特灵风机盘管机组技术参数
- 格式:pdf
- 大小:4.53 MB
- 文档页数:32
机组型号说明H F C F 0 3 L 3 0 N 1 0 A 0 A 0 0 V_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18序号1:H = 水平吊挂; 序号2: F = 风机盘管序号3: C = 暗装式序号4: F = 设计号序号5,6:名义风量,单位CMH 02 = 340 CMH 03 = 510 CMH 04 = 680 CMH 05 = 850 CMH 06 = 1020 CMH 08 = 1360 CMH 10 = 1700 CMH 12 = 2040 CMH 14 = 2380 CMH 序号7:左右手接管位置(面对出风) L = 左式R = 右式序号8:盘管排数 2 = 2排冷盘管 3 = 3排冷盘管4 = 4排冷盘管 A = 2排冷热盘管,1排热盘管 B = 3排冷热盘管,1排热盘管序号9:电加热0 = 无电加热 A = 配0.5kW 电加热器(02) B = 配1.0kW 电加热器(03) C = 配1.4kW 电加热器(04) D = 配1.6kW 电加热器(05) E = 配1.8kW 电加热器(06) F = 配2.8kW 电加热器(08) G = 配3.2kW 电加热器(10) H = 配3.6kW 电加热器(12) J = 配4.6kW 电加热器(14) 序号10:电机形式N = 标准静压H = 高静压 A = DCBL标准静压(附液晶面板)B = DCBL高静压(附液晶面板)C = 密闭型标准静压 D = 密闭型高静压序号11:电压/ 赫兹/ 相 1 = 220/50/1序号12:控制水阀形式0 = 不配水阀A = 2管制,2通水阀B = 2管制,3通水阀C = 4管制,2通水阀D = 2管制,含液晶面板,2通水阀 E = 2管制,含联网型(VWV 系统)液晶面板,2通水阀 F = 2管制,含液晶面板,3通水阀G = 4管制,含液晶面板,2通水阀序号13:控制盒类型A = 标准接线盒B = 带电加热控制的接线盒C = DCBL 控制D = ZN控制E = VWV 控制(标准的风机盘管) 序号14:回风箱/ 过滤网0 = 不带回风箱,不带过滤网 A = 带后回风箱,不带过滤网 B = 带后回风箱,带6mm 尼龙过滤网 C = 带后回风箱,带20mm 铝制过滤网D = 带下回风箱,不带过滤网 E = 带下回风箱,带6mm 尼龙过滤网 F = 带下回风箱,带20mm 铝制过滤网序号15 :水盘长度及材料 A = 普通水盘,标准长度。
特灵中央空调产品技术说明空调系统1.0螺杆式冷水机组特灵rthd系列螺杆式冷水机组由一个半密封式直接传动螺杆压缩机,冷凝器,微处理器控制,膨胀阀,带检修阀的制冷剂过滤器,绝缘弹簧,流量开关,液量测量装置和悬挂压缩机电机启动器组成;出厂前通过检验并可随时运行,机组符合ARI 标准,额定频率为50HZ。
压缩机半密封式,直接传动,3000rpm,由滑阀控制功率的水平旋转压缩机,油槽加热器和冷冻油压差系统。
润滑系统润滑滚动轴承组件支撑旋转组合。
系统有一个由微处理器控制的油槽加热器。
电机电机有一个冷气抽气机,密封,双杆,鼠笼式感应电动机。
电机可在415V/50HZ/3Ph电源,3000Rpm转速下工作。
电机是WYEDELTA连接。
蒸发器-冷凝器组蒸发器壳是碳钢板,蒸发器和冷凝器管的替换相对独立的,标准管道是外肋铜管与翅片连接,内表面完美无缝。
水箱设计可承受300psig(2067kPa,1psig=6.89kPa)的压力。
流水侧在1.5倍的设计工作压力下进行静液测试。
微处理器控制面板微处理器控制面板是出厂前进行安装并通过测试的。
通过控制能源转换器提供控制系统能源。
控制器通过压缩机滑阀来加载或卸载冷水。
微处理器自动控制回流水,避免由于蒸发器制冷剂温度低,冷凝温度高,电机电流过载非正常操作的条件引起的停机。
如果非正常操作条件持续和达到保护极限,机器将会停机。
以下情况会造成机器停机保护,需要手工复原:●蒸发器制冷剂温度、压力低;●冷凝器制冷剂压力高;●油位低;●传感器或回路检测错误;●电机电流过载;●压缩机卸载温度高;●各部件失去连接;●电子输送错误:无电压,相不平衡,变相;●外部或当地紧急停电;●启动转换器坏了。
以下情况,机器会自动停机保护:·` `●短暂的能源缺失●低/高压●蒸发器或冷凝器水流没有了如果发生一次故障,会有超过100次的诊断。
显示器会指出错误,要求复原,显示诊断时间和日期,诊断时运行的机器状态,和帮助信息。
LWHA水平吊顶式空气处理机组皮带风机湿膜加湿器(自选)制热盘管(自选)制冷盘管电动机和皮带轮冷凝水排出口水出口水入口December 2005October 2006LWHA机组技术参数表LWHA机组技术规格LWHA机组性能表—制冷量压降kpa 15.521.943.955.044.160.213.623.432.645.2总热kW 7.714.119.925.932.239.442.352.765.578.8显热kW 5.910.614.919.424.129.132.138.948.258.3流量l/s 0.370.680.951.241.541.892.02.53.13.8压降kpa 6.39.319.023.719.026.68.915.718.622.4总热kW 10.418.726.133.942.351.055.668.286.1105.2显热kW 7.712.717.923.228.934.739.347.959.072.4流量l/s 0.500.891.251.622.022.442.73.34.15.0进风干湿球温度27℃/19.5℃4排6排LWHA 型号013023033043053063080100120150送风量m 3/h130023003300430053006300800095001200015000总热kW 19.835.445.859.276.390.3106.7128.8167.4191.5显热kW 8.314.819.324.932.037.943.152.062.477.3流量l/s 0.951.691.782.253.203.505.16.18.09.1压降kpa 34.348.157.868.470.480.144.574.896.2106.4总热kW 24.042.255.271.491.5108.2133.1160.0200.1244.0显热kW 9.917.522.929.737.944.953.464.180.298.0流量l/s 1.101.781.772.253.203.506.47.69.611.6压降kpa 63.674.581.297.599.4113.462.4103.9142.9197.84排6排进风干湿球温度34℃/28℃LWHA机组性能表—加热盘管进风温度-4℃进风温度5℃进风温度-12℃热水进出水温度60℃/50℃2排总热kW 15.126.936.147.860.873.588.1106.6133.5163.01排总热kW 8.014.419.125.933.240.853.064.280.297.12排总热kW 12.622.530.240.151.061.873.889.5112.1136.91排总热kW 6.311.615.621.327.333.844.353.767.181.42排总热kW 17.430.941.454.769.583.9100.8121.8152.6186.11排总热kW 9.416.922.229.938.447.060.873.591.7111.2进风温度-4℃进风温度5℃进风温度-12℃2排总热kW 21.438.251.267.986.3104.6124.9151.3189.6231.41排总热kW 11.019.926.536.146.357.074.790.6113.1137.12排总热kW 18.933.745.260.276.592.8110.5134.1168.1205.31排总热kW 9.317.123.031.540.450.066.080.1100.0121.32排总热kW 23.742.156.574.895.0115.0137.6166.5208.7254.61排总热kW 12.422.329.640.151.463.382.599.8124.7151.1LWHA 型号013023033043053063080100120150m 3/h 130023003300430053006300800095001200015000送风量热水进出水温度90℃/70℃备注:外形尺寸中长度尺寸“/”前表示A型机组长度,“/”后表示B型机组长度。
风机盘管技术参数表
1. 额定回风供冷工况:进风干球27℃,湿球温度19.5℃,进水温度7℃,进出水温差5℃;
2. 额定回风供热工况:进风干球21℃,进水温度60℃;
3. 以上表中风量、供冷全热/显热、供热量均基于YGFC-H 系列卧式暗装型机组不带任何附件,若增加附件(如回风箱,过滤网等),参数会有衰减。
对于VC 型机组相应数据需乘以修正系数(风量的修正系数为0.95,供冷全热/显热量、供热量的修正系数请参阅上表)。
CE/VE 型机组的风量同卧式暗装型。
4. 四管制机组的热水盘管进出水管径为Rc1/2。
5. 静压类型:S 标准型(12Pa )、H 高静压型(30Pa )、U 超高静压型(50Pa)。
6. 直流无刷电机仅适用于CC/CB/CD 机组,S/H/U 三种静压通用(出厂默认设置为S 型,客户可根据需要自行设定);详细性能参数,请参见选型软件。
7.表中机组重量为交流电机机组重量,直流无刷电机机组重量需在上表数据上增加3.5公斤。
8. 表中机组噪声值基于机组不带附件(如回风箱,过滤网等)时在半消声室中按GB/T19232
标准测试所得。
4。
风机盘管详细参数风机盘管是一种采用风扇驱动循环空气并通过冷热水管道进行换热的设备。
它主要由风机、换热器、水泵、阀门、温度传感器等组成。
以下是风机盘管的详细参数。
1.风机参数:风机盘管使用的风机一般采用直流风机或交流风机。
直流风机的功率一般在30W到300W之间,噪音一般在25dB(A)到50dB(A)之间,风量可调。
交流风机的功率一般在100W到1000W之间,噪音一般在35dB(A)到65dB(A)之间,风量可调。
2.换热器参数:换热器是风机盘管中最重要的组件之一,它通过冷热水管道实现热交换。
换热器的材料一般采用铜管和铝翅片,具有良好的热传导性能和耐腐蚀性能。
换热器的换热面积一般在0.5m²到2m²之间。
3.水泵参数:水泵是风机盘管的另一个核心组件,它负责将冷热水输送到换热器中进行热交换。
水泵的功率一般在50W到500W之间,流量一般在0.5m³/h到2m³/h之间,工作压力一般在0.5MPa到1.5MPa之间。
4.阀门参数:阀门是控制风机盘管的冷热水流量和温度的关键组件。
常见的阀门类型包括电动阀、手动阀和比例阀等。
电动阀一般采用24V电压控制,功率在3W到10W之间;手动阀采用手动操作,可以手动调节冷热水的流量;比例阀则通过电信号调节冷热水的流量和温度。
5.温度传感器参数:温度传感器用于监测风机盘管的冷热水温度。
常用的温度传感器包括热电偶和温度传感器。
热电偶的测温范围一般在-200℃到1200℃之间,精度一般在0.1℃到1℃之间;温度传感器的测温范围一般在-40℃到150℃之间,精度一般在0.1℃到0.5℃之间。
6.其他参数:除了以上主要参数外,风机盘管还有一些其他参数,如整机功率、噪音、外形尺寸、重量等。
整机功率一般在100W到2000W之间,噪音一般在25dB(A)到60dB(A)之间,外形尺寸一般在900mm×600mm×300mm到2000mm×1500mm×600mm之间,重量一般在30kg到200kg之间。