicating the transmitter and monitor are reconnecting. This can take up to 3 minutes before a tank reading appears.4.8 ALARM4.8.1 SET ALARM TIMEIn normal display mode press ALARM key. Previously set alarm time will display. Press SET key 3 seconds to set alarm hour. Alarm hour will flash. Press +/MAX/MIN or -/TANK key to increase or decrease alarm hour. After alarm hour is set press SET key to set alarm minute. Press +/MAX/MIN or -/TANK key to increase or decrease alarm minute.During alarm hour or minute flashing press ALARM key to enable or disable time alarm. When alarm time is enabled the icon is visible. When alarm time is disabled the icon is invisible. Press SET key to confirm alarm time setting and start to set level high or low alarm.4.8.2 SET TANK LEVEL HIGH AND LOW ALARMAfter finishing alarm time setting previously, now set tank level alarm value will flash. Press +/MAX/MIN or -/TANK key to increase or decrease HIGH alarm value. After tank level HIGH alarm is set press SET key to set tank level LOW alarm. Press +/MAX/MIN or -/TANK key to increase or decrease LOW alarm value.During high or low alarm value flashing press ALARM key to enable ordisable water level alarm. When high or low alarm is enabled the icon isvisible. When high or low alarm is disabled the icon is invisible. After tank level low alarm is set press SET key to exit.4.8.3 ENABLE OR DISABLE ALARM BUZZERIn default setting buzzer press ALARMALARM key 5 icon will appear.When water level is less than 20% of tank depth the icon1. Time:0:00—2. 12HR/24HR format:(default: 24HR)3. Temperature unit:ºC/ºF (default: ºC)4. Water level:metre/feet (default: m)5. TANK LEVEL/TANK TEMP display: (default: TANK TEMP)6. Alarm set:0:00—23:59 (default: 12:00, disabled)7. Water level HI-alarm:0 –15m(0 feet - 49.2 feet)(default: 10m, OFF)8. Water level LO-alarm:0 –15m(0 feet - 49.2 feet)(default: 2m, OFF)6. SPECIFICATIONSTransmission distance: max.100 metres (in open space)Frequency: 433MHzIndoor temperature range: 0 - 50°C,Resolution: 1°C,Accurate:+/-1°C,Tank temp measure range:-40 - 60°C,Resolution: 1°C,Accurate:+/-1°Water level measure range:0 - 15m,Resolution: 0.01m,Accurate: +/-0.03mAlarm duration: 120 secondsPower consumption●Indoor receiver: 2 x AA 1.5V batteries●Tank transmitter: 6 x AAA 1.5V batteriesLife: Minimum 24 monthsDistributed by:Sontax AustraliaPhone: 1800 653 238Email:****************.auWebsite: .auNeed assistance with set-up or operation?Before you return this product to the retailer,CALL US FIRST TOLL FREE:1800 653 238Monday – Friday 7.30am – 4.00pm (WST)EMAILYOURQUESTIONSTO:****************.au11。
XMUZ型液位显示仪安装使用说明书开封仪表厂液位仪表分厂二 OO 二年十二月_XMUZ- 型数字液位显示仪一、功能用途和使用范围1.特点:采用嵌入式微处理器具有数字和模拟两种显示方式液位上下限声响报警液位上下限控制信号输出4-20mA模拟输入,RS-485 串行数据输入可选有横、竖两种安装形式和有、无光柱两种显示形式可供选择2.主要用途与功能:用途:该液位显示仪能与输出 4-20mA.DC或具有RS-485接口的液位变送器配套使用,测量并显示被测对象的液位高低。
广泛应用于化工、石油、冶金、水电等部门的工业监测与控制。
功能:a.数字显示液位的高低。
b.模拟显示液位高低的百分比。
c.液位报警上,下限参数连续可调,并永久记忆不丢失。
d.可通过串引接口向上位计算机提供液位数据,远传距离可达 1.2公里e.可为液位变送器提供 24V直流电源。
3.使用环境条件环境温度: 0 ~ 50 ℃相对湿度≤ 85 %大气压力:86 ~ 106KPa机械震动:频率 f < 25Hz.振幅≤ 0.1mm外磁场:≤ 400m/A工作条件: 供电电源: 220V.AC± 10 % 50Hz± 5 %功率: < 10 W工作状态: 连续或断续工作二.主要技术性能1.本仪表执行 Q/098 KRY07-1998 《 XMUZ- 型液位显示仪》企业标准2.输入信号:4-20 mA.DC 输入阻抗≥ 1MΩRS-485 串行数据输入3.输出信号:上下限报警输出继电器触点容量 1A/30V 直流0.3A 125V AC. 串行输出符合 RS-485 标准4.显示输出:数字显示:位数 4 位,采样时间1秒误差: 0.5 % F.S模拟显示:百分比显示误差: 1% F.S5.电源输出:+ 24VDC/100mA,+12 VDC/100mA可选6.外形尺寸:150 × 160 ×807.仪表盘开孔尺寸:152 ×768.重量:约 0.5 Kg三.仪表工作原理:该仪表以嵌入式微处理器为核心,如果是从液位变送器输入的4-20mA模拟信号一路转换为频率信号,经软件进行标度及工程量变换,及上下限报警处理,然后将运算结果送面板显示或经串行口远传输出,另一路则送光柱显示单元将结果进行光柱模拟显示。
通过ISO9001国际质量体系认证TC-S(M)W系列长窗式双色水位计(半导体光源)使用说明书铁岭市光明仪器仪表厂TIE LING CITY GUANGMING INSTRMENTS AND METERS FACTORY一、用途及特点TC-S(M)W系列长窗式双色水位计是用于蒸汽锅炉或其它压力容器监测水位的一次就地直读仪表。
它是在总结国内外各种透射式双色水位计优点基础上最新研制的长窗式双色水位计,它与其它双色水位计相比较,具有如下几种特点:1、TC-SW-I型系列双色水位计盲区少、窗口布置合理。
在水位计本体上设置三个窗口,所以在水位计观察范围内只有两段盲区,每个窗观察范围是120mm而锅炉水位正常波动范围是±50mm,它正处于水位计中间窗口的观察范围内、所以在锅炉正常运行时,可无盲区监视,这是牛眼式水位计不可比拟的。
2、自冲洗效果良好。
由于本系列水位计是长窗式,与冷凝水接触面积大,所以当蒸汽流经上连接管时,一部分变成冷凝水后可顺窗口表面冲洗观察窗,使窗口不易挂垢。
3、光源采用特制的管灯、不需镇流器、只接36V安全电压既可,而且灯管发光均匀,耐高温,寿命长。
光源也可采用二极管(LED)的光源,它节能,比管灯寿命更长,耐高温。
整体光源调整更方便。
4、该型号水位计具有观察范围宽、颜色清晰、透明逼真的优点。
5、TC-S(M)W-II(III)型系列无盲区五窗、七窗水位计是在上述优点基础上,研制出在一块本体上并列设置两排窗口通过光学原理转换达到在水位计正前方±3°角范围观看水位计的两排窗口,可同时观察到两排红绿变化且红绿分明、界面清晰,可在水位计可视范围内无盲区连续监视。
6、TC-S(M)W-Ⅱ(Ⅲ)型系列水位计的本体都采用优良材质,不锈死,不变形7、窗口组件选用国际一流材质,承压好,不泄漏,运行长久。
综上所过,该系列产品是监测锅炉水位的最理想仪表。
另外,我公司还可根据用户的实际情况,提供最合理的水位监视解决方案,并设计、加工,满足广大用户的特殊需要。
水位量无线自动控制设备使用手册型号SC669SWK特别提醒:防止烧坏收发机未接室外天线严禁开机!!!使用前请仔细阅读领会说明书首先,感谢您选用首创系列模拟量和数字量无线传感控制设备,我公司将一如既往地为您提供优质的产品和服务!敬告用户,请您在使用前,仔细阅读本手册!本手册适用于首创水位量无线自动控制设备,阅读时请您留意各型号的说明。
概述水位量无线自动控制设备是一种远端测控单元装置,负责对现场信号、工业设备的监测和控制。
是针对各种应用场合研发的通用型远程终端设备。
广泛应用于石化、油田、炼钢厂、核电站、消防、供水、环保、建筑、电力、采矿业、交通、水泥厂上料送料带连锁启停控制等各个场所,是一种有极高性能的无线远距离数据采集控制产品,可以接各种变送器输出。
水位量无线自动控制设备通常要具有优良的通讯能力和相应的存储容量,适用于更恶劣的温度和湿度环境,提供更多的计算功能,广泛应用于SCADA系统。
首创系列模拟量和数字量无线传感控制设备将现场数据采集、运算、通讯和控制功能有机地结合,为工业监测和控制系统提供快速、简便、低成本、易维护的解决方案。
它采用性能优良的工业级器件生产,集功能强大的控制器、采用世界顶尖高性能无线数传电台、输入输出接口、电源于一体,内置功能强大的监控程序,具有性能卓越、使用方便等有点。
产品特点◆可定制设置无采集端发射信号时被控设备自动停止工作保护功能。
◆SC669SWK型水位量无线自动控制设备可单独完成数据采集及控制,也可通过内置无线数传电台和远端控制中心组网使用,配接相应的液位传感器可检测水池水塔的高低水位;◆采用高性能、高可靠微处理器单元,高精度、高速度转换单元,完全能满足快速、高精度、实时的工业测控场合及要求,输出所需控制信号,控制相应设备PLC、变频器、水泵的启停;◆模块化、积木式结构,可根据输入输出口的数量非常灵活方便地配置内部硬件,从而达到最佳的性能价格比;◆内置首创世界顶尖高性能无线数传电台,有效保证了产品的稳定可靠性;◆可选择交流、直流及电池等多种供电方式;◆支持本地和远端串口通讯;◆工作稳定可靠,抗干扰能力强;◆一体化结构,独立机箱安装;◆工作温度范围宽,适合于恶劣的工作环境。
XW-1型水位仪显示器使用说明书
徐州市伟思信息系统工程研究所
2003年4月
目录
一、概述 1
二、技术参数 2
三、与传感器连接 3
四、显示选择操作 4
五、修改预置值操作 5
六、上中下限报警动作 5
七、使用注意事项 5
八、显示器类型选择 5
九、装箱清单 5
1
XW-1系列水位显示器使用说明
一、概述
XW-1系列显示器为6位LED 数字显示器,可以与WF 系列浮子式水位传感器或其它传感器连接,用来测量显示水位值。
它具有海拔值预置功能,还具有上下限预置功能,可以给出上下限报警信号。
还可以通过本身的RS-485口(XW-1A 型)或4~20mA 电流环(XW-1B 型)远程连接到计算机工业控制网络,用以对水位进行监测。
它具有光电隔离,可适应恶劣电气环境,性能可靠。
其面板形式如图1所示。
水位仪组成示意图如图2所示。
图
2
上中下XW-1系列显示器
二、技术参数
1、水位量程:与传感器相同(10m,20m,40m,80m等)
2、分辨力:与传感器相同(1cm,1mm等)
3、测量精度:与传感器相同,即±0.1%×量程±1cm(或1mm)。
4、显示方式:6位加2位LED显示。
6位为绝对水位(4位相对水位值+6位海拔值)
显示(红),字高0.56”。
2位为通信站号或作为其它符号显示(绿),字高0.3”。
5、传感器与显示器之间连接方式:多芯电缆(14~20芯)。
6、输入码制(传感器输出码制):循环码(葛雷码)或其它码制(需定制)。
7、传感器与显示器之间有线距离:可达2km。
8、数据远传方式(可选):
1) RS-485(XZ-1A型),用一对双绞线传输联网。
数据远传距离:1.2km。
RS-485口通信协议:1)MOD-WS1(MODBUS);2)SDI-12。
2)4~20mA电流环方式(XZ-1B型),用一对导线传输。
以上传输的数据不包含海拔值
9、电流环:分辨力:与传感器相同;非线性:最大±0.012%;最大误差:±0. 15%
10、人工预置功能
1)下限预置:出厂时为零。
(4位,不含海拔)
2)上限预置:出厂时为最大开度值。
(4位,不含海拔)
3)中限预置:出厂时为最大开度值。
(4位,不含海拔)
4)海拔预置:出厂时为零。
(6位)
5)量程(仅XZ-1B型):量程(4位,不含海拔)
6)通信站号预置:出厂时通常设为01。
11、报警、控制功能
报警控制信号:继电器触点。
触点容量:1A24VDC,0.5A125V AC。
当大于等于上、中限、小于等于下限值时,继电器触点吸合,并声、光报警(数
据区小数点闪烁)。
声报警持续时间约10秒钟。
中限仅继电器动作。
12、显示器与传感器耦合:光电隔离
13、工作方式:连续工作。
14、显示器内单片微机加有Watchdog,以防止运行变乱。
15、工作环境温度:0℃~ +50℃,相对湿度:85%(+25℃)。
16、电源:120VAC~ 264VAC,47~440Hz。
功耗:<5W。
保险丝2A。
17、外形尺寸:120×120×120mm。
屏装开孔尺寸:111×111mm。
2
3 三、与传感器连接
与传感器的连接是通过显示器后盖上的DB-25插接件、25芯电缆和传感器端的19芯航空插头实现的。
显示器后盖图如图3所示。
表1 D0~D15为数据线,D0为低位。
VEE 为12V 输出电源+极,G 为公共端(12V-极)。
其他为空脚。
VEE12V 输出电源作为光电编码器电源,额定电流100mA 。
机械传感器非电流环显示器不配此VEE 输出电源。
图3 显示器后盖图
1、继电器1(上限)常开点NO ,
2、继电器1(上限)触点公共端COM ,
3、继电器2(下限)常开点NO ,
4、继电器2(下限)触点公共端COM ,
5、继电器3(中限)常开点NO ,
6、继电器3(中限)触点公共端COM ,
7、485口A 端,
8、485口B 端(只有XW-1A 型配485口),
9、4~20mA 电流环+,10、4~20mA 电流环-(只有XW-1B 型配
4~20mA 电流环),11、DB25插座,传感器输入端,12、220V 电源插座(带保险丝座)。
19芯航空插头脚定义如图4和表2所示。
图4 19芯航空插头(背视图)
4
注:“VEE ”为外接电源正极;“G ”为公共端(电源负极)D0~D14为并行数据线。
显示器与传感器连接好后,既可插上电源。
无电源开关。
此时显示器上应当有数值显示。
四、显示选择操作
显示器开机时默认的显示内容为6位水位值,按循环选择键“■”,可以选择显示其他项目。
每按下一次则切换一个显示项目。
显示项目与选择顺序如图5所示。
图5
总共有以上6个(XZ-1B 型为7个)显示项目。
在站号预置项显示位置时,若继续切换显示项,则返回到水位项(默认显示项)。
显示器的符号LED (两个绿色的LED 数码管)在各个显示项目中显示相应的符号,各项符号和显示内容如下:
显示项目 符号位 数值位内容 水位值 (站号)XX XXXX.XX
上限预置 XX.XX 下限预置
XX.XX 中限预置
XX.XX
海拔预置
XXXX.XX
5
量程预置
XXX.X (仅XZ-1B 型) 站号预置 (站号)XX
五、修改预置值操作
上限、下限、中限、海拔、量程以及站号都可以由用户来修改。
即按循环选择键“■”切换到相应项后,按“●”键便进入修改状态,此时第1位数字闪烁,闪烁位表示该位可以修改。
修改数值使用增数键“▲”或减数键“▲
”。
每按一次增数键,数值加1;每按一次减数键,数值减1。
也可以不修改。
修改完(或不修改)该位后,再按一下选位键“●”,则第2位闪烁,表示可以修改第2位;再按一下选位键,则第3位闪烁;再按,则第4位闪烁;此时如果再按,则又回到第1位闪烁,如此循环切换。
如果从某一位开始后面各位都不必修改,则可以不再按选位键。
修改完毕后,按“■”键确认即可,此时便退出修改状态,回到该项原状态。
注意,对于XW-1B 型显示器,必须将量程项预置成与20mA 对应的数值。
六、上中下限报警动作
当水位值≥上限值时,上限继电器触点吸合;水位值≥中限值时,中限继电器触点吸合;水位值≤下限值时,下限继电器触点吸合。
上中下限均为4位,不含海拔。
与上、下继电器触点吸合的同时,数据显示区的小数点闪烁,蜂鸣器响。
声报警持续时间约10秒钟。
中限报警仅继电器触点吸合。
七、使用注意事项 当传感器超出最大量程时,显示值将不是正确值,而且上中下限继电器可能错误动作。
如果出现故障,请断掉电源。
八、显示器类型选择
表3列出了XW-1系列显示器的主要型号和功能,供参考选型。
表3
九、装箱清单
1、 显示器,1个。
2、 220V 电源线,1根。
3、 DB-25插头1个。
4、 固定支架 2只
5、 测试电缆 每批1根
6、 备份保险丝,2A
7、 显示器使用说明书,1本。