某工厂供配电系统设计毕业设计论文
- 格式:pdf
- 大小:4.74 MB
- 文档页数:20
ZHEJIANG WATER CONSERV ANCY AND HYDROPOWER COLLEGE 毕业设计说明书题目:海天机械厂35kV供配电系统设计系(部):电气工程系专业班级:姓名:学号:指导教师:20 年06 月03 日摘要此机械制造长属于大型企业,是35KV总降,一条进线对应一个变电所。
为了方便设计说明,选了一个金工车间进行具体的计算设计。
这个车间有很多的设备,而且几组设备是并行的流水线。
首先进行负荷计算,再参考电源进线方向,确定变压器的台数和容量。
根据厂内负荷情况,从技术和经济合理性确定厂区配电电压。
按负荷计算求出总降压变电所的功率因数,通过查表或计算求出达到供电部门要求数值所需补偿的无功率。
用总降压变电所主结线图,设备材料表和投资概算表达设计成果。
参考本地区气象地质材料,设计防雷装置。
进行防直击的避雷针保护范围计算,避免产生反击现象的空间距离计算,按避雷器的基本参数选择防雷电冲击波的避雷器的规格型号,并确定其接线部位。
进行避雷灭弧电压,频放电电压和最大允许安装距离检验以及冲击接地电阻计算。
最后根据总降压变电所变、配电装置总体布置设计综合前述设计计算结果,参照国家有关规程规定,进行内外的变、配电装置的总体布置和施工设计。
关键词:负荷计算;短路计算;高、低压设备选择;继电保护ABSTRACTThis machinery manufacturing long belong to large enterprise, is a 35KV total fall into line corresponds to a substation. In order to facilitate the design descriptions, choose a metalworking shop specific calculation design.This workshop has a lot of equipment, and several groups of equipment is parallel lines. First, then load calculation reference power into line, determine the direction of transformer capacity and the Numbers. According to the situation from inside the plant load technical and economical rationality sure factory distribution voltage. According to the load calculation work out the power factor of general voltage substation, through the look-up table to ask out or computational power supply departments requirements needed without power numerical compensation. General voltage substation with main and equipment and materials chart table and investment estimate express design results. Reference this area of geological materials, design meteorological lightning protection device. The scope of protection of direct lightning calculation, avoid to produce counterattack phenomenon according to the space distance calculations, the basic parameters of the lightning arresters choice of electric shock wave lightning arrester specifications, and determine its wiring parts. For corona arcing voltage, frequency discharging voltage and maximum allowed to install grounding resistance and impact from inspection calculated. Finally, according to the general voltage substation change, power distribution equipment layout design integrated the design and calculation results, according to relevant state regulations sets, the variable, power distribution device inside the overall layout and construction design.Keywords:load calculation; Short circuit calculation; High and low voltage equipments choice; Relay protection目录摘要 (1)ABSTRACT (2)目录 (3)引言 (4)1. 负荷计算及变压器的选择 (5) (5)负荷计算的方法 (5) (5) (6) (7)变压器的选择 (7) (7) (8) (8)2. 电气主接线设计 (9) (9) (9) (10) (12)3. 防雷与接地 (18) (18) (18) (18)接地 (19)接地与接地装置 (19) (20)结论 (22)参考文献 (23)附录 (24)计算书 (24)变电所平面图 (34)电气主接线图 (35)引言本变电站设计说明书是根据浙江水利水电专科学校电气工程系毕业设计任务书《海天通用机械制造公司供配电系统电气设计》编拟的。
工厂配电论文范文引言工厂配电系统是工业生产过程中的重要组成部分,它负责将来自变电站的电能分配给不同的负载设备,确保工厂正常运行。
然而,在实际的工厂配电系统中,由于负荷变化、线路老化、设备故障等原因,可能会出现电压不稳、电流过载以及电能浪费等问题。
因此,对工厂配电系统进行合理的设计和优化,对保障工厂的安全稳定运行具有重要意义。
本论文将基于一个实际工厂的配电系统,对其中的问题进行分析和解决方案的提出。
首先,将对工厂的负荷特点进行分析,包括负荷类型、负荷特性以及负荷变化规律。
然后,将对现有的配电系统进行评估,分析其存在的问题和改进的空间。
最后,根据分析结果提出相应的优化方案,并进行经济性分析和可行性评估。
负荷特点分析工厂配电系统的负荷特点对系统设计和优化具有重要影响。
在实际分析中,可以将负荷分为三类:恒定负荷、可变负荷和瞬变负荷。
恒定负荷是指在工作过程中电流和功率基本保持不变的负荷,比如照明和空调系统。
可变负荷是指在工作过程中电流和功率会有一定变化的负荷,比如生产机器和设备。
瞬变负荷是指在特定情况下电流和功率会出现突变的负荷,比如启动大功率设备和短路故障。
在具体分析负荷特点时,还需要考虑负荷的功率因数和功率因数的波动。
功率因数是指电流和电压之间的相位差,其数值范围在0到1之间。
当功率因数接近1时,表示负荷的有功功率占主导地位,负荷对系统的影响较小;当功率因数接近0时,表示负荷的无功功率占主导地位,负荷对系统的影响较大。
功率因数的波动可能会导致系统电压波动和电流谐波问题,对系统稳定性和设备寿命产生不良影响。
现有系统评估对现有工厂配电系统的评估可以从三个方面来进行:系统的接地方式、系统的电力负荷和系统的电力因数。
系统的接地方式工厂配电系统的接地方式主要有三种:单点接地、多点接地和无中点接地。
单点接地是指只存在一个接地点,多点接地是指存在多个接地点,无中点接地是指系统没有接地点。
不同的接地方式对系统的故障处理、保护及设备安全都有一定的影响。
毕业设计论文钢铁厂供配电系统设计摘要本文按照供电系统可靠性、经济性的要求,根据钢铁厂的负荷性质、负荷大小和负荷的分布情况对本厂供电系统做了全面综合的分析,详细阐述了工厂总降压变电所实现的理论依据。
通过对整个供电系统的分析和对钢铁厂的电力负荷、功率补偿、短路电流的计算,合理的选择电力变压器、断路器等各种电气设备;对工厂总降压变电所不同的主接线方案进行比较,选择可靠性高,经济性好的主接线方案,实现了工厂供电系统安全、可靠、优质、经济地运行。
关键词电力负荷;功率补偿;短路电流;防雷与接地目录1电力负荷及其计算 (2)1.1工厂的电力负荷 (2)1.2计算负荷确定的方法 (2)1.3变压器功率损耗的计算 (5)1.4工厂的计算负荷和年电能消耗量 (6)2 变配电所选择 (12)2.1变配电所的类型 (12)2.2变电所主变压器容量的选择 (13)3 电气主接线 (14)3.1具有母线的电气主接线 (15)3.2无母线的电气主接线 (16)3.3工厂总降压变电所的主接线方案选择 (17)4 电力线路接线方式 (19)4.1高压放射式接线 (19)4.2高压树干式接线 (19)5 电力线路的敷设 05.1架空线路 05.2电缆线路 06 高压供电线路导线截面及型号的选择 06.1按经济电流密度选择导线截面 06.2导线截面及型号的选择 (1)6.3母线的选择 (2)7 电气设备的选择 (2)7.1电气设备选择的一般条件 (2)7.2高压一次设备的选择 (3)8 短路电流计算 (10)8.1三相短路电流的计算 (10)8.2电力系统的短路电流计算 (11)9 防雷与接地 (13)10 附图纸 (16)11 谢辞 (17)12 参考文献 (18)1电力负荷及其计算1.1 工厂的电力负荷 (1)电力负荷的概念电力负荷又称为电力负载。
它有两重含义:一是指耗用电能的用电设备或用电单位(用户),如说重要负荷、不重要负荷、动力负荷、照明负荷等。
毕业设计某钢铁厂车间供配电系统设计摘要:本文主要围绕钢铁厂车间的供配电系统进行设计,包括正常工作状态下的系统组成、电压等级选择、电源接入方式、输电线路的选择、低压配电系统的设计以及系统的可靠性评估等方面。
通过合理设计和优化,能够提高供配电系统的稳定性和可靠性,确保车间生产正常进行。
关键词:供配电系统;电压等级;电源接入方式;输电线路;低压配电系统;可靠性评估1.引言供配电系统是钢铁厂车间正常运作的关键设施之一,对于保证车间生产安全和稳定运行起着重要作用。
因此,对该车间供配电系统进行合理设计至关重要。
2.正常工作状态下的系统组成车间供配电系统主要由电源接入装置、主配电装置、低压配电系统以及输电线路等组成。
电源接入装置用于将电力系统中的电能引入到车间内,主配电装置用于将电能分配到各个设备或设施,低压配电系统用于将电能进一步分配到车间内的各个电气设备或用电点,输电线路则负责将电能从电源接入装置传输到主配电装置。
3.电压等级选择根据钢铁厂车间的实际需求以及国家标准,可以选择合适的电压等级。
一般情况下,钢铁厂车间的供配电系统电压等级选择为10kV或35kV,以满足车间内设备的电能需求。
4.电源接入方式电源接入方式可以选择直接接入或通过变电站接入。
直接接入方式适用于电力系统供能较为稳定的地区,能够减少设备的中间环节,提高系统的可靠性;而通过变电站接入方式适用于电力系统供能不稳定的地区,能够通过变电站对电能进行调节和稳定,保证车间的正常运行。
5.输电线路的选择输电线路的选择应根据钢铁厂车间的实际情况来确定。
一般情况下,可以选择架空线路或地下电缆线路。
架空线路施工简便、维护方便,适用于较为开阔的场地;地下电缆线路施工较为复杂,但不易受天气条件的影响,适用于较为狭小的场地。
6.低压配电系统的设计低压配电系统主要包括开关设备、电缆和配电柜等。
根据车间内的用电设备情况,合理设计低压配电系统的布置和容量,能够保证车间内各个电气设备的正常运行。
机械工厂供配电系统电气设计毕业论文设计在机械制造行业中,供配电系统在生产中起着至关重要的作用。
这个系统由一系列的设备和设施组成,包括发电机、变压器、断路器、开关和电缆等。
这些设备和设施的设计和配备会直接影响机械工厂的生产效率和质量。
因此,我们的毕业论文选择了机械工厂的供配电系统电气设计作为研究主题。
供配电系统电气设计包括了多个方面,如负载计算、设备选型、线路设计、接线方式和系统保护等。
其中,最重要的是负载计算。
我们根据机械工厂每个车间的总功率需求,计算出每个车间的负载,并进一步根据负载特点,选择相应的设备。
为了确保供配电系统的可靠性,设备选择是至关重要的。
具体包括发电机和变压器的容量和介质类型、断路器和开关的额定电流、电缆的截面积和材料等。
在选择中,我们不仅要考虑设备的性能和稳定性,也要考虑成本和使用寿命。
在进行线路设计时,我们还要保证线路的合理布局和合适的距离,以免因不当的设计导致电路短路、漏电等问题。
在接线方式选择时也需要注意,以免出现接错或接不牢等极端情况,避免出现短路或其他事故。
此外,系统保护也是电气设计中不可忽视的一环。
我们要保证系统在故障时能够及时跳闸,避免对设备以及人员的伤害。
对于系统的保护,我们可以使用保护继电器、接地保护和过载保护等方式来保护系统的安全和稳定性。
通过合理配置的保护和自动控制设备,可以有效地减少供电中断的几率。
同时,在电气设计中,我们也需要考虑到系统的扩展性。
为了适应不同生产情况的变化,我们在选用设备和搭建系统时也要考虑到未来的扩展需求。
因此,在设计时应排除冗余投资,低成本、高效建设是我们努力的方向。
在实践中,我们还要认真解决设备运行中出现的问题。
比如,我们会遇到因设备老化、环境影响、因长时间运行导致的设备故障等问题。
在这种情况下,我们首先需要对设备进行诊断,找到问题的根源,然后采取针对性措施进行解决。
综上所述,机械工厂供配电系统电气设计需要考虑系统的可靠性、可扩展性、以及系统保护。
工厂供电论文(优秀范文五篇)第一篇:工厂供电论文摘要:工厂供电指工厂所需电能的供应和分配。
随着社会进步,工厂的“工业4。
0”的实现大大提高生产效率和产量,降低运营成本,减轻工人的劳动强度,逐步实现生产过程自动化。
因而对工厂供电的安全、稳定、智能化提出更高的要求。
关键词:工厂;电气设计;智能化;施工;工厂电气设计1.1 设计要求工厂供电保证工厂生产和生活用电的需要,供电设计必须满足以下基本要求:(1)遵守国家规程、执行政策;(2)安全可靠;(3)降低成本,优质经济;(4)近期为主、考虑发展。
1.2 设计内容及步骤随着工厂“4。
0工业智能化”的推广,对厂区电能提出了更高的要求,因而作为厂区供电设计者必须全面了解国家供电标准及规范、强电动力系统、弱电系统、网络控制系统和消防系统等规范和相关知识。
本论文主要针对强电动力系统进行阐述。
近年来,我先后参与设计了5个新建厂区的供配电设计,对厂区生产工艺、负荷布局、负荷数量和性质,供电安全可靠型,经济的分配电能和智能控制方面有一定的总结和归纳,整理如下:厂区强电动力系统主要分为:外线高压设计、配电站设计、厂区配电系统设计和防雷接地设计四个部分。
每个项目的工厂电气设计,会从以下方面进行设计:(1)对所设计的厂区进行全面了解,主要对用电性质和用电负荷,掌握相关的设备和设施的用电参数。
(2)负荷计算。
计算厂区各用电设施的负荷,统计各车间和厂区的负荷,结合车间功率损耗和线路损耗,求出全厂区变电所高、低压侧计算负荷及总功率因数。
(3)工厂供、配电系统短路电流计算。
根据不同运行方式下的短路参数,求出不同运行方式下各点的三相及两相短路电流,保障用电安全(此项最容易忽视的环节)。
(4)厂区总配电室选址和变压器选型设计。
根据当地供电局批复的高压电源进线方向,综合考虑总配电室的有关因素,计算厂区负荷、短路电流以及扩建和备用的需要,确定变压器型号和高、低接线方式。
配电室选址建议工厂采用中心敷设方式,可有效的减少电缆压降和能耗损失,降低施工成本。
摘要工厂供电,是指工厂所需的电能的供应与分配,也称工厂配电。
众所周知,电能是现代工业生产的主要能源和动力。
电能既能易于由其他形式的能量转换而来,而易于转换为其他形式的能量以供应用。
电能的输送和分配既简单经济,又便于控制、调节和测量,有利于实现生产过程自动化,而且现代社会的信息技术和其他高新技术无疑不是建立在电能应用的基础之上的。
因此电能在现代工业生产及整个国民经济生活中应用极为广泛。
本论文设计首先计算电力负荷和变压器的台数、容量;利用所学的知识确定变电所的位置。
计算出短路电流的大小,选出不同型号的变压器,进而确定变压器的连接组别,画出必要的变电所主接线图。
关键词:主接线图、短路电流、电力负荷、变压器AbstratThefactorypowersupply,itistopointtothefactorypowersupplyanddis tribution,alsocalledplantdistribution.Asisknowntoall,theelectricityisofmodernindustrialproduction,th emainformofenergyandpower.Electricenergycaneasilybyotherformsofenergyconversion,andeasytoconverttootherformsofenergytosupplytheu se.Electricpowertransmissionanddistributionofeconomicissimple,an deasytocontrol,adjustandmeasurement,whichishelpfultorealizethepr oductionprocessautomation,andthemodernsocialinformationtechnolog yandotherhigh-techundoubtedlyisnotbasedonelectricpoweronthebasis ofapplicationof.Sothepowerinthemodernindustryproductionandthewho lenationaleconomiclifearewidely.Thisthesisdesignfirstcalculatedpowerloadandtransformersets,cap acity;Useknowledgetodeterminethepositionofthesubstation.Tocalcul atetheshortcircuitcurrentsize,choosedifferenttypesoftransformer, andthendeterminethetransformerconnectioncategories,drawthenecess arysubstationmainwiringdiagram。
工厂供配电设计毕业论文工厂供配电设计毕业论文随着工业化进程的不断推进,工厂的供配电系统设计变得越来越重要。
供配电系统作为工厂的核心设施之一,直接关系到工厂的正常运行和生产效率。
因此,对于工厂供配电系统设计的研究和优化成为了许多工程师和研究人员的关注焦点。
工厂供配电系统设计的目标是确保电力供应的可靠性、安全性和经济性。
首先,可靠性是供配电系统设计的首要考虑因素。
一个工厂的电力供应中断可能导致生产线停工,造成巨大的经济损失。
因此,供配电系统的设计必须考虑到各种故障情况,并采取相应的措施,如备用电源和自动切换装置,以确保电力供应的连续性。
其次,供配电系统设计还必须注重安全性。
电力供应系统中存在着各种潜在的危险,如电弧、电击和火灾等。
因此,在供配电系统设计中,必须合理选择电缆、开关设备和保护装置,以确保电力供应的安全性。
此外,还需要制定相应的操作规程和紧急预案,以应对突发情况。
最后,供配电系统设计还需要考虑经济性。
工厂供配电系统的建设和运行成本是一个重要的考虑因素。
在设计中,需要合理选择电缆、开关设备和保护装置,以及优化供配电系统的拓扑结构,以降低成本并提高效率。
此外,还需要对供配电系统进行定期维护和检修,以延长设备的使用寿命并降低故障率。
在工厂供配电系统设计中,还需要考虑一些特殊因素。
例如,对于大型工厂来说,供配电系统的容量和可扩展性是一个重要的考虑因素。
随着工厂的扩大和生产需求的增加,供配电系统需要具备足够的容量和灵活性,以适应未来的发展。
此外,对于一些特殊行业,如化工和石油化工,供配电系统的设计还需要考虑到防爆和防腐等特殊要求。
总之,工厂供配电系统设计是一个综合性的工程问题,需要考虑到可靠性、安全性和经济性等多个方面。
通过合理选择设备、优化系统结构和制定相应的操作规程,可以确保工厂的电力供应连续、安全和经济。
在未来的研究中,还可以进一步探索新的技术和方法,以提高供配电系统的性能和效率。
毕业设计(论文)设计(论文)题目:小型工厂的供配电系统设计诚信承诺书本人慎重承诺和声明:本人在毕业设计(论文)过程中遵守学校有关规定,恪守学术规范,在指导教师的指导下独立完成,没有剽窃和抄袭他人的学术观点、思想和成果,未篡改研究数据,若有违规行为的发生,我愿接受学校处理,并承担一切法律责任。
论文作者签名:年月日重庆邮电大学本科毕业设计(论文)摘要电能是工业生产的主要动力能源,是现代文明的物质技术基础。
没有电力,就没有国民经济的现代化。
现代社会的信息化和网络化,都是建立在电气化的基础之上的。
电力供应如果突然中断,则将对这些用电部门造成严重的影响。
工厂供配电设计的任务是从电力系统取得电源,经过合理的传输、变换,分配到工厂车间中每一个用电设备上。
因而工厂供配电的设计对于一个企业来说是相当重要的,是企业生产出高品质产品的硬件保证。
在本设计中,依据给定的设计范围和基础资料,对塑料制品厂全厂总配变电所进行了初步的电气设计。
通过负荷计算、无功补偿、电气主接线选择、短路电流计算、电气设备选择、继电保护及防雷装置设计等一系列具体工作,按照课题的具体要求,使设计方案能够符合国家标准的有关规定,体现了安全、可靠、灵活、经济的原则,为塑料制品厂供电的可靠性、安全生产和经济运行提供了强有力的保证。
并根据设计要求,绘制了总配电所电气主接线图、1~5号车间变电所主接线图和总配电所平面布置简图等有关设计图纸。
通过这次设计,塑料制品厂的供配电系统的基本功能就实现了,从该厂附近的变电所取得10kV电源,通过设计中的配电所进行电力的传输分配到5个车间变电所,车间变电所把电压从10kV变成400V给各个车间设备以及工厂生活提供电能。
【关键词】总配电所主接线变压器短路电流继电保护ABSTRACTThe power of electricity is the major motive source of industrial production, material and technical basis of modern civilization. No electricity,no modern economy. Modern society's information and network, are based on the electrification of. If the sudden interruption of power supply, it will cause serious impact on these electricity sector. The mission of the factory power supply and distribution design is getting power source from the electric system and assign to each electricity using equipment of the factory workshop via reasonable transmission and transformation. Therefore, the factory power supply and distribution design is very important for an enterprise. It is also a high quality certificate of the production.In this design, I make a initial electric design for the power distribution of the whole plastic products factory according to the provided range of design and basic material. To make sure that the design is conformance to the national criterion and to be safe, dependable flexible and economical, I do the design after a series of load calculation, Reactive power compensation, Electrical main wiring choice, Short-circuit current calculation, electrical equipment choice, relay-protection and prevent thunder according to the particular demand of the course. It also makes sure that the course of power supply is dependable, safe and economical. At the same time, according to the demand, I have draw the main electrical power distribution by the total one-way wiring diagram,1 to 5 workshop substation main wiring diagram and the total distribution of the schematic layout.Through this design, supply and distribution system of the basic functions of plastic products factory is achieved, to obtain power from 10kV substation near the plant, carried out by the design of the electric power transmission and distribution substation assigned to five workshops, the workshop substation the voltage from 10kV to 400V into each workshop to provide power equipment and plant life.【Key words】Total substation Electrical main wiring Transformer Short-circuit current Relay- protection目录前言....................................................................................................................... - 1 - 第一章绪论........................................................................................................... - 2 - 第一节工厂供电意义和要求........................................................................... - 2 - 第二节本厂的基本概况及设计要求............................................................... - 2 -一、生产任务及车间组成............................................................................. - 2 -二、负荷性质及负荷情况............................................................................. - 3 -三、供用电协议............................................................................................. - 3 -四、本厂自然条件......................................................................................... - 3 - 第三节本章小结............................................................................................... - 4 - 第二章负荷计算及无功补偿............................................................................... - 4 - 第一节供电电压的选择................................................................................... - 5 - 第二节负荷计算............................................................................................... - 5 -一、负荷计算的定义及计算方法................................................................. - 5 -二、负荷计算结果......................................................................................... - 7 - 第三节功率补偿............................................................................................... - 8 -一、意义......................................................................................................... - 8 -二、电容补偿................................................................................................. - 8 -三、补偿装置选择......................................................................................... - 9 - 第四节本章小结............................................................................................. - 10 - 第三章总配电所设计......................................................................................... - 11 - 第一节配电所的位置及型式......................................................................... - 11 -一、所址选择的一般原则........................................................................... - 11 -二、总体布置要求....................................................................................... - 11 - 第二节主接线方案......................................................................................... - 12 -一、主接线的设计原则及基本要求........................................................... - 12 -二、电气主接线的设计............................................................................... - 12 - 第三节短路电流计算..................................................................................... - 13 -一、产生短路电流的原因及危害............................................................... - 13 -二、短路电流计算的目的及计算方法....................................................... - 13 -三、短路电流计算....................................................................................... - 14 - 第四节主要电气设备选择............................................................................. - 16 -一、选择条件............................................................................................... - 16 -二、电气设备选择校验............................................................................... - 18 - 第五节配电所进出线的选择......................................................................... - 19 -一、概述....................................................................................................... - 19 -二、10kV架空线的选择 ............................................................................. - 20 -三、备用电源电缆进线的选择................................................................... - 20 -四、10kV母线的选择 ................................................................................. - 21 -五、配电所出线的选择............................................................................... - 22 - 第六节主要设备继电装置的整定及保护..................................................... - 23 -一、概述....................................................................................................... - 23 -二、继电保护装置的接线方式................................................................... - 23 -三、继电保护装置的操作方式................................................................... - 23 -四、电流速断保护....................................................................................... - 24 -五、回路方案选择与继电保护的整定....................................................... - 24 - 第七节防雷及接地......................................................................................... - 25 -一、概述....................................................................................................... - 25 -二、防雷措施............................................................................................... - 26 -三、接地装置............................................................................................... - 26 - 第八节本章小结............................................................................................. - 27 - 第四章车间变电所设计..................................................................................... - 28 - 第一节车间负荷计算及无功补偿................................................................. - 28 -一、车间负荷计算....................................................................................... - 28 -二、车间无功补偿....................................................................................... - 28 - 第二节车间变压器的选择............................................................................. - 29 -一、变电所变压器台数的选择................................................................... - 29 -二、变电所主变压器容量的选择............................................................... - 29 -三、主变压器相数选择............................................................................... - 30 -四、主变压器型号的选择........................................................................... - 30 - 第三节短路电流计算及一次设备的选择..................................................... - 30 -一、短路电流计算....................................................................................... - 30 -二、一次设备的选择................................................................................... - 32 - 第四节车间变电所布置................................................................................. - 33 -一、车间变电所的类型............................................................................... - 33 -二、车间变电所所址的选择....................................................................... - 33 -第五节车间变电所的继保装置的整定......................................................... - 33 -一、主变压器的继电保护装置及低压侧的保护装置............................... - 33 - 第六节防雷和接地......................................................................................... - 34 - 第七节本章小结............................................................................................. - 35 - 结论..................................................................................................................... - 36 - 致谢..................................................................................................................... - 37 - 参考文献................................................................................................................. - 38 - 附录..................................................................................................................... - 39 -一、英文原文.................................................................................................. - 39 -二、英文翻译.................................................................................................. - 46 -三、工程设计图纸.......................................................................................... - 52 -前言毕业设计在大学的教学过程显得非常重要,通过这次毕业设计进一步加深了在大学期间所学的工厂供电的认识,理解并掌握了关于工厂的配电系统是如何进行规划与设计,如何在国家相关规定下进行运行。
系统设计课程任务书1、设计题目:某工厂供配电系统电气部分设计2、设计目的:通过本工程设计:熟悉供配电系统初步设计必须遵循的原则、基本内容、设计程序、设计规范等,锻炼工程设计、技术经济分析比较、工程计算、工具书使用等能力,并了解供电系统前沿技术及先进设备。
3、设计依据:本设计是为某纺织厂设计一座高压配电所。
⑴该纺织厂主要生产化纤产品,工厂个车间符合情况见附表。
该厂大部分车间为三班制,少数车间为两班或一班制,年最大有功负荷利用小时数为5800h。
该厂属二级负荷。
⑵供电电源:从某35/10kv变电站提供电源,用双回10kv架空线向工厂供电,此站距厂1km;变电站短路数据:Sk.max=200MVA,Sk.min=110MVA。
⑶当地供电部门要求工厂:①过电流保护整定时间不大于1.0s;②在工厂10kv电源侧进行电能计量;③功率因数应不低于0.9⑷工厂自然条件:年最高气温39℃,年平均气温23℃,年最低温-5℃,年最热月平均最高气温33℃,年最热平均气温2℃,年最热月地下0.8m处平均温度25℃,主导风向为南风,年雷暴日数52。
平均海拔22m,地层以砂粘土为主。
4、设计的具体任务与要求⑴工厂的负荷计算及无功补偿,确定各车间变电所变压器型式、容量和数量。
⑵设计和论证变电站的主接线,并作图;结合主接线方案确定主变压器型式、容量和数量⑶短路计算,并选择校验一次设备。
⑷选择并校验电源进线及工厂高压配电线路。
⑸变电站防雷保护规划设计及接地装置的设计。
⑹变电站防雷保护规划设计及接地装置的设计。
⑺作电气平面总布置图。
附表:工厂负荷情况摘要随着国民经济的发展,电能需求量越来越大,其中城市用电量更是急剧增加。
目前,我国一般大、中型城市的市中心地区每平方公里的负荷密度平均已达左右,有些城市市中心局部地区的负荷密度甚至高达上万千瓦,乃至几万千瓦,且有继续增长的势头。
因此供配电系统的发展趋势是:提高供电电压:如以进城,用配电。