箱型风冷机组使用、安装、维护说明书目录第一章用户须知及使用说明----------------------------------------------------------------------------3 用户须知------------------------------------------------------------------------------------------3使用说明------------------------------------------------------------------------------------------4 第二章机组的安装----------------------------------------------------------------------------------------5 安装位置的选择与安装要点------------------------------------------------------------------5机组开箱检查------------------------------------------------------------------------------------6机组的吊装及固定------------------------------------------------------------------------------6机组的电气安装---------------------------------------------------------------------------------7机组的水系统安装------------------------------------------------------------------------------7 第三章操作调试------------------------------------------------------------------------------------------8 第四章机组的维护与保养------------------------------------------------------------------------------9 第五章常见故障与分析处理--------------------------------------------------------------------------10 第六章技术参数------------------------------------------------------------------------------------------11第一章用户须知及使用说明请确认您在使用本机组之前至少已阅读了本说明书的"用户须知";"用户须知"提供了非常重要的有关安全及机组使用的要点,请您确保按其正常操作执行。
一、a.故障报警时发出“嘀——嘀——嘀——”连续声。
按键确认时发出“嘀—”单声。
b. 液晶LCD点阵显示器显示4行15列汉字。
c. 功能键“FUN”、查询“ALARM”按功能“FUN”键进行手动除霜和强制开关机。
在主画面时,按“ALARM”键直接查询故障情况,再按下时,可复位故障并退出。
在故障发生时,按任意键消除报警发声。
d. 机组运行LED指示灯组包括运行指示(RUNNING),故障指示(ALARM),低温、除霜、防冻指示(LOWTEMP),制热指示(STANDBY1),制冷指示(STANDBY2),OUTPUT1-OUTPUT12分别为1-8#模块的工作信号指示。
e. 启动“START”、停止键“STOP”系统在任何界面下均可单键启停。
按“START”键,机组即开始按系统设定开机机理运行。
按“STOP”键即按系统设定关机机理运行。
f. 设置、选择键组按“MENU”键逐层返回。
连续按此键可返回至主界面。
“ENTER”键选择确认。
对欲修改设定值,先翻屏至相应界面,再按“ENTER”键进行修改。
对反白部分选中必须按“ENTER”键确认。
g. 游标键按“☐❑”游标键可翻屏。
在设定状态时,此两键可调整数字及反白部分下移,按“♦◆”游标键反白部分逐位移动。
h. RS-485标准串行通讯口与计算机(PC机)通讯的连接口(RJ11),通讯距离可达1200米,计算机需配置485/232转换口。
i. RS-485标准串行通讯口与控制系统I/O 模块通讯的连接口(RJ11),通讯距离可达1200米。
j. RS-232标准串行通讯口与计算机(PC 机)或调制解调器(MODEM )通讯的连接口,通过MODEM 可进入公众电信交换网,进行远程通讯监控。
注:h 和j 所指通讯口通过机内跳线选择。
k. 电源输入口电压:24V AC ±10% 功率:5W二、菜单说明功能选择界面(主菜单)A 、显示系统状态——实时显示机组AI 状态、DO状态、DIN 状态,风机累计运转时间,本机序列号等参数。
冷水机组第一节实施1.1 安装A. 设备的安装应按照制造厂家安装说明书规定的方式进行,以保证设备的正常运行及容易维修。
B. 为了便利维修及拆除配件而不需把冷冻水及冷媒排出,所以制冷机的位置上的安排应达到这方面的要求。
C. 所有皮带、滑轮、齿轮、转轴连接器、凸出的螺丝及其它转动部份也应正确地保护。
D. 按制冷机生产厂家的意见,提供及安装所有的支架、吊架、固定螺丝、防震弹簧或防震垫板等所需的设备。
E. 所有低温表面包括蒸发器、水室、吸入弯管、节能器和电动机冷却管等,须由原厂提供保温材料覆盖。
1. 2 试验和起动A. 在设备制造厂的代表监督下进行。
1. 冷媒充灌2. 起动3. 现场试验B. 真空检漏1. 现场检测泄漏。
2. 用卤素检测仪检查泄漏。
3. 用高压真空泵产生0.6mbar的真空度抽空设备。
a. 真空度维持四小时。
b. 四小时结束时,真空泵停止。
c. 制冷设备的真空度在24小时内,损失小于50微米。
4. 并提交六份有证明的试验报告以供验收。
C. 现场制冷剂管道试验:1. 现场试验应符合当地有关政府部门的规范及机械制冷安全规范:美国国家标准协会(ANSI)B9.1的规定。
2. 设备制造厂提供:冷媒充灌完成证明书﹑起动和现场试验证明书,以及设备已可正常运行的证明书。
3. 在安装完成和验收时,应提供适合的指导人员主持为期五天,每天六小时的培训课程,以指导业主的代表熟悉所有细节,以保证他们在设备运行获得最大的效率。
在完成每天的培训课程都须由业主的代表签署确认。
第二节品牌范围特灵Trane/约克York/开利Carrier.第三节基本要求:根据本文中规定和相关图纸,提供所有空调冷水机组。
3.1每台冷水机组都应当为技术文件中所列出的型号和功率,在规定的状态下应提供规定的供冷量,并且不得超过规定的转速、功率、水压降和噪音。
3.2在运输、贮藏和安装过程中,应适当加以保护,防止腐蚀和受损,被损坏的设备及材料将不会被接受3.3所有冷水机组都应载有生产厂商的铭牌,同时给出生产厂商名称、型号、主要设备参数及生产日期等3.4供应商需对机组电机、电机冷却管、压缩机进气管、膨胀阀、蒸发器等配置原厂阻燃保温材料。
风冷式冷水机组操作指导书本指导书旨在向操作人员提供风冷式冷水机组的操作指导和相关注意事项,请在操作前仔细阅读本指导书内容,并严格按照操作步骤进行操作。
机组概述风冷式冷水机组是一种常用的空调设备,用于提供冷水来实现空调系统的制冷功能。
机组的主要部件包括压缩机、冷凝器、蒸发器以及相应的控制系统。
操作步骤1. 确保机组周围环境通风良好,不受阻碍。
2. 先检查机组外部是否有明显异常,如漏水、损坏等情况。
如有异常,请立即联系维修人员处理。
3. 检查机组的电源连接是否牢固,电源是否正常。
确保机组处于断电状态下进行下一步操作。
4. 打开机组控制面板,根据实际需求设置相应的参数,如温度、湿度等。
确保参数设置正确。
5. 打开机组电源,启动机组。
此时应注意机组启动过程是否正常,如压缩机是否正常运转等。
6. 监测机组运行过程中的温度和压力等参数,确保机组正常运行,并根据需要进行相应调整。
7. 在机组运行过程中,定期检查机组的工作状态,并及时处理任何异常情况。
8. 操作结束后,首先关闭机组电源,然后关闭机组控制面板。
注意事项1. 操作人员必须经过专业培训,并具备一定的机械和电气知识。
2. 在操作过程中,应注意自身安全,避免触碰机组的运动部件和高温部件。
3. 在操作机组之前,应熟悉机组的技术规格和操作流程。
4. 操作人员不得私自改变机组参数,如需相应调整,应经过授权人员同意。
5. 发现机组异常情况时,应及时报修,不得私自进行维修。
6. 操作人员离开机组时,应将机组处于关闭状态,并及时清理操作现场。
请严格按照本指导书的内容进行操作,确保机组的正常运行。
如有任何疑问或异常情况,请及时联系维修人员进行处理。
*以上内容仅供参考,请勿引用无法确认的内容。
*。
麦克维尔MAC风冷模块式冷水机组—控制面板操作说明麦克维尔MAC风冷模块式冷水机组—控制面板操作说明1 开关机·按ON/OFF键,机组在开机(RUN灯亮)、关机(RUN灯灭)之间切换。
2 模式选择·按“模式”键可在制冷/制热模式之间切换,须注意的是,模式切换必须在关机状态下进行,这样对压缩机能起到一定的保护作用。
3 参数查询·使用本控制器能查询它所联网的任意一台机组的工作状态及参数(有哪几台压缩机在工作、设定的进水温度、实际进水温度、设定的出水温度、实际出水温度、机组的定时设置、制冷防冻温度、冬季防冻温度、除霜温度等)。
·按“机组”键后机组号码闪烁,此时按“▲”或“▼”键改变机组号,查看到的是不同机组的当前参数,若要查询某个机组的工作参数,找到欲查询的机组号时按“确定”键即可查询该机组的工作参数了,按“▲”或“▼”键查看该机组的不同的参数。
4 参数设置按“机组”键后机组号码闪烁,此时按“▲”或“▼”键改变机组号,找到欲设置参数的机组号时按“确定”键即可设置该机组的工作参数了(可设置的参数有:制冷进水温度、制冷出水温度、制热进水温度、制热出水温度、防冻温度、除露点A温度、除露点B温度、除霜温度)。
(password:55)按“▲”或“▼”键选择要设置的参数,按“确定”键后就可以按“▲”或“▼”键设置参数值,设置完成后按“确定”键保存设置结果。
重复步骤②可设置其它参数。
5 实时时钟设置·用针形工具按“模式”键上方的小孔,液晶显示器上显示“星期设置”的字样,按“▲”或“▼”键设置当前时间是星期几,设置好了之后再按小孔,星期设置成功,同时显示器上显示“时钟设置”字样,时间会闪烁,此时按“▲”键修改小时,按“▼”键修改分钟,再按小孔即可保存设置的时钟。
6 定时设置按“定时”键后显示器上同时显示“星期设置”和“定时设置”的字样,此时按“▲”或“▼”键选择要设置定时的时间在星期几,选好后按“确定”键,显示器上显示“定时设置”的字样,此时按“▲”键选择要设置当天的哪个定时(能设置4个,在“机组号”上方有指示),按“▼”键选择“定时开”或“定时关”,按“确定”键后再按“▲”键修改小时,按“▼”键修改分钟,设置好时间后按“确定”键保存这个定时设置。
约克风冷冷水机组说明书约克风冷冷水机组的说明书约克风冷冷水机组是一种高效、可靠的空调设备,它主要用于制冷、冷水循环和空气调节等领域。
下面,我们将详细介绍约克风冷冷水机组的相关知识。
1. 约克风冷冷水机组的结构和特点约克风冷冷水机组的主要结构由压缩机、冷凝器、膨胀阀、蒸发器、电气控制系统等部分组成。
其特点是具有小型化、高效、低噪音等特点,可在高、低温环境下正常工作,适用于大型公共建筑、工业用房、商业大楼等场所的空调系统。
2. 约克风冷冷水机组的工作原理当室内温度达到设定值时,空调控制系统会打开冷水机组,冷凝器中的制冷剂会吸收空气中的热量,然后通过蒸发器释放出去,使得室内温度降低。
蒸发器中的制冷剂重新进入到低温低压状态,再次进入到冷凝器中循环。
整个过程需要一个高效的压缩机来完成。
3. 约克风冷冷水机组的维护和保养为了保证约克风冷冷水机组的正常工作,必须定期进行维护和保养。
首先,需要清洗和更换过滤器,保证空气流通畅通。
其次,冷凝器和蒸发器也需要进行清洁。
此外,还需要检查蒸发器、冷凝器、压缩机、膨胀阀等部件是否正常运转,如有故障及时进行处理。
4. 约克风冷冷水机组的应用范围约克风冷冷水机组非常适用于大型公共建筑、工业用房、商业大楼等场所的空调系统。
特别是在高温、高湿的夏季,约克风冷冷水机组能够提供舒适的室内环境,满足人们的需求。
总之,约克风冷冷水机组是一种高效、可靠的空调设备。
通过定期的维护和保养,可以延长其使用寿命,并保证其正常运行。
因此,在选择空调设备时,约克风冷冷水机组是一个非常不错的选择。
水冷机电源主要由整流滤波电路,全桥变换电路,PWM控制电路,稳压、限压电路,稳流、限流电路,保护电路,以及辅助电源电路等组成。
三相(或单相)电网电压经电源开关后,进行整流滤波,得到的520VDC(单相为300VDC)的平滑直流电压供给逆变电路。
三相电压取一路380V AC(或单相220V AC)经变压器降压整流后,再通过三端稳压器稳压得到±12V电压供给各部分控制电路。
逆变电路主要由大功率IGBT模块(或场效应MOSFET模块)组成全桥变换电路。
当PWM输出控制信号通过隔离驱动器分别驱动功率模块,两组对角管分别交替导通,在高频变压器初级产生高频脉冲电压,次级电压由高频变压器变压后整流向负载提供能量。
输出端分别接有稳压、限流和稳流、限压等的反馈环路,当面板开关置于稳压状态时,稳压和限流电路起作用,当输出电压升高或下降时,取样电压通过稳压电路内部电压比较器跟基准电压比较,其误差信号电压加到PWM控制电路,使PWM输出脉宽作相应变化,从而稳定输出电压,如负载电流过高时,限流电路工作,使输出电流限制在限流设定值内。
同样,在稳流状态下,稳流电路作用,使输出电流稳定在设定值内,而当过压时,限压电路使输出电压钳压在限压值。
当有异常情况(如输入过压或欠压,过流或过热等)产生保护信号加到保护控制电路时,保护电路输出一个电压加到PWM电路,使PWM电路停止输出,从而达到保护目的。
技术参数:输出电压:0-12V (0-额定值连续可调)输出电流:0-10000A(0-额定值连续可调)电压电流精度1%设备电源连接:电源电压要求为三相380V,允许网压波动-10%——+10%,即电压范围为350V—430V,超过此范围,可能会造成设备损坏,请用户注意。
由于该设备功率大,接电连接时,应保证连接牢固,尽量减少电连接处接触电阻,以免工作时电压下降严重,影响设备正常工作,用户尤其应避免将电源线简单地挂在电网上的做法。
对于2000A/16V电源建议用户采用16平方毫米以上的电缆供电。
目录中文一、操作注意事项(保养及维护) (1)二、安装要求 (1)三、开机准备 (1)四、面板示意图及操作说明 (1)五、修改参数操作说明 (3)六、故障说明 (6)七、故障排除 (6)八、风冷式冷冻机内部结构示图 (8)九、水冷式冷冻机内部结构示意图 (8)十、风冷式冷水机安装示意图............................................. (9)十一、水冷式冷水机安装示意图....................................... . (9)十二、电器连接示意图 (9)感谢您选用科凌冷冻机,为了您能正确高效的使用,请详细阅读说明书。
一、操作注意事项(保养及维护)1、冷冻水泵不可在水箱内无水的情况下运转;(水箱内装有水位保护,当水箱无水或水位太低时,发出水位故障报警信号。
)2、电源操作开关请尽量避免连续切换;如长时间不使用本设备时,请关闭设备总电源。
3、冷冻水温度达到设定温度时,压缩机会自动停止运行,此属正常现象;4、控制温度应避免设定在5℃以下(低温冷冻机除外),防止冷冻介质在蒸发器中结冰损坏机组;长期不使用本机,应把冷冻介质排放干净;5、为确保制冷效果,使整机保持良好运转,请定期清洗冷凝器、蒸发器及水过滤器。
6、风冷式冷冻机散热器表面保持清洁干净,通风良好;水冷式冷冻机冷却水清洁干净,冷却塔内不得有杂物及其它障碍物,定期清洗冷却塔,冷却水温及流量符合使用要求。
7、故障报警时,应及时检查,按第七项和第十项所列方法排除故障,或及时通知维修人员处理。
二、安装要求:1、冷冻机安装前请选择地基平稳,四周空旷,畅通及避免腐蚀、污染、日晒、雨淋,方便安装维修之场所;2、水冷式冷冻机,根据冷冻机制冷量选用匹配的冷却水塔。
冷水机管路配管,请根据机身管路尺寸进行安装,切勿将冷却水管尺寸缩小,这样会引起高压超载,影响制冷效果及增加耗电量;3、风冷式冷冻机,请必须安装在距离墙壁一米以上空间位置,进出风口留出足够的空间,利于通风及设备维护,以免造成散热不良引起高压过载影响制冷效果及增加耗电量。
1 General概述This unit is fitted with the SIEMENS PLC controller together with othermatching electric appliances like imported contactor、thermal relay、airswitch and air switch,ensuring safe running of unit. In order to realizedependable operation of unit ,PLC is fitted with reliable programcontrolled system having application function up to current advancedlevel among the same trade. This unit is characterized byself-operation ,safety and dependability.本机组电气控制系统采用德国SIEMENS公司提供的PLC控制器,其他电器配套有进口接触器、热继电器、空气开关和三相电源监测器,可确保机组安全运行。
为了使机组可靠运行,电脑配置了完善的程序系统,应用功能达到目前同行业先进水平。
本电脑通讯端口采用RS-485信号标准的9针D型连接器,并符合EN50170所定义的PROFIBUS工业现场总线标准,实现计算机联网监控。
本机组有节能,自动运行,安全可靠等特点。
This operation instruction is applicable for the operation of Jirong water chillersof LRSFZ type.本操作指南适用于LRSFZ型风冷冷(热)水机组的操作运行。
2 Preparation before start-up开机前准备Make the following checks carefully before start-up:机组启动之前必须认真检查以下几项内容:Examine the electrical system (de-energized):电气系统的检查(断电检查):The internal parts of de-energized electrical system can be checked. thechecked items cover the tightness of bolts for wires、contactor etc,screwing-up of wiring for comp and reliable connection of plugged –incomponents and PLC module,(confirm if they come loose duringtransportation) to make sure contact well.在确定机组断电情况下,可对电控系统内部进行检查。
风冷冷(热)水机控制器功能说明书一、概述:1.本控制器适用于单压缩机、双压缩机风冷冷(热)水机组。
可以通过网络实现集中控制。
2.本控制器由主控板、线控器和连接线组成。
3.主要功能简介。
◆ 制冷功能; ◆ 制热功能; ◆ 液晶显示; ◆ 定时功能; ◆ 远程控制; ◆ 机组运行参数设置; ◆ 停电记忆功能; ◆ 辅助电加热; ◆ 用户功能选择; ◆ 二通阀连锁控制; ◆ 运行状态指示; ◆ 板换防冻; ◆ 冬季防冻功能; ◆ 水流不足保护; ◆ 高/低压保护; ◆ 制冷时,板换防冻保护; ◆ 制热时,出水温度过高保护; ◆ 压机安全启动,运行保护及平均开启功能; ◆ 18种故障显示及报警; ◆ 出水、回水、回风,室外盘管温度检测。
二、系统的构成:1.系统1:压缩机1、四通阀1、除霜感温器1、压缩机1高/低压开关、压缩机1过载。
2.系统2:压缩机2、四通阀2、除霜感温器2、压缩机2高/低压开关、压缩机2过载。
3.水路系统:水泵、水流开关、防冻开关、水泵过载、回水感温器、出水感温器、水泵过载。
4.辅助电加热(或曲轴箱加热器)、加热器、室外风机1、室外风机2、连锁二通阀开关信号、风机过载。
三、系统的设置:1、控制器有多项功能,可供用户选择(通过改变短路跳线的状态) 23、出厂设置为:4、用户需要更改设置,应在通电前完成。
四、控制器的操作及参数设定:面板图:RESET按键操作及设置:1、开/关键(ON/OFF):按此键一次,控制系统在待机状态和运行状态切换。
2、模式键(MODE):按此键一次,控制系统在“自动→制冷→制热→自动”间切换。
(模式选择,必须在停压机状态下才有效,改变模式后10秒内不可开压机。
)3、回复键(RESET):有故障报警时,当故障排除后,按此键可清除故障显示代码,使控制系统恢复正常运行状态。
4、增键(∧):直接按此键一次,设定温度在原来的基础上加1℃,如果设定温度已经为最大值,再按此键无效。
约克025G系列水冷柜机控制器技术方案一、概述1、控制器适用于水冷式单冷/冷暖型空调机2、控制器采用单片机控制,主要功能包括综合控制、信息处理及应急故障越权控制。
3、具体控制对象为:压缩机1~3台,风机1台,水泵1台,加热器2组4、控制器额定电压:220V/50HZ电压范围:180~245V AC5、回风温度显示范围:-9~50℃,显示精度:±1℃6、温度传感器工作范围:-50~105℃,精度:±0.5℃7、继电器压降(在最大电流下小于1%),绝缘电阻>100KΩ8、变压器:7.5/220VAC(蓝—蓝),10.5/220V AC(黄—黄) 10W9、回风感温探头线长为2.5m10、1/0板与主控板之间的连线长度为1.2m11、耐湿热:90~95HR 40±2℃12、耐振动:50HZ 0~1.5mm13、抗干扰:1000V辐射:1000V静电:4000V14、符合国家单元式空调机安全标准安全标准号:GB4706.32-1996二、控制功能1、压缩机数目设定通过拨动开关设定压缩机数目为1台、2台或3台2、单冷/冷暖设定通过拨动开关设定为单冷或冷暖方式。
3、有无水泵功能设定通过拨动开关设定为有或无水泵功能工作方式,在无水泵功能工作方式下,水泵控制及相应的报警及运行显示均不起作用。
4、自检/正常工作方式:通过一跳线接高电平时正常工作,接低电平时自检,自检功能只适合电子车间生产调试时使用。
5、初始化默认值:空调机出厂时,水泵拨动开关设定为无水泵功能工作方式,在制冷和制热模式下设定温度值默认为25℃,每一次上电使用前,在制冷和制热模式下设定温度值为上次记忆设定值6、模式选择在主压机或运行状态中,均可通过,轻触按钮设定以下面的工作模式,开用相应模式指示灯指示:冷暖型(水泵模式)单冷型7、温度设定上电后,空调机在停机、启动或运行状态下,在制冷和制热模式下数码管显示回风温度值,用户需要设定温度时,可按一下温度设定键设定温度,并用数码管显示设定温度值,设定温度操作完毕10s后自动回复到显示回风温度值。
东洋制冷冷水机说明书工业冷水机使用说明书使用前请详细阅读本说明书,并保存此书以备日后参考冷水机安装一、冷水机搬运冷水机搬运前应做好必要的防护措施,搬运过程中禁止倒置、碰撞、震动等,防止机组受损。
二、冷水机安装1、冷水机安装地面要平整,并牢固可靠;15匹以上的冷水机应建造安装基础,同时要找平安装点。
机组与墙之间的距离要有1米宽,使机组有足够散热和检修空间。
2、冷水机应水平安置,安装点应加减震器;冷水机应安置在通风较好、能防雨淋、灰尘较少、远离振动和无腐蚀性气体的地方。
3、按照规范的系统水管匹配和空间位置要求,优化设计水管系统,并按照相关安装标准进行施工安装。
4、水源水质较差和周围环境恶劣时,对于水冷式冷水机,冷冻水和冷却水系统必须安装过滤器;散热过滤装置必须及时清洗或更换。
5、对于封闭冷冻水系统,其最高处必须安装自动排气阀,最低处必须安装泄污排水接头。
6、对于水冷式冷水机,要根据机组制冷能力选用匹配的冷却塔。
7、冷冻水管试漏后,要包好保温层,避免冷量损失和防止管路滴水。
三、电源连接1、冷水机电源采用三相五线,电源线(R.S.T)接电源线、或单相线(R.S.E),(N)接零线,(E)接地线。
2、机组用主电源线经电控箱上的穿孔连接在箱内接线柱上,保证接线牢固。
若冷水机相位掣安装相反,控制面板上的红色指示灯(相位故障)亮,请将电源总掣关闭,然后将电源线R.S.T其中两相对调,再开启电源开关,这时电源指示灯亮,表明已恢复正常。
3、机组配电要求:注意:主电源电压:额定电压±10%,主电源频率:50±2%Hz主电源电压波动超过范围时,不准启动冷水机,否则视为错误操作,由此产生的机组损坏不在本公司保修、保养范围之内。
4、水系统的水流开关、水泵、冷却塔等连锁电路在必要时可正确连接在机组端子2和3控制电路中,将端子2和3短接线去掉。
5、冷水机组设有电流过载保护,压缩机排进气端之高低压保护,马达线圈过热保护,蒸发器防结冰保护,冷却水之水流连锁保护等多种保护措施。
深圳市凯德利冷机设备有限公司
机组安装、操作及维护说明书
安全须知
各系列机组在设计规范内运行时能够得到安全和可靠的服务,由于机组在使用压力、电机接线及装置设备等各方面的原因只有经过本公司培训的合格操作员和维修技师可以操作和维修本设备。
产品合格证产品名称风冷式冷水机组
型号KC-025DA
产品编号 MFC-2015091599
质量检验陈正东
检验日期
目录
一、机组的适用范围 (1)
二、规格 (1)
三、安装说明 (1)
四、操作说明 (1)
1、使用操作…………………………………………………………………………………… .. 1
2、面板操作简介 (2)
3、用户操作 (2)
4、故障显示及排除 (2)
五、故障排除 (3)
六、保养 (4)
七、注意事项 (4)
八、电路图……………………………………………………………………(见附页)
风冷式冷水机组操作手册
一﹑机组适用范围
在工业上广泛用于塑料﹑电子﹑化工﹑冶金﹑食品﹑制药﹑电镀﹑皮革﹑工艺和科研等﹔在商业上广泛用于酒店﹑宾馆﹑超级市场和影剧院等。
二﹑规格
機型KC-020DA
最低控制溫度7℃-12℃電源380V-50HZ
傳熱媒體水冷媒R-22
壓縮機(品牌)三洋冷凝器形式翅片式
蒸發器形式水箱盘管式
公稱能力56070 Kcal/h 冰水器進/出口尺寸2”
冷凍水量13.6m3/h 冷凝器進/出口尺寸
消耗電力21.7kw 機體尺寸1900*990*1860mm
三﹑安装说明
1﹑机器安装﹐要求平放﹐不可倾斜﹔
2﹑机器两侧应有一米左右保养空间﹔
3﹑冰水管管路务必接成回路﹐使冰水得以循环﹔
4﹑冰水管路必须保温﹔
5﹑接电源时请确定电源足以承担冷水机组最大负荷﹔
6﹑机组电源﹐必须单独控制﹔
7﹑必须接地线﹐以确保安全。
四﹑操作說明
启动机组前﹐应检查冰水管路阀门是否打开(注﹕长期停机后﹐再次开机前﹐应打开电
源24小时后再开启机组)﹔
机组控制﹕
1、使用操作(面板图)
本公司使用微电脑控制器,显示屏为模块式屏幕,。
显示界面的设计充分运用人类工程
学原理,使用操作简便直观,操作人员只需稍阅说明书就可上岗操作,其操作面板如图示。
1.1>按键指示灯
*COMP1* 压缩机1控制指示灯,灯亮允许启动否则不允许启动,由*COMP1*按
键控制.
*COMP2* 压缩机2控制指示灯,灯亮允许启动否则不允许启动,由*COMP2*按
键控制.
*RESET* 有故障时的指示灯(闪烁显示),无故障时按下<RESET>可关闭.
*PUMP* 机组运行指示灯,机组运行时此灯亮,否则灭.
*0FF* 延时停机指示灯,延时停机时闪烁点亮.
*SET* 参数设置指示灯,处于参数设置界面时此灯亮.
1.2>面板指示灯
*POWER* 电源指示灯,通电后灯亮.
*RUN* 机组运行指示器,非待机状态亮.
*ERROR* 故障指示灯,有故障时亮.
*COMP1* 压缩机1运行指示灯.
*COMP2* 压缩机2运行指示灯
2、面板操作键简介
2.1>面板中间为两个模块显示屏,PV屏显示实际温度,SV屏显示设定温度。
2.2>面板左边的5个LED灯分别指示:(从上到下)电源,运行,故障,压缩机1,压缩机2。
2.3>面板下侧两排8个按键分别为:, RESET(复位),UP (向上),DOWN(向下),SET(设置),PUMP(泵), COMP1(压缩机1),COMP2(压缩机2),OFF(停止)。
3、用户操作
3.1>开机显示
开机时,系统开始10秒倒计时,PV屏显示版本,SV屏显示倒计时时间。
3.2>用户主界面显示
程序倒计时完成后,进入用户界面显示::PV屏显示“OFF”(停机状态),SV 屏不显示。
此时,按“SET”可以修改当前设定温度,利用“UP”,“ DOWN”修改。
改完
后按“SET”确定退出,若干10秒钟不按“SET”键,电脑板将自动记录当前温度。
3.3>控制说明
(1)开机:按“PUMP”键启动机器:开冷冻泵---延时---开冷却风机---延时---根据能量调节开压缩机。
(2)关机:按“OFF”键停止机器:关所压缩机---延时---关冷却风机---延时---关冷冻泵。
(3)能量调节:a)只有1个压缩机:在升温过程中,当T﹥=Ts﹢△T时启动压缩
机;在降温过程中,当T﹤=Ts﹣△T时停止压缩机.
b)有2个压缩机时:在升温过程中,当T﹥Ts时启动1台压缩机,
当T﹥=Ts﹢△T时启动2台压缩机;在降温过程中,当T﹤Ts
时停止1台压缩机,当T﹤Ts﹣△T时停止2台压缩机.
(4)压缩机都停完后,延时了”冷却水泵/风机启动后延时”的时间,停掉冷却.
备注: △T为设置的控制偏差, Ts为设定的控制温度.
4、故障显示及排除
4.1>故障制约关系
当冷冻水泵出现故障时,关掉运行中的所有设备。
当冷却泵出现故障时,停冷却泵和所有的压缩机,冷冻水泵不停。
当某一台压缩机出现故障时,只停本身这台压缩机,其它压缩机,冷却泵和冷冻水泵不受影响。
当两台压缩机同时出现故障时,所有压缩机及冰水泵冷水泵全部停止。
4.2>故障代码显示
当机器运行出现故障时,SV显示屏会出现相应的代码。
故障代码故障名称说明
1 错相保护故障请检查三相电输入
2 1号压缩机高压请检查1号压缩机
3 1号压缩机低压请检查1号压缩机
4 1号压缩机过载请检查1号压缩机
5 2号压缩机高压请检查2号压缩机
6 2号压缩机低压请检查2号压缩机
7 2号压缩机过载请检查2号压缩机
8 冷冻水压过低请检查冷冻水泵
9 冷冻水泵过载请检查冷冻水泵
10 冷却水压过低(风机过热) 请检查冷却水泵(风机过热)
11 冷却水泵过载(风机过载) 请检查冷却水泵(风机过热)
12 出水温度过低
13 出水探头开路请检查出水温度探头
14 出水探头短路请检查出水温度探头
15 防冻故障请检查出水温度探头
当出现故障时,给出报警,同时“RESET”复位指示灯闪烁,发出报警声,此时找出故障原因,排除故障,并按“RESET”键消除报警声音,故障排除。
当出现多个故障时,按“UP”或“ DOWN”查询,所有的故障都被排除后,“RESET”指示灯熄灭。
“RESET”键在任何用户操作界面均有效。
当系统从无故障到出现故障时,自动进入故障查询状态。
自动进入故障查询界面后,当长时间不按任何键就自动返回。
警告﹕该机组参数已设定﹐请勿自行调整﹐如有特殊要求请与我公司售后服务部联系,否则因此引起的后果将不在保修范围内。
五﹑故障排除
当机组出现故障时﹐应观察异常现象指示﹐找出故障现象﹐然后断开总电源开关﹐根据下列步骤进行检查﹕
(1)﹑当出现压缩机高压异常时﹐应检查﹕
a. 冷却风机是否故障﹔
b﹑翅片是否清洁;
确认无误后﹐就按复位键进行复位﹐5分钟后再开机﹔
(2)﹑当出现压缩机低压异常时﹐应检查机组管路有无泄漏和阻塞现象﹐排除故
障后进行复位﹐过5分钟再开机﹔
(3)﹑显示温度过低时﹐应检查冰水管阀门是否打开和冰水是否正常循环无误﹐
过5分钟再开机﹔
(4)﹑当出现油压过低时﹐应通过窗口看机油是否充足﹐不足就加入﹔
(5)﹑当出现压缩机过载时﹐应检查﹕
a﹑电磁开关﹐有无老化﹑断路和接触不良等现象﹔
b﹑用高阻计检查压缩机的绝源电阻是否正常﹔
c﹑用万能表检测压缩机的线圈电阻产否平衡﹐如有异常﹐务必更换压缩机(注意﹕压缩机在此情况下﹐没有找出故障原因﹐不能盲目开机)﹔
(6)﹑当出现水泵过载时﹐检查方法同(5)。
六﹑保养
1﹑高压计如果超过23kg/cm2时﹐应检查翅片﹐并清洗冷却系统﹔
2﹑机组长期停止使用﹐应开闭总电源开关。
七﹑注意事项
本公司的产品在一年内免费维修。
有以下情行者﹐将不予保修﹕
1﹑自行拆卸机组者﹔
2﹑自行调整压力控制器﹑温度控制器和计算机控制板数据﹐自行加冷冻油和制
冷剂造成机组损坏的﹔
3﹑自行更换电器组件和改变控制线路以及制冷系统的冷媒管路造成设备和配件
损坏的﹔
4﹑由客户自行运输或安装不当造成机组设备和配件损坏的﹔ 5﹑由贵公司热力负荷超出机组负荷而造成机组损坏的。
八﹑电路图(见附页)
温度探头公共端
2号压缩机过载
3冷却水压过低\线控开关
冷却过载
冷冻水压过低
冷冻水泵过载
防冻故障
68754开关量公共端
电源错相保护
1号压缩机高压
1号压缩机低压
1号压缩机过载
2号压缩机高压
2号压缩机低压
出水温度探头
2187备用
4
6532
1
冷却水泵\冷却风机
冷冻水泵
1号压缩机
2号压缩机
21543报警
7698
2
1X1.GW511A.DGTSJX.F01C.电气连接示意图.冷水机A C 220V
FU L N AC220V