"G"提供过压保护功能:280±5%V AC 仅适用于1P+N 和2P 产品脱扣指示DZ47LE 上有剩余电流动作脱扣指示,复位按钮弹起,为漏电脱扣手动控制:手柄允许两种复位模式过电流故障:断路器和剩余电流动作装置同时复位漏电故障:剩余电流动作装置先复位,断路器后复位机械寿命:2000次电气寿命:2000次环境温度使用环境温度:-5℃~+40℃接线6~32A ,可接16mm 2 及以下导线40~60A ,可接25mm 2 及以下导线安装符合标准:IEC61009-1 / GB16917.1符合认证:CCC 认证脱扣特性B 型曲线保护短路电流较小的负载(如电源、长电缆等)脱扣特性:瞬时脱扣范围 (3~5) InC 型曲线保护常规负载和配电线缆脱扣特性:瞬时脱扣范围 (5~10) InD 型曲线保护起动电流大的冲击性负荷 (如变压器等)脱扣特性:瞬时脱扣范围 (10~14) In技术参数50, 60444额定电流:6,10,16,20,25,32,40,50,60 A 额定工作电压:230/400V AC 额定绝缘电压:500V额定剩余动作电流:30,50,75,100,300mA分断能力40~60M52.54.52.0DZ47LEN1B10DZ47LEN1B16DZ47LEN3B10DZ47LEN3B16DZ47LEN3B20DZ47LEN3B25DZ47LEN3B32DZ47LEN3B40DZ47LEM3B50DZ47LEM3B60DZ47LEN6B6DZ47LEN6B10DZ47LEN6B16DZ47LEN6B20DZ47LEN6B25DZ47LEN6B32DZ47LEN6B40DZ47LEM6B50DZ47LEM6B60DZ47LEN4B6DZ47LEN4B10DZ47LEN4B16DZ47LEN4B20DZ47LEN4B25DZ47LEN4B32DZ47LEN4B40DZ47LEM4B50DZ47LEM4B60454590909090901081081089999999999991261261261171171171171171171351351353P+N 4PDZ47LEN1C6DZ47LEN1C10DZ47LEN1C16DZ47LEN3C10DZ47LEN3C16DZ47LEN3C20DZ47LEN3C25DZ47LEN3C32DZ47LEN3C40DZ47LEM3C50DZ47LEM3C60DZ47LEN6C6DZ47LEN6C10DZ47LEN6C16DZ47LEN6C20DZ47LEN6C25DZ47LEN6C32DZ47LEN6C40DZ47LEM6C50DZ47LEM6C60DZ47LEN4C6DZ47LEN4C10DZ47LEN4C16DZ47LEN4C20DZ47LEN4C25DZ47LEN4C32DZ47LEN4C40DZ47LEM4C50DZ47LEM4C60DZ47LEN1D6DZ47LEN1D10DZ47LEN1D16DZ47LEN3D10DZ47LEN3D16DZ47LEN3D20DZ47LEN3D25DZ47LEN3D32DZ47LEN3D40DZ47LEM3D50DZ47LEM3D60DZ47LEN6D6DZ47LEN6D10DZ47LEN6D16DZ47LEN6D20DZ47LEN6D25DZ47LEN6D32DZ47LEN6D40DZ47LEM6D50DZ47LEM6D60DZ47LEN4D6DZ47LEN4D10DZ47LEN4D16DZ47LEN4D20DZ47LEN4D25DZ47LEN4D32DZ47LEN4D40DZ47LEM4D50DZ47LEM4D60订货信息101610162025324050606101620253240506061016202532405060注: 1.以上为剩余电流为30mA 产品订货号2.若订购50,75,100,300mA ,请在相应订货号后加上R50,R75,R100,R3003.若订购带过压保护功能产品,请在相应订货号后加“G"漏电保护装置附件DZ47LE与断路器拼装示意图订货信息SD99DZ47SD 接线能力:1-4mm2导线。
DENCP2019年6月第一版DZ47TRLE透明小型漏电断路器60 A30mA C6kA 6 DZ47TRLEN1C6DZ47TRLEN2C6DZ47TRLEN3C6DZ47TRLEN6C6DZ47TRLEN4C610 DZ47TRLEN1C10DZ47TRLEN2C10DZ47TRLEN3C10DZ47TRLEN6C10DZ47TRLEN4C1016 DZ47TRLEN1C16DZ47TRLEN2C16DZ47TRLEN3C16DZ47TRLEN6C16DZ47TRLEN4C1620 DZ47TRLEN1C20DZ47TRLEN2C20DZ47TRLEN3C20DZ47TRLEN6C20DZ47TRLEN4C2025 DZ47TRLEN1C25DZ47TRLEN2C25DZ47TRLEN3C25DZ47TRLEN6C25DZ47TRLEN4C2532 DZ47TRLEN1C32DZ47TRLEN2C32DZ47TRLEN3C32DZ47TRLEN6C32DZ47TRLEN4C3240 DZ47TRLEN1C40DZ47TRLEN2C40DZ47TRLEN3C40DZ47TRLEN6C40DZ47TRLEN4C404.5kA50 DZ47TRLEA1C50DZ47TRLEA2C50DZ47TRLEA3C50DZ47TRLEA6C50DZ47TRLEA4C5060 DZ47TRLEA1C60DZ47TRLEA2C60DZ47TRLEA3C60DZ47TRLEA6C60DZ47TRLEA4C60D 4.5kA 6 DZ47TRLEA1D6DZ47TRLEA2D6DZ47TRLEA3D6DZ47TRLEA6D6DZ47TRLEA4D610 DZ47TRLEA1D10DZ47TRLEA2D10DZ47TRLEA3D10DZ47TRLEA6D10DZ47TRLEA4D1016 DZ47TRLEA1D16DZ47TRLEA2D16DZ47TRLEA3D16DZ47TRLEA6D16DZ47TRLEA4D1620 DZ47TRLEA1D20DZ47TRLEA2D20DZ47TRLEA3D20DZ47TRLEA6D20DZ47TRLEA4D2025 DZ47TRLEA1D25DZ47TRLEA2D25DZ47TRLEA3D25DZ47TRLEA6D25DZ47TRLEA4D2532 DZ47TRLEA1D32DZ47TRLEA2D32DZ47TRLEA3D32DZ47TRLEA6D32DZ47TRLEA4D3240 DZ47TRLEA1D40DZ47TRLEA2D40DZ47TRLEA3D40DZ47TRLEA6D40DZ47TRLEA4D4050 DZ47TRLEA1D50DZ47TRLEA2D50DZ47TRLEA3D50DZ47TRLEA6D50DZ47TRLEA4D5060 DZ47TRLEA1D60DZ47TRLEA2D60DZ47TRLEA3D60DZ47TRLEA6D60DZ47TRLEA4D6060A15mA C6kA 6 DZ47TRLEN1C6R15* DZ47TRLEN2C6R15* DZ47TRLEN3C6R15* DZ47TRLEN6C6R15* DZ47TRLEN4C6R1510 DZ47TRLEN1C10R15* DZ47TRLEN2C10R15* DZ47TRLEN3C10R15* DZ47TRLEN6C10R15* DZ47TRLEN4C10R1516 DZ47TRLEN1C16R15* DZ47TRLEN2C16R15* DZ47TRLEN3C16R15* DZ47TRLEN6C16R15* DZ47TRLEN4C16R1520 DZ47TRLEN1C20R15* DZ47TRLEN2C20R15* DZ47TRLEN3C20R15* DZ47TRLEN6C20R15* DZ47TRLEN4C20R1525 DZ47TRLEN1C25R15* DZ47TRLEN2C25R15* DZ47TRLEN3C25R15* DZ47TRLEN6C25R15* DZ47TRLEN4C25R1532 DZ47TRLEN1C32R15* DZ47TRLEN2C32R15* DZ47TRLEN3C32R15* DZ47TRLEN6C32R15* DZ47TRLEN4C32R1540 DZ47TRLEN1C40R15* DZ47TRLEN2C40R15* DZ47TRLEN3C40R15* DZ47TRLEN6C40R15* DZ47TRLEN4C40R154.5kA50 DZ47TRLEA1C50R15* DZ47TRLEA2C50R15* DZ47TRLEA3C50R15* DZ47TRLEA6C50R15* DZ47TRLEA4C50R1560 DZ47TRLEA1C60R15* DZ47TRLEA2C60R15* DZ47TRLEA3C60R15* DZ47TRLEA6C60R15* DZ47TRLEA4C60R1560A50mA C6kA 6 * DZ47TRLEN1C6R50* DZ47TRLEN2C6R50* DZ47TRLEN3C6R50* DZ47TRLEN6C6R50* DZ47TRLEN4C6R5010 * DZ47TRLEN1C10R50* DZ47TRLEN2C10R50* DZ47TRLEN3C10R50* DZ47TRLEN6C10R50* DZ47TRLEN4C10R5016 * DZ47TRLEN1C16R50DZ47TRLEN2C16R50* DZ47TRLEN3C16R50* DZ47TRLEN6C16R50* DZ47TRLEN4C16R5020 * DZ47TRLEN1C20R50DZ47TRLEN2C20R50* DZ47TRLEN3C20R50DZ47TRLEN6C20R50* DZ47TRLEN4C20R5025 * DZ47TRLEN1C25R50DZ47TRLEN2C25R50* DZ47TRLEN3C25R50* DZ47TRLEN6C25R50* DZ47TRLEN4C25R5032 * DZ47TRLEN1C32R50DZ47TRLEN2C32R50* DZ47TRLEN3C32R50DZ47TRLEN6C32R50* DZ47TRLEN4C32R5040 * DZ47TRLEN1C40R50* DZ47TRLEN2C40R50DZ47TRLEN3C40R50DZ47TRLEN6C40R50* DZ47TRLEN4C40R504.5kA50 * DZ47TRLEA1C50R50* DZ47TRLEA2C50R50* DZ47TRLEA3C50R50* DZ47TRLEA6C50R50* DZ47TRLEA4C50R5060 * DZ47TRLEA1C60R50DZ47TRLEA2C60R50DZ47TRLEA3C60R50DZ47TRLEA6C60R50* DZ47TRLEA4C60R50注:带*号的物料,需要定制15mA,漏电保护更可靠!当临时用电场所环境为潮湿或有腐蚀气体时,额定剩余动作电流为15mA的漏电断路器可提供更可靠的用电保护!全新平台设计,质量稳定可靠业界领先技术平台,全自动化生产工艺,产品质量更加稳定可靠。
DZ47LE系列漏电断路器样本DZ47LE系列漏电断路器是一种用于保护电路免受漏电和过电流损害的断路器。
它是一种自动开关设备,可在电路发生过电流或漏电时切断电流,从而保护电器和人身安全。
下面将介绍DZ47LE系列漏电断路器的样本,包括其特点、型号和应用范围。
1.安全可靠:DZ47LE系列漏电断路器可可靠地检测电路中的漏电故障,并在短时间内自动切断电流,以防止潜在的触电事故。
2.高灵敏度:DZ47LE系列漏电断路器具有高灵敏度的漏电保护功能,能够检测绝缘电阻下降至5MΩ以下的电流泄漏情况。
3.大断电容量:DZ47LE系列漏电断路器具有较大的断电容量,能够在漏电发生时快速切断电流,保护电器设备免受漏电损坏。
4.功能完善:DZ47LE系列漏电断路器可以实现漏电、过载和短路保护功能的综合保护,可根据实际需求选择不同额定电流和断电容量的型号。
1.DZ47LE-63:适用于63A以下的电路,具有63A的额定电流和6kA的断电容量。
2.DZ47LE-100:适用于100A以下的电路,具有100A的额定电流和10kA的断电容量。
3.DZ47LE-125:适用于125A以下的电路,具有125A的额定电流和10kA的断电容量。
4.DZ47LE-150:适用于150A以下的电路,具有150A的额定电流和15kA的断电容量。
DZ47LE系列漏电断路器的应用范围十分广泛。
它适用于各类住宅、商用和工业场所的电路保护,如家庭、办公室、商场、工厂等。
它可以用于保护电器设备、照明设备、插座等电路免受漏电和过电流的损害。
同时,DZ47LE系列漏电断路器还可以广泛应用于各个行业的电力配电系统中,起到保护电路和人身安全的作用。
综上所述,DZ47LE系列漏电断路器是一种安全可靠、高灵敏度和大断电容量的漏电保护开关。
它具有多种型号和广泛的应用范围,可以满足各类电路的保护需求。
同时,DZ47LE系列漏电断路器还具有功能完善的特点,可以实现综合保护功能,确保电路和人身安全。
安装、使用产品前,请仔细阅读使用说明书并妥善保管、备用安全告知在安装、操作、运行、维护、检查之前,请务必认真阅读本说明书,并按照说明书上的内容准确安装、使用本产品。
危险:严禁湿手操作断路器; 使用中,严禁触摸导电部位;维护与保养时,必须确保产品不带电; 严禁用短路的办法来测试产品。
注意:安装、维护与保养时,应由具有专业资格的人员操作;产品的各项特性出厂时已整定,使用中不能自行拆装或随意调节; 使用前请确认产品工作电压、额定电流、频率及特性是否符合工作要求; 按照产品上的接线标识进行安装接线(负载端即出线端);导线伸入接线孔后拧紧接线螺钉,拧紧导线使导线不得松动、拔出,裸露铜线头不能露在接线端外; 本产品对同时接触被保护电路两线引起的触电危险不能进行保护;本产品防护等级IP20不具备防尘功能,当用于灰尘较多的场合时,请安装于密封较好的终端箱中;本产品不适用于电动机频繁启动、电热设备、电容柜、高感性、高容性负载和高温环境等特殊场合;如果产品在开箱时有破损或异常响声,应立即停止使用并联系供应商。
电源侧有电压时,合闸后产品中线路板处在工作状态,侧面有一定温度,属于正常现象;目录1主要用途及适用范围 ....................................................... 错误!未定义书签。
2产品型号及含义 . (1)2.1产品型号及含义 (1)2.2面板介绍 (2)3 正常工作条件和安装条件 (2)4技术特性 (3)4.1 分类 (3)4.2 主要技术参数 (3)4.3 主要技术性能 (4)5外形及安装尺寸 (4)6安装、使用和维护 (5)7故障分析 (6)8 开箱检查 (7)9公司承诺 (7)1主要用途及适用范围DZ47sLES系列剩余电流动作断路器(以下简称漏电断路器)具有漏电(触电)、过载、短路等保护功能,还可根据用户的需要增加过压,欠压保护功能。
DZ47sLES漏电断路器适用于交流50/60Hz,额定电压230V/400V,额定电流至63A及以下的线路中,用来对人的间接接触保护,以及对建筑物及类似用途的线路进行过电流保护。
DZ47LE-125NAVIGATOR Series RESIDUAL CURRENTOPERATTED CIRCUIT-BREAKERUser ManualPlease carefully read this User Manual before installing andoperating the product, and keep this manual properly for futurereferenceDZ47LE-125 Residual Circuit Operated Circuit-BreakerUser ManualSafety NoticePlease carefully read this manual before the installation, operation, run, maintenance, and inspection of the product, and install and operate this product properly according to the contents of the instructions.Danger:⚫It is prohibited to operate the circuit breaker with your wet hands;⚫It is prohibited to touch the conductive part during operation;⚫Make sure that the product is de-electrified during the maintenance and service;⚫It is prohibited to use the short circuit method to test the product;Caution:⚫The installation, maintenance, and service shall be carried out by the qualified professionals;⚫The three-pole and four-pole products are only available for the power supply of the three-phase system;⚫All characteristics of the product have been set in the factory, and the product cannot be disassembled without permission or adjusted at will during operation;⚫Please confirm that the product voltage, rated current, frequency, and characteristics of the product meet the working requirements before use;⚫In order to prevent short circuit between the phases, the exposed wire or copper busbar at the terminal block shall be subject to the insulation treatment;⚫To test the insulation resistance or power frequency withstand voltage, please disconnect the electronic components between the current circuits, otherwise the product performance will be deteriorated;⚫The product only provides the protection for electric leakage fault generated at the load end;⚫For less wiring or wrong wiring connection, the electric leakage protection function of the product will be disabled;⚫If found damage or heard abnormal sound when unpacking the product, please stop the operation immediately and contact the supplier;⚫This product is not suitable for special occasions such as frequent startups of motor, electric heating equipment, capacitor cabinets, high inductive and high capacitive loads and high temperature environments;⚫When scrapping the product, please dispose the product waste properly; thanks for your cooperation.About DZ47LE-125 Residual Circuit Operated Circuit-Breaker●Panel introductionPress oncea monthPress beforepower-onLoad endLegends:1. Power supply end2. Company logo3. Rated current: 63A, 80A, 100A, 125A4. Technical parameters: Ue: 230V (1P+N,2P) / 400V (3P, 3P+N, 4P),Icu: 10kA, Ics= 75% Icu, Uimp: 4kV(C) Ii=8.5In (for power distribution protection),(D) Ii=12In (for motor protection) I△m = 2500A5. Standard: GB/T 14048.2 and IEC 60947-26. Load end 7 Test button 8. Wiring diagram9. Residual operating current and time 10. Reset buttons.Normal Operation, Installation and Transportation Conditions● Normal operation and installation conditions(1)The upper limit of the ambient air temperature shall not exceed +60°C, the lower limit shall not exceed -20°C, and the mean temperature shall not exceed +35°C within 24 hours;(2)The altitude of the installation site does not exceed 2000m;(3)When the maximum temperature is +60°C, the relative humidity of the air does not exceed 50%; a higher relative humidity is allowed at lower temperatures, such as 90% at +20°C. Special protection measures should be taken for condensation occurred occasionally due to temperature changes;(4)The external magnetic field near the installation site of the circuit breaker should not exceed 5 times of the geomagnetic field in any direction;(5)The installation site shall be vertical, and the inclination angle does not exceed 10° in any direction;(6)Installed in places where there is no obvious impact and vibration and no rain and snow attacks;(7)Pollution degree: Level 2;(8)Installation category: Class II, Class III;(9)Protection grade: Installed a power distribution tank, distribution cabinet or box: IP40.⚫Normal storage and transportation conditions(1) Temperature: -40°C ~ +70°C;(2) Relative humidity (at 25°C): ≤ 95%;(3) Please handle the product gently during transportation, do not upside it down, and prevent it from violent collision.Main Specifications and Technical Parameters●The main technical parameters are listed in Table 1Table 1 Main technical parametersModelNumber of poles Zero line added Freq. HzRated current In ARated voltage Ue VRated limit short circuit breaking capacity Icu ARated residual operating current I △n mA Rated residual non-operating current I △nomA Breaking time at I △n sRatedresidual making and breaking capacity I △m A Trip typeD Z 47LE -1251 N 50 63 80 100 12523010000 (Ics=75% Icu)3050 75 100 30015 25 37.5 50 150≤0.1 2500C type Ii = 8.5In (for power distribution protection)D type Ii = 12In (for motor protection)2 3 4003 N 4● The protection characteristics of the overcurrent release are listed in Table 2Table 2 Protection characteristics of the overcurrent releaseType of overcurrent instantaneous releaseTest current A Starting state Test time Expectedresults RemarksReferencetemp.C, D 1.05In Cold state t ≤1h (In ≤63A)t ≤2h (In>63A)No trip --+30+50o CC, D 1.3In Followed by test t<1h (In ≤63A)t<2h (In>63A)Trip The current rises tothe specified valuewithin 5sC, D 2.55In Cold state 1s<t<120s Trip -- C 8.5Inx80% Cold state t ≤0.2s No-trip Turn on the aux.switch, and connectthe power supplyD 12Inx80%C 8.5Inx120% Cold state t<0.2s Trip Turn on the aux.switch, and connectthe power supplyD 12Inx120%●The protection characteristics curves of circuit breaker are illustrated in Fig. 1 and Fig. 2Fig. 1 C type thermal /electromagnetic tripcharacteristics curveFig. 2 D type thermal /electromagnetic tripcharacteristics curveOutline and Installation DimensionsThis series of circuit breaker of the rail-mounted type, suitable for TH35-7.5 steel mounting rail, and its outline and installation dimensions are shown in Fig. 3.Unit: mm72.5 (IP+N is 69)Fig. 3 Outline and installation dimensionsProduct accessoriesThere are two different accessories for circuit breaker, including OF aux. contact and SD alarm contact. Accessories are all installed at the left side of the product.Installation, Operation and Maintenance●Installation and Operation(1)Before installation, check whether the product identification is consistent with the working conditions.(2)Press the Reset button before power on.(3)Please operate the residual current operated circuit breaker several times before power on, and its mechanism shall work flexibly and reliably without blockage.(4)For residual current operated circuit breaker, the “1”, “3”, “5”, and “N” ends are power ends, and “2”, “4”, “6”, and “N” ends ar e load ends, and they shall not be connected reversely;(5)The sectional area of the connecting wire sees Table 3.Table 3 Rated current and sectional area of the connecting wireRated current A 63 80 100 125 Sectional area of wire, mm216 25 35 50 Wiring tighening torque N.m Power end and load end: 3.5(6)After power on, operate the test button of the residual current operated circuit breaker several times and confirm whether it can work reliably.(7)When the handle moves upwards, the indicator window displays red, indicating that the circuit is in the connection state; when the handle moves downward, the indicator window displays green, indicating that the circuit is in the disconnection state.(8)When installation, insert the residual current operated circuit breaker into the mounting rail, and ensure that the residual current operated circuit breaker is fixed on it without any looseness and falling off. To remove the residual current operated circuit breaker, pull the stopper.The working reference temperature of the residual current operated circuit breaker is +30+50℃. When the ambient temperature changes, its rated value shall be correct. The temperature correction coefficients see Table 4. If multiple residual current operated circuit breakers are installed in an enclosed box, the temperature inside the box will increase correspondingly, and the rated current shall multiply by the derating coefficient 0.8.Table 4 Rated current and temperature correction coefficient tableRated current ARated current correction value A-20o C -10o C 0o C +10o C +20o C +30o C +40o C +50o C +60o C63 78.9 75.7 72.5 69.3 66.2 63 59.2 55.4 51.680 100 96 92 88 84 80 75.2 70.4 65.6 100 125 120 115 110 105 100 94 88 82 125 169.2 162.8 143.8 137.5 131.2 125 117.8 111.5 105 Maintenance and Service●The maintenance and service must be carried out by the qualified professionals;●Be sure to ensure the product is deenergized (except for the use of test button for test);●The maintenance and service must be carried out once a year under normal operating conditions, and the maintenance contents are listed in Table 5.Table 5 Maintenance and ServiceItem ContentsAppearance No dust, no condensation; clean if necessaryNo damageNo color changes on the housing and terminal blockConnection of terminal block Tighten it according ot the torque listed in Table 3 without looseness Handle closed/open operation Operated flexiblyTest button After the product trips, the handle shall indicate the trip position Insulation test It is prohibited to carry out the insulation test between the phases atthe load endTest via test button Conduct the simulation of the electric leakage proteciton test oncemonthlyFaults and TroubleshootingFault Cause SolutionMis-operation Residual current operatedcircuit breaker worksimproperly to cause mis-operationThe three-pole residual current operatedcircuit breaker is used in the three-phase four-wire circuit, because the normal operatingcurrent in the zero line does not pass throughthe current transformer, once the single-phaseload starts, the residual current operatedcircuit breaker will work.3P residual current operated circuit breakerLightIncorrect wiringIn the three-phase four-wire circuit, 3P+N or4P residual current operated circuit breakermust be used.3P+N or 4PResidual current operated circuit breakerLightCorrect wiringZero line on the load sideof the residual currentoperated circuit breaker isearthed to cause mis-operationWhen the zero line on the load side of theresidual current operated circuit breaker isearthed, the normal operating current willflow into the earth through the earth point tocause misoperation.Residual current operated circuit breakerIncorrect wiringConnected to the equipment housingConnect the earth wire to the zero line on thepower side of the residual current operatedcircuit breakerResidual current operated circuit breakerConnected to theequipment housingCorrect wiringLeakage current andcapacitance current of thewire to the earth causemis-operationThe wire on the load side is close to the earthtightly and has long laying length, generaing alarge capacitance current to earth Select the residual current operated circuitbreaker with a large residual operating current The leakage current to earth of the wire on theload side increases due to insulationreduction.No-operation No-operation caused bythe repeated earthing onthe load side of theresidual current operatedcircuit breakerThe neutral line on the load side of theresidual current operated circuit breaker isearthed, and the leakage current will beshunted through the earth point in the event ofcurrent fault on the line, making the currentdifference between the leakage current andthe current flowing back to the N phase is lessthan the rated residual operating curent,causeing non operation.Residual current operated circuit breakerIncorrect wiringRemove the repeated earth wire on the loadside.Residual current operated circuit breakerCorrect wiringNo-operation caused bythe open phase on thepower side of the three-pole (or four-pole)residual current operatedcircuit breakerThe phase wire on the power side of the three-pole (or four-pole) residual current operatedcircuit breaker is not wired as requiredConnect the phase line on the power side asrequiredUnpacking InspectionAfter unpacking, the user must check whether the product is intact, whether the exposed metal is rusty, and whether the product is defects due to poor transportation or storage. If found the above phenomenon, please stop the product, and contact the supplier timely for solution.Company’ commitmentThe free repair or replacement will be provided by the company for damage or abnormal operation of the product produced by our company due to poor manufacturing quality within 36 months from the date of the production under the premise that the user conforms to the operation and storage conditions and that the product is well sealed. A paid repair is provided when the warranty period expires. However, the paid repair is provided for damage caused by one of the following situations even within the warranty period:(1)Improper operation, maintenance, or storage;(2)Modification without permission, or improper maintenance;(3)Damage caused by falling off after purchase or occurred during the installation process;(4)Irresistible nature disasters such as earthquakes, fires, lightning strikes, and abnormal voltages.If you have any questions, please contact the dealer or the company’s customer service department.Customer service hotline: 400-826-8008Ordering NoticePlease specify the following contents when ordering:a)Name, model and spec. of residual current operated circuit breaker;b)Rated current of the residual current operated circuit breaker;c)Residual operating current of the residual current operated circuit breaker;d)Number of poles;e)Qty.For example, to order DZ47LE-125, three-pole circuit breaker, C type, rated current 100A, rated residual operating current 30mA, 100 units.Please specify: DZ47LE-125/3P, C100, 30mA, 100 units.Certificate DELIXI ELECTRIC LTD Name: Residual Current Operated Circuit Breaker Model: DZ47LE-125The product passes the inspection, and is allowed to be shipped.Standard: GB/T 14048.2Inspector: Check 02Date of production: See the label in the inner boxDELIXI ELECTRIC LTDDelixi Industrial Park, Liushi Town, Yueqing City, Zhejiang Province P/C.: 325604 Tel: (86-577)6177 8888Fax: (86-577)6177 8000Customer service hotline: 400-826-8008The first edition of this User Manual was issued in July 2019.。
DZ47小型断路器使用说明书一.用途DZ47-63(C45-63)小型断路器(以下简称断路器)主要用于交流50Hz/60Hz,额定电压至400V,电流至63A的电气线路及设备的过载和短路保护中,亦可用于作为线路不频繁转换之用。
目前我公司生产的小型断路器最高电流可达125A,63A以上的电流安排有80A、100A、125A.小型断路器又分为C型和D型,一般家用为C型断路器,动力系统中选用D型断路器。
二.产品型号及含义三.产品分类按极数分类有:单极(1P)断路器二极(2P)断路器三级(3P)断路器四极(4P)断路器按额定电流分:6A、10A、16A、20A、25A、32A、40A、50A、63A、80A、100A、125A。
额定工作电压单极为230V/400V,二极、三级、四级为400V.按瞬时脱扣电流分C型和D型。
四.正常使用条件周围空气温度不低于-5度,不高于+40度,日平均值不超过+35度。
安装地点海拔高度不超过2000米。
大气相对湿度,在最高温度+40度时不超过50%,在较低温度时可以有较高湿度,如最湿月平均温度不超过+25度时,月平均相对温度不超过90%,并允许由于温度变化发送在产品表面的凝露。
断路器使用地点的等级污染等级为2级。
断路器采用TH35-7.5型钢安装导轨安装。
断路器的安装类别通常为II、III类。
断路器按正常工作位置安装,安装面与垂直面的斜度不大于正负5度。
断路器接线方法,用螺钉压紧接线。
断路器具有隔离功能。
五.技术数据过电流脱扣特性断路器在基准环境温度30~35度下的过流脱扣特性应符合表1的规定。
本产品符合标准GB14048.2/GB10963.1.额定短路通断能力:Ics=Icn=4500A(大于或等于40A)/3000A(小于或等于50A).剩余短路接通分断能力:Im=2000A六.结构特征与工作原理本断路器有触头、灭弧系统,电磁系统和脱扣机构及操作机构而组成,电磁系统采用精密型和电阻型双金属材料,触头采用银氧化镉触头,另外还选用了增强耐弧塑料等新型材料,保证产品性能。
"G"提供过压保护功能:280±5%V AC 仅适用于1P+N 和2P 产品脱扣指示DZ47LE 上有剩余电流动作脱扣指示,复位按钮弹起,为漏电脱扣手动控制:手柄允许两种复位模式过电流故障:断路器和剩余电流动作装置同时复位漏电故障:剩余电流动作装置先复位,断路器后复位机械寿命:2000次电气寿命:2000次环境温度使用环境温度:-5℃~+40℃接线6~32A ,可接16mm 2 及以下导线40~60A ,可接25mm 2 及以下导线安装符合标准:IEC61009-1 / GB16917.1符合认证:CCC 认证脱扣特性B 型曲线保护短路电流较小的负载(如电源、长电缆等)脱扣特性:瞬时脱扣范围 (3~5) InC 型曲线保护常规负载和配电线缆脱扣特性:瞬时脱扣范围 (5~10) InD 型曲线保护起动电流大的冲击性负荷 (如变压器等)脱扣特性:瞬时脱扣范围 (10~14) In技术参数50, 60444额定电流:6,10,16,20,25,32,40,50,60 A 额定工作电压:230/400V AC 额定绝缘电压:500V额定剩余动作电流:30,50,75,100,300mA分断能力40~60M52.54.52.0DZ47LEN1B10DZ47LEN1B16DZ47LEN3B10DZ47LEN3B16DZ47LEN3B20DZ47LEN3B25DZ47LEN3B32DZ47LEN3B40DZ47LEM3B50DZ47LEM3B60DZ47LEN6B6DZ47LEN6B10DZ47LEN6B16DZ47LEN6B20DZ47LEN6B25DZ47LEN6B32DZ47LEN6B40DZ47LEM6B50DZ47LEM6B60DZ47LEN4B6DZ47LEN4B10DZ47LEN4B16DZ47LEN4B20DZ47LEN4B25DZ47LEN4B32DZ47LEN4B40DZ47LEM4B50DZ47LEM4B60454590909090901081081089999999999991261261261171171171171171171351351353P+N 4PDZ47LEN1C6DZ47LEN1C10DZ47LEN1C16DZ47LEN3C10DZ47LEN3C16DZ47LEN3C20DZ47LEN3C25DZ47LEN3C32DZ47LEN3C40DZ47LEM3C50DZ47LEM3C60DZ47LEN6C6DZ47LEN6C10DZ47LEN6C16DZ47LEN6C20DZ47LEN6C25DZ47LEN6C32DZ47LEN6C40DZ47LEM6C50DZ47LEM6C60DZ47LEN4C6DZ47LEN4C10DZ47LEN4C16DZ47LEN4C20DZ47LEN4C25DZ47LEN4C32DZ47LEN4C40DZ47LEM4C50DZ47LEM4C60DZ47LEN1D6DZ47LEN1D10DZ47LEN1D16DZ47LEN3D10DZ47LEN3D16DZ47LEN3D20DZ47LEN3D25DZ47LEN3D32DZ47LEN3D40DZ47LEM3D50DZ47LEM3D60DZ47LEN6D6DZ47LEN6D10DZ47LEN6D16DZ47LEN6D20DZ47LEN6D25DZ47LEN6D32DZ47LEN6D40DZ47LEM6D50DZ47LEM6D60DZ47LEN4D6DZ47LEN4D10DZ47LEN4D16DZ47LEN4D20DZ47LEN4D25DZ47LEN4D32DZ47LEN4D40DZ47LEM4D50DZ47LEM4D60订货信息101610162025324050606101620253240506061016202532405060注: 1.以上为剩余电流为30mA 产品订货号2.若订购50,75,100,300mA ,请在相应订货号后加上R50,R75,R100,R3003.若订购带过压保护功能产品,请在相应订货号后加“G"漏电保护装置附件DZ47LE与断路器拼装示意图订货信息SD99DZ47SD 接线能力:1-4mm2导线漏电保护装置CDB6v漏电保护模块漏电保护装置CDL7漏电开关CDB6s标准断路器/DZ47标准断路器/DZ47LE标准漏电保护断路器CDB3“相线+中性线”断路器/CDB3LE“相线+中性线”漏电保护断路器。
DZ47LE漏电断路器
用途
DZ47LE漏电断路器是由DZ47断路器与漏电保护附件拼装而成,适用于交流50Hz、三相400V及单相230V,额定电流至63A的电路中,作为人身触电和设备漏电保护之用,亦可用于线路的过载和短路保护且正常情况下作为线路及电动机的不频繁转换。
该产品分为普通型和银钻型两种,其中银钻型带通断观察窗,并可用汇流排连接。
产品执行标准:GB16917.1家用及类似用途和带过电流保护的剩余电流动作断路器第一部分:一般规则。
主要技术性能与工作原理
1、DZ47LE漏电断路器为电流动作型电子式快速漏电断路器,由高导磁材料制造的零序电流互感器、电子组件板,漏电脱扣器和DZ47-63空气开关组成。
当被保护电路有漏电电流或人体间接触电时通过零序电流互感电流的矢量和不等于零,互感器二次线圈的二则产生电压,并经电子元件放大,当达到整定值时,通过漏电脱扣器在0.1秒内切断电源,从而起漏电和漏电保护作用。
2、当被保护线路发生过载或短路时,DZ47-63空气开关自动跳闸,切断电源。
3、DZ47-63空气开关的过电流脱扣器在周围介质温度为+30℃从冷态开始各极同时通电,其动作特性为:
a、1.13倍额定电流1h内不动作,
b、1.45倍额定电流1h内动作。
4、漏电开关在正常工作中,漏电开关复位按钮应凹下,才正常工作,当复位按钮凸上,证实漏电跳闸。
暂停使用,查明故障方可使用。
5、具体性能见表(1)
正常工作条件
1、最高空气温度为+40℃,最低空气温度为-5℃;
2、海拔高度不超过2000米;
3、空气相对温度不大于85%;
4、安装位置的外磁场,在任何方向不应超过地磁场的5倍;
5、无显著摇动和冲击振动的地方;
6、产品必须远离有害、有腐蚀气味环境;
7、没有雨雪侵袭的地方。