毕业设计(论文)-风电场电气主接线设计与优化华北电力大学本科毕业设计(论文)摘要风力发电作为一种清洁的可再生能源发电方式,已越来越受到世界各国的欢迎,与此同时,风电场设计也备受重视。
虽然风电场电气设计与传统电厂设计的原理相同,但传统的设计方法并不一定适合风电场设计。
所以有必要进行专门针对风电场电气主接线设计的研究。
风电场的电气设计主要包含几个方面:风力发电机组升压方式、风电场集电线路选择、风机(风电机组)分组及连接方式。
现国内外风力发电机组出线电压多为690V,多采用升至35kV方案。
风电场集电线路方案一般采用架空线或电缆敷设方式。
架空线的成本较低,但可靠性较低,电缆的成本高,可靠性也高;集电线路结构有4种常用方案,链形结构;单边环形结构;双边环形结构;复合环形结构。
链形结构简单,成本不高。
环形设计成本较高,但其可靠性较高。
风力发电机分组多为靠风机的排布位置、及结合现场施工的便捷性制定。
作者主要针对风电场电气主接线进行设计和优化,通过对风机的分组和连接方式、风电场集电线路方案、风电场短路电流计算及设备选取等的问题进行深入的计算与讨论,提出一些关于风机分组连接、集电线路设计的可行方案。
并通过现有风电场的数据,对方案进行技术和经济方面的比较,确定最终方案并对其进行优化。
为今后的风电场设计提供一些经验和参考意见, 便于今后找出一套适用于风电场电气主接线设计的方法。
关键词:风电场,电气设计, 集电系统,优化I华北电力大学本科毕业设计(论文)ABSTRACTBy the wind power as one kind of clean renewable energy source the electricity generation way, the design of wind farm has been popular and been paid attention to with the world. Although the electrical design of wind farm and the traditional design technology at the electrical principle is the same, but sometimes the methods are not suitable in fact. So specifically forthe electrical design of wind farm has come into being.The electrical design of wind farm mainly includes several aspects: wind turbine generators, wind energy booster way of electrical collector system, WGTS’s groupand connection. Now the WGTS’s voltage qualifies for 690V, and much taking the voltage to 35kV. Wind farm electrical collector system generally uses the bus or cable.The cost of bus is relatively lower, but reliability is low, cableis high costs and high reliability; The electrical collector system has four common solutions, stringclustering; Unilateral redundancy clustering; Bilateral redundancy clustering;Composite redundancy clustering. String clustering is simple structure, cost is not high. With redundancy design cost is higher, but it has high reliability. For more on WTGS group and combining lay on its location and the convenient of building.We will discuss about the main points of the wind farm electrical design and optimized. It will get some design which is about thegrouping and connection and the connection lines that can be used, by calculating and discussing, include the grouping and connection of the WTGS, the connection lines, the wind farm electrical short-circuitcurrent computation , the equipment selection and so on. We will compare different schemes from the economic and technical aspects based onexciting wind farm data, then optimizing and being sure these plans. These conclusions and viewpoints can be references for the future wind farm design, and be easy finding out a set of way to be suitable the electrical design of wind farm.KEY WORDS: Wind farm, electrical design, electrical collector system, optimizationII华北电力大学本科毕业设计(论文)目录摘要..............................................................................? ABSTRACT..............................................................................? 第1章绪论 (3)1.1研究背景 (3)1.2研究意义 (4)1.3国内外研究现状 (4)1.4本文主要内容...................................................5 第2章风场介绍及主要设备选型 (6)2.1风电场基本资料 (6)2.2电气主接线设计 (6)2.3主要设备选型 (8)2.3.1风电机组的选型 (8)2.3.2风机箱变的选型 (8)2.3.3主变压器的选型................................................9 第3章风电场接线方案比选 (11)3.1概述 (11)3.2集电线路方案比选 (11)3.2.1方案描述及比较 (11)3.2.1.1技术特点 (11)3.2.1.2经济比较 (12)3.2.2结论 (13)3.3风机分组和连接方案的比选 (13)3.3.1方案描述 (13)3.3.2方案比较 (13)3.3.2.1技术比较 (13)3.3.2.2经济比较 (21)3.3.3结论 (21)1华北电力大学本科毕业设计(论文)3.4本章小结............................................................22 第4章短路电流计算及其它电气设备的选取 (23)4.1计算说明 (23)4.2系统等效简化图 (23)4.3短路电流的计算 (24)4.3.1各元件的标幺值 (24)4.3.2 各短路点的短路电流计算 (24)4.4其它电气设备的选取 (26)4.4.1 断路器的选取 (26)4.4.2隔离开关的选取 (28)4.4.3 电压互感器的选取 (28)4.4.4电流互感器的选取 (28)4.5本章小结............................................................30 第5章方案优化 (31)5.1概述 (31)5.2风机分组的优化 (31)5.2.1技术比较 (31)5.2.2经济比较 (34)5.2.3结论 (34)5.3线路优化 (35)5.3.1线路的选择 (35)5.3.2技术比较 (35)5.3.3经济比较 (38)5.3.4结论……………………………………………………38 5.4本章小结………………………………………………………………39 结论……………………………………………………………………40 参考文献..............................................................................41 附录..............................................................................42 致谢 (45)2华北电力大学本科毕业设计(论文)第1章绪论1.1 研究背景风能是一种无污染的、储量丰富的可再生能源。
关于风电场接入系统电网一次部分研究随着风电装机规模的不断扩大,风电场接入电网的问题越来越引起人们的关注。
在风电场与电网连接过程中,涉及到的问题包括电压质量、电流变化、频率稳定性等。
本文将对风电场接入电网一次部分进行研究,探讨风电场接入电网的情况,分析其对电网的影响,并提出相应的解决方案。
一、风电场接入电网的情况风电场接入电网需要考虑的问题有很多。
其中一点就是风电机组与电网之间的电气连接问题。
风电机组通过电气连接将自己与电网连接起来,从而使其发电功率输出到电网中。
不同的风电机组会采用不同的电气连接方式,主要分为两种:1. 直接型电气连接:将风电机组通过电气系统直接连接到电网中。
2. 变流型电气连接:将风电机组通过变流器将发电机输出的电流转换为电网所需的电流。
在这两种电气连接方式中,直接型电气连接相对简单可靠,但其控制性能较差,不能满足灵活性要求;而变流型电气连接则能够对电压和频率进行调节和控制,但其连接部分有大量的电子元器件,容易出现设备故障。
风电场接入电网,会对电网造成一定的影响。
这主要表现在以下几个方面:1. 电压波动:对于直接型电气连接的风电机组,当风电场的电功率突然改变时,电压波动会出现。
这种现象被称为电气冲击。
2. 电流变化:风电机组的运行状态也会导致电流的变化。
如果电网无法有效地控制和调整电流,会引起电压和频率的变化。
3. 频率稳定性:风电机组具有随风速、发动机转速、风轮叶片角度等参数变化而变化的特点,这种变化在一定程度上会影响电网的频率稳定性。
以上这些问题,都需要风电场在接入电网时进行考虑和解决。
三、解决方案为了解决上述问题,需要采取一系列的措施。
下面针对每个问题提出解决方案。
1. 解决电压波动问题电压波动是由于电网电容冲击引起,解决方法包括增加电容存储能量,提高电网综合阻尼等。
电流变化会导致电网电压和频率的变化,解决方法包括在输电线路上增加补偿电容,控制风电场的投入和退出等。
3. 解决频率稳定性问题风电场对电网频率的影响导致电网的频率稳定性不好,解决方法包括增加系统惯性、提高发电机系统控制精度等。
摘要(zhāiyào)风能作为(zuòwéi)一种清洁能源,现在已越来越受到各个(gègè)国家重视。
虽然(suīrán)风电场主接线设计与常规的设计原理几乎一样,但是由于其本身的装机容量小等原因,又与常规的设计有一定的区别。
此次风电场主接线设计主要包括以下几方面:方案的设计及确定、风电场设备的选取、短路电流计算和开关器件的选取及校验。
风力发电机出口电压一般为690v,通过箱式变压器升高到35kv,并通过架空线连接到升压变电站,主变压器升高到110kv,送入电网。
计算电压偏移,来校验导线的性能。
计算三相短路电流,来校验开关器件是否满足要求。
本次的风电场设计方案采用的双母线接线方式,适合于能够扩建的电厂。
只建设一期工程的风电场不适用于本次设计。
关键词:风电场,主接线设计,集电线路第一章绪论(xùlùn)1.1 研究(yánjiū)背景随着煤炭等化石能源(néngyuán)渐渐的枯竭,风能作为一种清洁的可再生能源已经越来越受到各个国家的重视。
2013年3月,中国(zhōnɡɡuó)可再生能源学会风能专业委员会发布了中国总体装机情况,中国在2013年新增装机容量为16088.7MW,同比增长24.1%,累计装机容量为91412.89MW,同比增长21.4%,为世界第一。
这些数据表明我国正大力发展风力发电这项产业。
但由于我国的风电产业起步较晚,相应的技术不成熟,所以在我国的很多风机制造企业的风力发电机都需要从外国风机制造商引进技术。
在我国缺少能够真正自主研发且性能稳定的风机制造商。
2013年全球风电的累计装机容量已达到318.137GW,新装机容量每年都在快速的提升,这说明风电产业在全球都在快速发展。
以丹麦的vistas、美国的ge、西班牙的gamasa等公司为其中的龙头。
欧洲的风电事业起步早、技术成熟,在全球的风机市场占有很高的份额。
大型风电场升压站 220kV电气主接线方式探讨摘要:风力发电通过风电场内部的功率汇集系统将风能转化而来的电能汇集从而注入电网,在不同投资预算情况下,可采用可靠性不同的汇集拓扑结构。
可靠性是风电场功率汇集拓扑在规定条件下无故障地完成其功能的概率,是汇集系统完备性的最佳度量。
功率汇集系统可靠性直接关系到风电场注入电网能量的多少,也与风电场的投资收益设置及电力系统的安全稳定运行密切相关。
国内外已有不少学者对风电场功率汇集拓扑的投资经济性和新型的直流汇集方式开展了研究工作,但对可靠性的关注较弱。
基于目前的技术水平特别是直流电力电子变换技术的局限,风电场较少采用直流汇集的方式,传统的交流汇集方式仍是现在的主流,且电缆和开关仍是制约汇集系统可靠性的主要因素。
将风电汇集拓扑的内部损耗、经济性、可靠性等各项指标分别进行定量分析比较,但对可靠性的评价采用简单的串联累加模式,缺乏对冗余接线的深入研判。
比较多个风电场组合的功率汇集方式(链型、辐射型和混联型)在可靠性、经济性和技术性方面的优缺点,但未以风电场内部功率汇集拓扑为重点。
关键词:大型风电场;升压站;220kV;电气主接线方式;探讨引言长期以来,智能变电系统迅速发展,在发展建设中不断增加投资力度,合并单元智能终端转变规划,变电站电压输出引导设计的思路。
对于智能变电系统双母线接线形式220kV系统二次电压配置设备,在单一接口的设计方案中存在一定的问题,在运行和管理中需要有效的设计方案来支撑,维护电网运行的可靠性与经济性的整合。
针对这样的现实状态和理论依据,需要做出相应的设计配备和改良措施。
1、风电场与常规发电厂的区别及其特殊性1.1区别风力发电单机的容量较小,而常规火电厂的单机容量要比风力发电单机的容量大很多。
风力发电机的出口电压相对较低,需要经过变压器将电压升高到要求的电压值才能够投入使用,而常规火电厂的发电机则不需要利用变压器来提高需要的电压。
风的波动性较大,需要无功补偿装置来为电压的幅值变化进行补偿,保证电压的稳定性,而常规的电厂则不需要无功补偿装置来保证电压的稳定性。
摘要风力发电作为一种清洁的可再生能源发电方式,已越来越受到世界各国的欢迎,与此同时,风电场设计也备受重视。
虽然风电场电气设计与传统电厂设计的原理相同,但传统的设计方法并不一定适合风电场设计。
所以有必要进行专门针对风电场电气主接线设计的研究。
风电场的电气设计主要包含几个方面:风力发电机组升压方式、风电场集电线路选择、风机(风电机组)分组及连接方式。
现国内外风力发电机组出线电压多为690V,多采用升至35kV方案。
风电场集电线路方案一般采用架空线或电缆敷设方式。
架空线的成本较低,但可靠性较低,电缆的成本高,可靠性也高;集电线路结构有4种常用方案,链形结构;单边环形结构;双边环形结构;复合环形结构。
链形结构简单,成本不高。
环形设计成本较高,但其可靠性较高。
风力发电机分组多为靠风机的排布位置、及结合现场施工的便捷性制定。
作者主要针对风电场电气主接线进行设计和优化,通过对风机的分组和连接方式、风电场集电线路方案、风电场短路电流计算及设备选取等的问题进行深入的计算与讨论,提出一些关于风机分组连接、集电线路设计的可行方案。
并通过现有风电场的数据,对方案进行技术和经济方面的比较,确定最终方案并对其进行优化。
为今后的风电场设计提供一些经验和参考意见, 便于今后找出一套适用于风电场电气主接线设计的方法。
关键词:风电场,电气设计, 集电系统,优化ABSTRACTBy the wind power as one kind of clean renewable energy source the electricity generation way, the design of wind farm has been popular and been paid attention to with the world. Although the electrical design of wind farm and the traditional design technology at the electrical principle is the same, but sometimes the methods are not suitable in fact. So specifically for the electrical design of wind farm has come into being.The electrical design of wind farm mainly includes several aspects: wind turbine generators, wind energy booster way of electrical collector system, WGTS’s group and connection. Now the WGTS’s voltage qualifies for 690V, and much taking the voltage to 35kV. Wind farm electrical collector system generally uses the bus or cable. The cost of bus is relatively lower, but reliability is low, cable is high costs and high reliability; The electrical collector system has four common solutions, string clustering; Unilateral redundancy clustering; Bilateral redundancy clustering; Composite redundancy clustering. String clustering is simple structure, cost is not high. With redundancy design cost is higher, but it has high reliability. For more on WTGS group and combining lay on its location and the convenient of building.We will discuss about the main points of the wind farm electrical design and optimized. It will get some design which is about the grouping and connection and the connection lines that can be used, by calculating and discussing, include the grouping and connection of the WTGS, the connection lines, the wind farm electrical short-circuit current computation , the equipment selection and so on. We will compare different schemes from the economic and technical aspects based on exciting wind farm data, then optimizing and being sure these plans. These conclusions and viewpoints can be references for the future wind farm design, and be easy finding out a set of way to be suitable the electrical design of wind farm.KEY WORDS: Wind farm, electrical design,electrical collector system, optimization目录摘要 (Ⅰ)ABSTRACT (Ⅱ)第1章绪论 (3)1.1研究背景 (3)1.2研究意义 (4)1.3国内外研究现状 (4)1.4本文主要内容 (5)第2章风场介绍及主要设备选型 (6)2.1风电场基本资料 (6)2.2电气主接线设计 (6)2.3主要设备选型 (8)2.3.1风电机组的选型 (8)2.3.2风机箱变的选型 (8)2.3.3主变压器的选型 (9)第3章风电场接线方案比选 (11)3.1概述 (11)3.2集电线路方案比选 (11)3.2.1方案描述及比较 (11)3.2.1.1技术特点 (11)3.2.1.2经济比较 (12)3.2.2结论 (13)3.3风机分组和连接方案的比选 (13)3.3.1方案描述 (13)3.3.2方案比较 (13)3.3.2.1技术比较 (13)3.3.2.2经济比较 (21)3.3.3结论 (21)3.4本章小结 (22)第4章短路电流计算及其它电气设备的选取 (23)4.1计算说明 (23)4.2系统等效简化图 (23)4.3短路电流的计算 (24)4.3.1各元件的标幺值 (24)4.3.2 各短路点的短路电流计算 (24)4.4其它电气设备的选取 (26)4.4.1 断路器的选取 (26)4.4.2隔离开关的选取 (28)4.4.3 电压互感器的选取 (28)4.4.4电流互感器的选取 (28)4.5本章小结 (30)第5章方案优化 (31)5.1概述 (31)5.2风机分组的优化 (31)5.2.1技术比较 (31)5.2.2经济比较 (34)5.2.3结论 (34)5.3线路优化 (35)5.3.1线路的选择 (35)5.3.2技术比较 (35)5.3.3经济比较 (38)5.3.4结论 (38)5.4本章小结 (39)结论 (40)参考文献 (41)附录 (42)致谢 (45)第1章绪论1.1 研究背景风能是一种无污染的、储量丰富的可再生能源。
风电场电网连接技术研究与实现随着环境保护和可再生能源的重要性日益凸显,风力发电成为了越来越受关注的领域。
风电场的电网连接技术是风力发电系统不可或缺的一部分,对于实现可靠、高效、安全的电力输送起着重要的作用。
本文将从风电场电网连接技术的研究与实现角度进行探讨。
一、风电场电网连接技术的研究意义风电场电网连接技术是将风力发电场的电能与城市电网连接起来的关键技术,不仅直接影响到风力发电的可靠性与功率输出,还对电力系统的稳定运行和智能化调度等方面产生重要影响。
因此,研究风电场电网连接技术对于提高风力发电系统的经济性和可靠性具有重要意义。
二、风电场电网连接技术的分类风电场电网连接技术可以按照电网类型、连接方式、电力传输方式等多种方式进行分类。
根据电网类型,可以将风电场电网连接技术分为交流电网连接技术和直流电网连接技术。
根据连接方式,可以将其分为集中式连接和分布式连接。
根据电力传输方式,可以分为常规传输技术和海底电缆传输技术等。
三、风电场电网连接技术的关键难题在实际应用中,风电场电网连接技术面临着一些重要的技术难题。
一是电压和频率的稳定性问题,由于风能的不稳定性,风电场电网连接需要应对电压和频率的波动。
二是电网运行的安全和稳定问题,风电场的并网会对电力系统产生一定的影响,需要合理地调整放电功率和频率等参数。
三是实现大规模风电场的并网问题,如何高效地将分布式风力发电单元进行并网连接是一个复杂而重要的问题。
四、风电场电网连接技术的研究方法在研究风电场电网连接技术时,可以采用理论分析和仿真模拟相结合的方法进行。
理论分析可以通过建立数学模型和物理模型来研究风电场电网连接技术的特性和影响因素。
仿真模拟可以借助计算机软件,模拟不同条件下的电网连接情况,以评估其性能和可靠性。
五、风电场电网连接技术的实现方案在实现风电场电网连接技术时,可以采用一些关键技术和装置来提高系统的安全性和稳定性。
一是采用智能型开关技术,可以对电流和电压等参数进行精确控制。
电气基础综合设计
实训报告
课程名称:风力发电厂电气主接线设计专业:新能源科学与工程
班级:
学号:
学生姓名:
目录
一、风电场基本资料 (2)
二、电气主接线设计 (3)
图一 (3)
图二 (4)
三、主要设备选型 (4)
1. 风电机组的选型 (4)
2.风机箱变得选择 (5)
表二 (5)
3.主变压器的选型 (6)
表三 (6)
一、风电场基本资料
现设计风电场使用1.5MW双馈型风力发电机机组33台,总装机容量
49.5MW,风电场集电采用34KV线路,分布在大约30平方公里的丘陵上,33台风电机组设计分五个集电回路,线路总长约28公里。
风电场有110KW升压站一座,主变压器为容量63000KVA,电能输出采用110KV架空线路。
电能由风电场升压经变电站往变电所输出。
二、电气主接线设计
介于风电场的容量较小,且配有一个主变得情况,宜选用单母线接线方案。
此方式有着接线简单清晰,设备少,操作简单和便于扩建的优点,适用于此电场的主接线设计方式,电场的主接线图如下:
图一
图二
三、主要设备选型
1. 风电机组的选型
现选择由中国南车集团出产的YFF06型1.5MW风冷双馈风力发电机,具体数据如表一:
2.风机箱变得选择
风机出口电压为690V,所以需要为风机提供一变压器以达到集电线路的额定电压,具体数据如表二:
风力发电机箱变参数
表二
3.主变压器的选型
风电场的总容量为49.5MW。
所接电网电压为110KV,以次数据选择主变压器,具体数据如表三:
风电场主变压器参数
表三。
2018年5月风电场电气主接线的探讨
刘亚楠(中国电建集团江西省电力设计院有限公司)
【摘要】随着风电的发展,风电场电气也受到了业界关注。
风电场主接线设计与常规设计的原理是相同的,但是由于风电场自身的特点,其与常规设计之间又有着一定的区别。
本文将从风电场电气设计的特点及基本原则出发,对风电场电气主接线进行深入探讨,旨在为风电场电气设计提供参考。
【关键词】风电场;电气设计;主接线;原则
【中图分类号】TM645【文献标识码】A【文章编号】1006-4222(2018)05-0198-02
风力发电方式作为一种清洁、可再生能源发电方式,受到了越来越多的关注。
风电场电气主接线设计通常情况下所使用的设计原理与常规电厂的设计原理是相同的,但是又由于风电场的一些特殊性特点,应当对风电场电气主接线展开进一步研究,在提升风电场设计质量的同时为风力发电的发展奠定良好基础。
1风电场与常规发电厂的区别及其特殊性1.1区别
风力发电单机的容量较小,而常规火电厂的单机容量要比风力发电单机的容量大很多。
风力发电机的出口电压相对较低,需要经过变压器将电压升高到要求的电压值才能够投入到使用,而常规火电厂的发电机则不需要利用变压器来提高需要的电压。
风的波动性较大,需要无功补偿装置来为电压的幅值变化进行补偿,保证电压的稳定性,而常规的电厂则不需要无功补偿装置来保证电压的稳定性。
1.2特殊性
风电场具有一定的特殊性,由于其所处的地带相对较为偏僻,分布的方式相对较为分散,在主接线设计的过程中需要将多台风机接入到线路中,因此,在设计的过程中需要考虑更多集电线路与母线的连接,并考虑变电器升压的连接,以保证线路的稳定性[1]。
1.3风电场电气设计原则
风电场电气主接线的设计应当要遵循先进性原则(如:技术的先进性、设备先进性、理念的先进性等)、可持续发展性原则(如:工程长期发展规划、近期发展规划等)、节约环保原则(如:节约用地、场区环境保护、降低能耗等)。
在这些原则的基础上展开主接线设计,能够在最大程度上做到节能、环保、降耗、高效。
2风电场电气主接线设计
2.1风电场电气主接线方式
①单元接线方式。
该方式是指将发电机与变压器直接连接到一起,该方式是最为简单的接线方式,其特点是几个元件单独连接,中间没有任何横向连接。
②桥型连接方式。
桥型连接方式分为两种,一种是内桥方式,另一种是外桥方式。
其中内桥接线方式主要用于线路过长、线路故障频发处,而外侨连接方式主要用于变压器故障频发、线路短路等情况中。
③单母线分段连接方式。
单母线分段连接方式具有一定的优点,其可以通过两个电源来供电,当母线发生故障的时候,减小停电的范围。
但是这种方式也有一定的缺点,如:在任意一个断路器检修的时候,所有的线路都需要停电。
在实际应用的过程中,若是对可靠性要求不高的情况下,可以采用分段隔开开关的方式,若是对可靠性的要求较高,那么就可以采用分段断路器来进行设计。
④双母线连接方式。
双母线连接方式的优点有很多,如:可靠性较高、调度较为灵活,当母线发生故障的时候不
需要全面停电来进行检查,当风电场扩建的手也不需要均衡
扩建。
但是该方式也有一定的缺点,如:倒母操作相对较为复
杂,容易出现问题,对人身安全以及设备安全产生影响;同时,
线路中的隔离开关量也大幅度增加[2]。
如图1所示,该图所展示的是单母线分段接线方式,图2所展示的是双母分段线接
线方式。
2.2风电场电气主接线设计要点
①风电场高压侧主接线。
在风电场高压侧,其接线方式主要有单元接线方式以及单母线接线方式两种方式,基于单个风电场电能的升压站,应当要采用单元接线方式和但母线接线方式两种形式,而基于多个风电场电能的升压站,应当要采用单母线接线方式或是单母线分段接线方式,以此来保证高压输出的稳定性。
②风电场低压侧主接线。
风电场低压侧的主接线方式通常采用单母线分段连接方式,且分段的段数应当要与主变压器的数量保持一致,以保证党主变压器检修的时候,母线段的风机能够继续输出电能。
③风电场场用电
主接
图
1
图2
电力讯息198
2018年5月
线。
在通常情况下,场用电系统应当要使用三相四线制的接线方式,并根据升压站的电压来选择合适的接线方式,如:单母线分段接线应用给予220kW的升压站;单母线接线应用于110kW升压站[3]。
2.3主接线设备的选择
主接线设备的选择是主接线设计中应当要考虑的重点环节之一,科学合理的设备选择能够提高线路的运行效率,在一定程度上降低维修的次数,降低故障发生的频率,并达到节能降耗的目的。
风电场相关设备包括箱式变压器、主变压器以及架空导线等。
①箱式变压器的选择。
在箱式变压器容量的选择上,除了要能够满足发电机额定功率以及机组本身所需要的电量外,同时还要留出一定的裕度,约为10%左右。
通常情况下,当机组的容量不大于1500kW的时候,会采取单元接线的方式来配置美式箱变;当机组的容量大于1500kW的时候,所配置的箱变类型通常为欧式箱变。
②主变压器。
主变压器与变电所之间的连接通常会采用外桥连接方式,两个主变压器之间相互为备用的关系,当其中一个出现故障或是由于其他原因需要退出运行的时候,另外一个主变压器也能够承担大部分的电量传输工作。
③架空导线。
架空导线的选择应当要建立在基本条件的基础上,包括横截面积、机械强度、电压损耗以及发热条件等。
导线的横截面积是根据电流的密度来计算的,包括经济电流以及工作电流。
导线需要具有一定的机械强度,若是强度较低,则在使用的过程中很容易出现拉断的情况,影响线路的稳定性。
此外,导线本身的电阻和热效应会是导线的温度升高,破坏了导线的绝缘层,加速导线老化,影响导线的正常使用[4]。
由此可见,在选择导线型号的过程中,应当要选择允许通过的电流值大于计算出的电流值的导线,同时根据温度的变化来进行适当校正。
3结束语
综上所述,风电场设计将会影响到风电场的稳定运行,而电气主接线设计是影响风电场整体设计效果的重点内容。
因此,相关设计人员应当要在了解风电场电气设计特殊性的基础上,基于一定的设计原则,对风电场电气主接线进行设计,选择正确的主接线方式,注重每个环节的设计要点,并选择适当的主接线设备,以提升风电场电气主接线的设计质量。
参考文献
[1]刘洋,刘孟歆.风力发电场电气主接线设计[J].农村电气化,2017 (11):9~10.
[2]郑明.300MW海上风电场电气主接线设计[J].南方能源建设,2015,2
(03):62~66.
[3]石巍,张彦昌.风电场电气主接线的探讨[J].电力勘测设计,2015 (S1):327~331.
[4]石巍,张彦昌.风电场电气主接线的探讨[J].电气时代,2013(05): 72~76.
收稿日期:2018-4-22
作者简介:刘亚楠(1989-),硕士研究生,主要从事风电场电气设计工作。
电力调度的安全管理及电能质量控制对策张艳(国网四川省电力公司喜德县供电分公司,四川喜德县616750)
【摘要】随着社会经济的不断发展以及城市化进程的不断加快,人们的生活水平有了质的飞跃,对于电力调度的安全管理以及电能质量的控制消耗提出了更高的要求。
就当前实际状况来看,我国的电力调度系统仍旧存在诸多的漏洞。
但是,电力系统能够为人们生活质量的提升与社会经济的发展提供有力保障,基于此,分析电力调度安全管理以及电能质量控制的有效对策是当前相关部门的重点工作。
因此,本文笔者结合多年实际工作经验,首先对当前电力调度安全管理存在的问题进行讨论,接着给出有效的解决对策,最后对电能质量控制的有效措施进行分析,望借此为实际工作提供参考的依据,从而提高电力系统供电的稳定性与质量。
【关键词】电力调度;安全管理;电能质量;控制措施
【中图分类号】TM73【文献标识码】A【文章编号】1006-4222(2018)05-0199-02
1引言
随着城市化进程的不断加快,各行各业对于电能的需求不断增加,这给电力企业带来广阔发展前景的同时,也使得电力企业面临的挑战与考验不断增多。
如果在电网日常管理工作中相关管理制度或安全施工落实不到位,一旦电力系统发生故障,不仅影响电力系统的正常供电,而且给电力系统运行的稳定性产生不利影响,从而引发安全事故,给电力企业带来经济与人员损失的同时,也影响了人们的正常生活。
基于此,如何提高电力调度安全管理以及电能质量控制的效果,是当前相关部门亟待解决的问题。
下面本文就此展开重点讨论与分析。
2当前电力调度安全管理存在的问题根据相关调查资料,结合电力调度安全管理工作的性质以及特点,不难看出电力调度安全管理工作存在问题主要包括两大类,即电力调度安全管理人员自身的原因以及电力企业的原因;而具体来看,可以将电力调度安全管理工作存在问题的主要概括为下面六个部分,其中包括:
(1)电力调度安全管理人员没有定期维护或者更新电网中的相关电力设备,从而导致误调度现象出现的频率不断增加,从某种意义上来说给后期设备的维修与检测工作增加了难度;不仅如此,有些居民在已经建立完成的电力线路范围内大量修建房屋或者种植庄稼等,给电力区域造成不同程度的污染,从而大幅缩减电力设备的使用时间。
(2)电力调度安全管理人员职业素养以及综合素质有待提高,在实际电力调度工作中无法对电力调度安全管理的好坏进行正确的判断与认识,从而导致时常出现误调度现象。
(3)电力调度安全管理人员对事故发生的基本预案以及应急措施没有进行全面的掌握与了解,当面对电网事故的时
电力讯息199。