(完整)西安市某办公楼空调设计
- 格式:doc
- 大小:268.50 KB
- 文档页数:21
目录一负荷计算方法 ................................................................................. 错误!未定义书签。
1冷负荷计算 .................................................................................. 错误!未定义书签。
2根据冷负荷系数法 ...................................................................... 错误!未定义书签。
3热负荷计算 .................................................................................. 错误!未定义书签。
二建筑物地理信息 ............................................................................. 错误!未定义书签。
三建筑物围护结构信息 ..................................................................... 错误!未定义书签。
1建筑物墙体 .................................................................................. 错误!未定义书签。
2建筑物窗体及遮阳设施 .............................................................. 错误!未定义书签。
3采暖设计中的参数 ...................................................................... 错误!未定义书签。
摘要中国的建筑行业正处于飞速发展的阶段,人们对生活环境的要求也越来越高,而生活环境最主要的就是居住环境,这种需求带动了中国的空调制冷业的发展。
几种空气调节系统,全空气系统中的空气不仅承担室内的显热负荷而且承担着潜热负荷,空气—水系统有几种:一种是将新风处理到室内空气状态的等焓线,新风只承担室内显热负荷。
此时的风机盘管有凝结水容易长霉不利于室内卫生。
一种是将新风处理到室内空气状态的等湿线,新风承担显热负荷和部分潜热负荷。
一种是将新风处理到室内空气状态的等湿线以下,空气承担室内的潜热负荷,风机盘馆是干燥的,但此时处理空气的冷源温度较低全空气系统一般用于高大空间,如体育馆影剧院大剧院之类的。
空气—水系统一般用于宾馆酒楼写字楼等小空间又需新风的场所。
全空气系统的空气处理是在中央空调的集体处处理。
关键词:建筑居住环境;空调制冷;全空气系统;空气—水系统1.绪论1.1我国暖通空调的现状及其发展进入90年代后,我国的居住环境和工业生产环境都已广泛地应用空调,空调技术已成为衡量建筑现代化水平的重要标志之一。
90年代中期,由于大中城市电力供应紧张,供电部门开始重视需求管理及削峰填谷,蓄冷空调技术提到了议事日程。
近年来,由于能源结构的变化,促进了吸收式冷热水机组的快速发展,以及热泵技术在长江中下游地区的应用。
随着生产和科技的不断发展,人类对空调技术也进行了一系列的改进,同时也在积极研究环保、节能的空调产品和技术,已经投入使用了冰蓄冷空调系统、燃气空调、VAV空调系统、地源热泵系统等。
暖通空调技术的发展,必然会受到能源、环境条件的制约,所以能源的综合利用、节能、保护环境及趋向自然的舒适环境必然是今后发展的主题。
1.2建筑空调系统节能国内外研究现状1.2.1建筑空调系统节能国外研究现状能源是整个经济系统的基本组成部份,作为一个能源消耗大国,美国在节能和提高能源利用率方面投入了大量的人力、物力。
在美国的整个能源消耗中,有约1/3以上消耗在建筑能耗上,这些能耗用来满足人们的热舒适、空气品质、提高人们的生活质量。
西安市某广电大厦空调系统设计詹佳伦(青岛理工大学,山东 青岛 266000)摘要:本设计主要是对西安市某广电大厦空调系统进行设计,本大楼分楼下一层楼上二十三层,其中需要进行空调设计的是从楼上一层至二十一层,我所设计部分是楼下一层的设备层,以及楼上一至四层的裙房部分,设计主要包括楼下机房的布置,楼上一些特殊房间的空调布置,其中包括一至四层基础层及裙房部分办公室、休息室、大厅的空调布置,以及单独裙房部分大空间的空调设计,同时还有对各分区内的排风及防排烟布置,由于是广电大厦,部分机组的噪声需要得到控制,不得影响广播电视以及舞台表演,其中裙房中的大空间是一个大演播厅,层高高达十四点八米,因此选用了双侧喷头对喷送风的送风形式,并进行了详细的设计计算确定了布置位置,及个数。
关键词:空调设计;裙房;噪声;大空间;全空气1 绪论人们的生活依靠于建筑,而建筑品质的高低就影响到人类生活、工作的质量。
为满足人类生活、工作的要求,改善并提高内环境,是人们始终的追求。
现代的采暖通风空调技术在我国的发展起步较晚,但随着应用的增多,促进了采暖通风空调产业的发展。
本设计地点是西安市,设计部分为楼下负一层及楼上一至四层,其中裙房部分是一至三层,基础层是一至四层。
需要进行空气调节的是一至四层,总层高17米,最大冷符合达到725千瓦。
负一层为设备用房,主要就是设备间、水泵房,用于安置冷水机组,一层主要有大厅、接待室、办公室、化妆间、大演播厅。
二层多是办公室,以及部分导演室。
三层有一间食品加工间及办公室,导演室等。
四层有休息室、接待室、办公室、资料室。
其中一层至三层层高均为4.4米,四层单独是3.8米,设备布置一至三层均放置在4米处,四层及以上均放置在3米处。
空调冷热媒参数:冷水供回水温度:7-12℃。
为满足人们生活、工作要求尽可能的提供适宜的内环境,并根据建筑结构,采用满足规范要求的系统进行设计,同时将排风、排烟以及噪音等因素纳入考虑。
一、设计题目西安(北京,郑州、成都、杭州)综合办公楼空调设计。
二、原始资料1. 概述:全楼共有地上六层;地上一层为贵宾接待室、机房控制室、接待准备室、产品展示厅、洽谈室等;二层为阅览室、活动室、办公室等;三层为总共办、档案室和开放式办公室等;四层为大、小会议室和开放式办公室等;五层为总会议室、办公室等;六层为休息室、会议室和办公室等。
2. 冷热源:空调冷、热源拟采用热泵机组,机组布置在专用机房。
机房拟专用设备机房,建筑尺寸另定。
机房夏季提供7~12℃冷媒水;冬季提供45~55℃低温热水。
3. 土建方面:建筑平、剖、立面图(共14张)三、设计内容及任务1. 设计的主要内容(1)、确定最佳空调方案(集中式、半集中式、分散式空调系统;全水、全空气、空气—水系统等各种方案比较);(2)、计算空调负荷(夏季冷负荷,冬季热负荷);(3)、选择空调设备(夏季为设计工况,冬季为校核工况);(4)、布置空调系统;(5)、风、水系统阻力计算;(6)、冷热站设计(水源热泵机组、循环水泵、冷却水泵等的选择;机房内设备的布置;机房水系统);(7)、设备及材料统计;(8)、空调系统的消声、防振及防火排烟;(9)、空调系统的运行调节;(10)、风、水系统管道的防腐保温。
2. 设计图纸(1)、图纸目录(A4 1张)(2)、设计总说明(A1 1张)(3)、各层空调平面图(水平面;风平面)(4)、空调系统图(水系统图A1 1张;风系统图A1 1张)(5)、空调剖面图(A2 1张)(6)、空调设备安装图(风机盘管、空气处理机等,A2 1张)(7)、空调管道及设备安装图(风机盘管、空气处理机等,A2 1张)(8)、各种非标管件大样图(弯头、三通、变径等,A2 1张)(9)、空调制冷机房平面布置图(A2 1张)(10)、材料及设备明细表(商城空调部分及冷热站部分,A2 1张)说明:上述图纸张数仅供参考,不少于7张A1,其中只能有一张非计算机绘图。
摘要本设计结合西安地区的自然条件和建筑物结构的实际情况,对该建筑进行冬夏两用中央空调系统设计。
设计中首先进行冷负荷计算,然后确定空调系统形式,进行平面布置,水力计算后选择水管和风管。
制冷、制热站设计,首先进行冷、热源选择,技术比较后确定所用机组设备方案。
对站房进行平面布置,选择附属设备,作系统原理图。
防排烟系统设计,根据建筑物实际,严格按照防火防排烟规范,确定防烟排烟系统形式,进行平面和系统设计。
关键词:冷热负荷水力计算冷热源隔声与防震加压送风AbstractThis design combines the natural condition of Xi'an's region and the actual circumstance of the building structures, to should construct to carry on the winter summer two use the central air condition system design. Design win carry on the cold hot burden calculation first, then make sure the air condition system form, carry on flat surface's arrange, the water power calculation chooses the pipe line moderate breezes tube behind. Make cold, make the hot station design, carry on the cold and hot source choice first, after technique compare certain equipments project of machine use. Carry on flat surface's arrange to the station, choose the subsidiary equipments, make the system principle diagram. Defend to line up the smoke system design, according to the building actual, defend to line up the smoke norm according to the fire prevention strictly, make sure to defend the smoke row smoke system form, carry on the flat surface and system designs.Key words: Cold hot burden, water power the calculation, the cold and hot source, separate the voice and quakeproofs,air pressure前言中国的建筑行业正处于飞速发展的阶段,人们对生活环境的要求也越来越高,而生活环境最主要的就是居住环境,这种需求带动了中国的空调制冷业的发展,特别是在“非典”之后,人们对室内空气品质(IAQ)有了更深刻的认识,室内空气的好坏直接影响到人们的健康,原来使用的空调技术已经不能满足人们的要求,对环境的需求意识已经不是简单的冷热意识,而是趋向于健康化、卫生化的需求。
1 绪论毕业设计是我们大学四年学习的总结,是理论联系实际的运用阶段,是对所学知识的一个综合。
本设计是陕西省西安市某综合办公楼的空调系统的设计,该综合楼共七层,层高3.6米,总面积4000平方米。
本设计历时近三个多月,共分两个阶段,第一阶段是查阅资料阶段,第二阶段是设计阶段。
我们在广泛了解了建筑空调系统的特点及详细资料的前提下,进行了空调系统的毕业设计。
设计过程中,我得到了指导老师李宝玉的悉心指导和同组同学的热心帮助,顺利完成了设计。
随着改革开放的不断深入和国民经济是迅速发展,人民的生活水平逐步提高。
在工业和民用的新建,改建和扩建工程中,对空调的需求越来越多,空调技术和工程已成为基本建设中比不可少的内容,尤其是办公室的空调发展技术更是突飞猛进,一日千里,每年都会有新技术,新产品的出现。
当然,在空调技术发展的过程中也会出现新问题、新思想,有待我们探讨和解决。
本工程根据工程的具体情况,确定空调系统的形式。
整个建筑采用风机盘管加新风系统,新风由设在各层新风机组对本层集中配送。
论文在编写过程中曾广泛参考过各种相关资料,除了部分在文后附出之外,其余参考未能一一标出,在此表示歉意。
由于时间仓促,同时由于缺乏实际的施工经验,再加上能力有限,故在本设计中难免有很多不足和错误之处,恳请各位老师和专家的批评指正。
2 设计原始资料2.1 地理环境参数陕西省西安市东经:108.93 北纬:34.3海拔:396.9m 年平均温度:13.3℃夏季大气参数大气压(Pa): 95920室外日平均温度(℃): 30.70室外计算日较差(℃): 8.70室外干球温度(℃): 35.20室外湿球温度(℃): 26通风计算温度(℃): 31室外平均风速(m/s): 2.20室外相对湿度(℃): 722.2建筑维护结构信息a)外墙选择墙体的建筑材料为:石灰、水泥、砂、砂浆加气混凝土,泡沫混凝土,钢筋混凝土墙体总厚度为320mm。
墙体传热系数为0.59W/(m2·℃)b)内墙选择墙体的建筑材料为:水泥砂浆,加气混凝土,泡沫混凝土,钢筋混凝土墙体总厚度为280mm。
一、计算参数的选择与设计标准1.1、室外设计气象参数位置:北纬34°,东经108.93° 大气压:96.0KP夏季室外计算干球温度[7]:35.2℃ 夏季室外计算湿球温度:26℃ 夏季日平均干球温度:31.2℃ 夏季日平均温差:8.7℃1.2、室内设计计算参数室内设计温度t N =26℃,相对湿度55%屋顶:由附录2-9查的,K=1.10,衰减系数0.52,衰减度15.15,延迟时间ε=5.9h , 外墙:由附录2-9查的,K=1.95,衰减系数β=0.35,衰减度ν=12.9,ε=8.5h , 内墙:由附录2-9查的,K=2.37,衰减系数β=0.59,衰减度ν=6.32,ε=5.2h , 楼板 由附录2-9查的,K=3.13,衰减系数β=0.64,衰减度ν=4.35,ε=4.1h , 窗:单层玻璃钢窗,挂浅色内窗帘,无外遮阳。
查得传热系数K=4.54[7]。
照明散热:室内照明采用日光灯 设备散热:室内设备主要是电脑二、房间负荷计算公式及过程 2.1房间负荷计算公式2.1.1外墙和屋面瞬变传热引起的冷负荷计算公式为外墙CLQ =KF t ττε-∆内墙)(n t t KF Q -∆+=-ξττ (2.1)2.1.2外玻璃窗瞬变传热引起的冷负荷计算公式为CLQ c KF t ττ⋅=∆ (2.2) 其中t τ∆——计算时刻的负荷温差,C ︒。
2.1.3 透过玻璃窗的日射得热引起的冷负荷计算公式为CLQ j g d n S j x x C C FJ ττ⋅⋅= (2.3) 其中g x ——窗的有效面积系数;单层钢窗0.85,双层钢窗0.75;d x ——地点修正系数;j J τ⋅——计算时刻时,透过单位窗口面积的太阳总辐射热形成的冷负荷[5],2W/m ; 2.1.4 设备照明和人体散热得热冷负荷计算公式T CLQ QJX ττ-= (2.7) 其中 Q ——设备、照明和人体得热,W ;T ——设备投入使用时刻或开灯时刻或人员进入房间时刻,h ;T τ-——从设备投入使用时刻或开灯时刻或人员进入时刻到计算时刻,h ;-T JX τ——T τ-时间的设备负荷强度系数,照明负荷强度系数、人体负荷强度系数[。
本科毕业设计说明书题目院(部):专业:班级:姓名:学号:指导教师:完成日期:目录ABSTRACT (Ⅳ)1 前言 (1)2 概况 (2)2.1 工程概况 (2)2.2 设计原始资料 (2)2.2.1 土建资料 (2)2.2.2 气象资料 (2)3 系统方案比较及确定 (4)3.1全空气系统(即集中式) (4)3.2风机盘管加新风空调系统(即半集中式) (4)3.3 系统方案采用 (4)4 空调系统设计 (5)4.1 冷热湿负荷计算 (5)4.1.1 冷负荷计算 (5)4.1.2 湿负荷计算 (20)4.1.3 热负荷计算 (22)4.2 风量计算 (24)4.4 设备选型 (27)4.5 水力计算 (27)5 制冷机房的设计 (31)5.1 确定制冷站总负荷 (31)5.2 冷却塔形号及台数的选择 (32)5.2.1 冷却塔的类型 (32)5.2.2 设备的选型 (33)5.3 辅助设备的选择 (33)5.3.1 冷冻水泵的选择 (33)5.3.2 冷却水泵的选择 (33)5.3.3 软化水处理器的选择 (33)5.3.4 软化水箱的选择 (34)5.3.5 冷却水处理器的选择 (34)5.3.6 定压设备的选择 (34)5. 4换热器的选择 (35)5. 5制冷机房的注意事项 (35)6 结论 (37)谢辞 (38)参考文献 (39)附录 (40)摘 要本设计为陕西宾馆办公楼空调设计,该建筑为7层高级公用建筑。
顶层为机房地上1层为办公大厅、会议室,2—6层为办公室,7层会议大厅。
结合工程实际设计资料(经济效益、环境效益),要求各功能房间采用全年舒适性空调,设计方案为一、七层采用全空气系统。
二至六层采用风机盘管加新风空调系统(即半集中式)·································。
开题报告一、课题研究内容1、课题来源概况本课题题目为西安市某办公楼中央空调系统设计。
本次毕业设计的任务要求是完成建筑物冷、热源空调系统负荷设计计算;分析并确定空调系统设计方案和主要设备的选型;完成管路系统的设计计算等;不低于规定要求的工程图纸设计任务;撰写毕业论文。
要求各项设计计算正确,论文条例清晰,图纸符合国家要求,按时完成各项设计任务。
2、研究设计意义随着现代科学技术的发展和我国市场经济的大发展,各地都在兴建高标准的办公楼。
办公楼的建筑水准和设备水准是一个国家现代化程度和技术水平的标志,而其空调方式应能适应办公楼的功能需求,因此搞好办公楼空调设计是至关重要的。
在此设计中采用中央空调系统,满足室内工作人员的舒适感。
3、空调系统控制概念介绍(1)、风机盘管的控制:设有风机盘管房间的室温,由设于房间内带有季节转换开关及三速调节开关的温度控制器来控制风机盘管回水支管上双位两通电动阀的通断控制供水量,三速开关控制风机送风量,满足室内温度要求。
(2)、新风系统的控制:新风送风温度由送风总管上的温度传感器经温度控制器指令新风机组表冷器回水管上的比例积分式两通电动阀的开度来调节供水量,使新风送风温度稳定在整定值上。
(3)、空调系统的控制:空调房间的室温控制由设于回风总管上的温度传感器经温度控制器指令空气处理机组表冷器回水管上的比例积分式两通电动阀的开度来调节供水量,实现室内温度稳定在设定的基准上。
4、研究设计目的在现代的办公大楼中,通过采用舒适性空气调节系统,保证了办公人员在工作生产时的舒适性感觉。
具体而言,我们研究、设计的目的除了满足室内空气温度、湿度和速度方面的要求之外,更重要的是满足其舒适性方面的要求。
空气温湿度与一般舒适性空调的温湿度基本类似。
根据我国《采暖通风与空气调节设计规范》(GBJ19-87)中规定,舒适性空调的室内参数应达到以下水平:5、空调系统形式的选择:根据建筑物的特点,在此设计中采用的是中央空调系统,选用中央空调系统和局部空调系统相比,具有很多优点:空调效果好;可送新风保证室内空气新鲜度;投资低;运行管理灵活方便,运行费用低;故障少、好维修;设备寿命长;噪声小;易于装饰配合,实现现代建筑的高档、豪华、明快、舒适之美感。
毕业设计说明书(论文)作者: x 学号: x系部: x专业:建筑环境与设备工程题目:西安某综合楼通风空调设计指导者:x副教授评阅者:2015 年5 月 x毕业设计说明书(论文)中文摘要Title Design of An Air-Conditioning System of An Comprehensive Building in XiAnAir conditioning design for this project includes the design of central air conditioning systems and ventilation of the building. The air-conditioning system design to achieve cooling in summer and heating in winter, and can meet the comfort requirements.Layer in the entire building shopping malls, full air system; three-to five-story hotel room fan-coil plus fresh air systems can be kept fresh indoor air comfort. The building has no specific room, directly House roof. Taking into account the location of XI ' an and meteorological parameters, winter temperature isn't very low,air-source heat pumps as the summer heat can be used, at the same time as a heat source in winter.Design elements include; cooling load calculation, remonstrate treatment choices, air-conditioning end equipment selection, it tube and wind path system design of computer auxiliary equipment selection and preparation of design specifications and construction drawingKey words comprehensive building air system fan-coil plus fresh air systems water systems目录前言 (1)第一章设计任务 (7)1.1设计目的 (7)1.2主要设计内容 (8)1.3技术文件 (8)1.4设计参数............................... 错误!未定义书签。
目录第一章绪论 (3)一、选题背景 (3)二、我国暖通空调的现状及其发展 (3)三、空调系统的设计与建筑节能 (3)四、设计目的 (4)第二章工程概况 (5)一、设计参数 (5)二、建筑物的基本设计参数 (5)三、初步设计 (5)第三章空调系统负荷计算 (6)一、负荷概念 (6)二、室内空调设计参数 (6)三、空调冷负荷计算 (6)四、空调湿负荷计算 (11)第四章系统方案论证 (13)一、空调系统的分类 (13)二、空调系统的比较 (13)三、空调系统形式确定 (15)四、风机盘管机组的结构和工作原理 (16)五、风机盘管的系统设计 (16)第五章送风量计算 (17)一、送风量的计算公式 (17)二、各房间送风状态的确定 (17)三、送风量的计算过程及结果 (18)四、风机盘管及新风机组的选择 (20)第六章空调风系统 (23)一、风管的选型 (23)二、风管水力计算 (24)第七章空调水系统 (28)一、水系统的选择 (28)二、冷冻水管的水力计算 (29)三、冷凝水管选型 (32)第八章保温与防腐 (35)一、保温方法 (35)二、保温材料的选择 (35)三、管防腐措施 (36)结论 (37)致谢 (38)参考文献 (39)第一章绪论一、选题背景通风空调工程设计是建筑设备工程专业学生需要掌握的重要的专业技能。
它是对专业知识的综合掌握和灵活运用。
随着社会的进步和人民生活水平的不断提高,人们对建筑室内环境的要求也越来越高,从单一的满足温度的要求向温湿度、室内空气品质、甚至放射性物质在空气中的含量等多方面同时满足的方向发展。
空气调节可以实现同时对空间内的温度、湿度、洁净度和空气流速等进行调节和控制,并提供足够量的新鲜空气。
舒适性空调是以室内人员为对象,创造舒适环境为目的。
为了能让老师和同学们在更舒适的环境下工作和学习,为此选择西安市某一小学办公楼作为此次通风空调设计系统的设计建筑。
二、我国暖通空调的现状及其发展进入上世纪90年代后,我国的居住环境和工业生产环境都已广泛地应用空调,空调技术已成为衡量建筑现代化水平的重要标志之一。
西安某综合商业建筑空调系统能耗分析作者:康炜来源:《城市建设理论研究》2013年第21期摘要:对西安高新国际商务中心,采用Energy-Plus软件建立了建筑模型,并进行空调系统的能耗分析,得到了全年该建筑的能耗状况,分析了全年空调系统的能耗以及不同冷冻水的状态下对该建筑空调系统的能耗水平的影响。
关键词:空调制冷系统;部分负荷率;能耗分析;Energy-Plus中图分类号:TU831.3+5 文献标识码:A 文章编号:目前我国每年城镇新建公共建筑约3~4亿m2 ,现有公共建筑约40亿m2。
一些大城市的能耗实测结果表明:特大型高档公共建筑单位面积的能耗约为城镇普通居住建筑能耗的10~15倍,一般公共建筑的能耗也是普通居住建筑能耗的5倍左右[1-2 ]。
公共建筑用能耗巨大,浪费严重。
而公共建筑的能耗中,约50~60 %用于空调制冷与采暖系统[3 ],因此其节能潜力很大。
本文选取了西安市高新国际商务中心的空调及制冷系统,进行了能耗模拟分析。
1 建筑及空调制冷系统概况该建筑位于西安高新区,建筑总高度为153.2米,共39层,其中含一局部为四层的商业建筑和一栋39层的办公楼。
商业建筑中部有一直径为12米左右的圆柱形中庭上下贯通,四层顶部80%的面积采用玻璃屋面。
建立Energy-Plus模型,如图1。
空调面积为88555.34m2,空调设计温度室内均为26℃,相对湿度为60%。
空调制冷系统采用了三台蒸汽溴化锂吸收式冷水机组(两用一备),单台冷机额定制冷量为2954kW;额定冷冻水供、回水温度为7/12℃,流量为508m3/h;额定冷却水供、回水温度为32/37.7℃,流量为623m3/h;冷机以压力为0.4MPa 的过热蒸汽为驱动动力。
空调末端:对于商场,采用定风量全空气系统,过渡季节全新风运行。
按不同的朝向,功能区以及防火分区划分空调区域:对于办公建筑,均采用风机盘管加新风系统。
图1 建筑模型设计模型设计模型的围护结构设定参数根据设计图纸和节能报告确定,具体数据见表1。
******大学毕业设计西安市某综合楼空调工程设计The Air Conditioning Project Design of Multi-functional Building in Xi’an2011 届机械工程学院专业建筑环境与设备工程学号 *****学生姓名*****指导教师******完成日期 2011年6月2日摘要本设计为西安市某综合楼通风空调工程设计,总建筑面积为11020㎡,其中空调面积约为7461㎡.该综合楼地上14层,地下1层,其中一层为商务大厅、餐厅,厨房、职工活动中心,层高为5.1米;六至十一层为办公室, 层高为3.4米;十三、十四层为客房标准间,层高为3。
4米;地下一层为车库、制冷机房、电控室、泵房等.本设计的主要内容有:空调负荷计算、新风量的确定、空气处理过程的设计、气流组织设计与计算、设备选型、水系统及风系统水力计算、地下车库通风量的确定、通风系统设计等.本设计总冷负荷为790.87kW,热负荷为254.55kW,制冷机房夏季采用2台SXZ6—35DH2系列蒸汽双效型溴化锂吸收式冷水机组作为冷源,冬季采用城市供热管网的蒸汽作为热源,采用1台YTBJS—0。
6Q型号汽水换热器。
对于办公室、标准间等小空间采用风机盘管加新风系统,每层设单独的新风机组,风机盘管独立承担室内的冷热负荷。
而对于一层商务办公厅、餐厅等空间较大、人员较多的房间采用吊顶式空调机组,以节约空间。
因为该综合楼房间类型较多,各房间冷热负荷并不相同,可以各个房间进行单独的调节。
车库通风系统采用中间送两边排风的方式达到通风换气的目的。
关键词:空调系统冷负荷水系统风机盘管独立新风系统车库通风AbstractThe building is located in Xi’an. The project is the m ultiple–use building air—conditioning engineering design .The building is a comprehensive building,The total building area is 11020㎡,but the air-conditioning area is 7461㎡.There are 14 floors of the building。
目录一 XX大学课程设计(论文)任务书 (1)二设计题目与原始条件 (1)2。
1 工程概述 (1)2。
2设计依据 (2)2。
2。
1 设计任务书 (2)2.2。
3 设计规范及标准 (2)2。
3 设计范围 (2)2。
4 设计参数 (2)2。
4。
1 空调设计室外空气计算参数 (2)2.4。
2室内空气设计参数及有关指标见下表 (3)2.4.3 其他 (3)三方案设计 (4)四负荷计算 (4)4.1空调冷负荷计算方法 (4)4。
2 相关参数的选取 (4)4.3 冷负荷的计算 (5)4。
3.1 外墙和屋面瞬变传热引起的冷负荷 (5)4。
3.2 内墙、地面引起的冷负荷 (6)4。
3。
3 外玻璃窗瞬变传热引起的冷负荷 (6)4.3.4 透过玻璃窗的日射得热引起的冷负荷 (7)4。
3.5 照明散热形成的冷负荷 (7)4.3.6 人体散热形成的冷负荷 (7)4。
3.7 设备散热形成的冷负荷 (8)4。
4 湿负荷的计算 (8)4.5 新风负荷计算 (8)4。
5.1 新风冷负荷 (8)4.5。
2 新风湿负荷 (9)4.6夏季空调计算结果汇总 (9)五空调处理过程的计算 (9)5。
1 全空气系统设计计算 (9)5.1。
1 夏季送风状态点和送风量 (9)5。
1.2 以第2层大厅为例进行设计计算 (10)5.2 风机盘管加独立新风系统设计计算 (11)六风机盘管﹑散流器﹑百叶的选择 (13)6。
1风机盘管的选择 (13)6.2 散流器选择 (14)6。
2。
1 全空气系统 (14)6.2。
2 风机盘管加新风系统 (14)七风系统水力计算 (14)7。
1风管材料和形状的确定 (14)7。
2送、回风管的布置和管径确定 (15)7。
3送风系统的设计 (15)7.4风管最不利点压力损失计算 (15)八水系统的计算 (16)8。
1水系统的设计 (16)8.2水系统阻力计算(鸿业计算) (16)九机组选择 (16)9。
1 新风机组的选择 (16)9。
2全空气机组的选择 (17)十设计总结 (17)十一参考文献 (17)一 XX大学课程设计(论文)任务书二设计题目与原始条件2.1 工程概述工程为西安市某一办公楼,砖混结构共两层,第一层层高为4。
2m第二层 3.2m。
建筑面积约2000m2。
底层为指挥中心,矛盾调处中心,爱心门诊,二层为办公室。
业主已给出建筑平面图,立面图和各个房间的功能,要求设计本办公楼夏季中央空调系统.2。
2设计依据2。
2.1 设计任务书《暖通空调》课程设计任务书2。
2。
3 设计规范及标准(1)采暖通风与空气调节设计规范(GBJ50019-2003版)(2)房屋建筑制图统一标准(GB/T50001-2001)(3)采暖通风与空气调节制图标准(GBJ114-88)2。
3 设计范围(1)中央空调系统选型,空气处理过程的确定。
(2)吊顶式空气处理器、风机盘管、送风口、回风口的选型,风管布置及水力计算。
(3)冷热源选择、水泵、膨胀水箱的选型及水系统设计。
(4)管路保温和消声减振设计2。
4 设计参数2.4.1 空调设计室外空气计算参数:⑴.地理位置北纬—34°18′;经度108°56′;海拨396.9m;⑵.大气压力冬季97870Pa;夏季95920 Pa;⑶.室外空气参数,见下表室外空气参数表2。
4.2室内空气设计参数及有关指标见下表室内设计参数表2。
4.3 其他噪声声级不高于45dB;空气中含尘量不大于0。
30 mg/m³;室内空气压力稍高于室外大气压。
三方案设计一、二层大厅空间大,人员密集,冷负荷密度大,室内热湿比小。
选择一次回风的定风量单风道全空气系统.为节约能源和资投,只进行单参数的露点送风.其理由如下:1)适用于室内负荷较大时;2)与二次回风相比,处理流程简单,操作管理简单;3)设备简单,最初投资少;4)可以充分进行通风换气,室内卫生条件好;因一、二层没有空调机房,所以一、二楼空调设备分别吊装在吊顶内,同时也可节省建筑有效使用面积。
(2)其余房间较小,各房间的使用时间也不同步,因此采用风机盘管+独立新风空调方式。
其优点如下:1)布置灵活,可以和集中处理的新风系统联合使用,也可单独使用;2)各房间互不干扰,可以独立的调节室温,并可随时根据需要开、停机组,节省运行费用,灵活性大,节能效果好;3)与集中式空调相比,不需要回风管道,节省建筑空间;现对风机盘管+独立新风系统对空气的处理过程进行确定, 新风处理到室内空气的焓值,不承担室内负荷。
而由风机盘管承担室内所有冷负荷。
四负荷计算4。
1空调冷负荷计算方法本设计采用冷负荷系数法冷负荷的计算。
4。
2 相关参数的选取围护结构参数见下表围护结构参数表其它的冷负荷相关参数见下表其它冷负荷相关参数表(四)注: (1)室内保持正压,不考虑空气渗透引起的冷负荷。
(2)本设计由于内部房间的温差较小,不考虑内围护结构的传热。
4.3 冷负荷的计算4.3.1 外墙和屋面瞬变传热引起的冷负荷Qc(τ)=AK[(tc+td)kαkρ-tR]式中: Qc(τ)--—-——- 外墙和屋面瞬变传热引起的逐时冷负荷,W;A —-—---—外墙和屋面的面积,m2;K —--—-——外墙和屋面的传热系数,W/(m2·℃) ;tR—--—--—室内计算温度,℃;tc-—---——外墙和屋面冷负荷计算温度的逐时值,℃;由《暖通空调》附录2-4和附录2-5查取;td-———--—地点修正值,由《暖通空调》附录2-6查取;kα-—--—-- 吸收系数修正值;kρ——-—-——外表面换热系数修正值;4。
3.2 内墙、地面引起的冷负荷Qc(τ)=AiKi(to.m+Δtα— tR)式中:ki-—-——-- 内围护结构传热系数,W/(m2·℃);地面:0。
47,W/(m2·℃);Ai—-————- 内围护结构的面积,m2;to.m———————夏季空调室外计算日平均温度,℃;Δtα——---—- 附加温升.注:由于该内维护结构之间的温差较小,在此次的设计中没有计算该项负荷。
4.3。
3 外玻璃窗瞬变传热引起的冷负荷Qc(τ) = cwKwAw( tc(τ)+ td- tR)式中 :Qc(τ)——-—-——外玻璃窗瞬变传热引起的冷负荷,W;Kw-——--—- 外玻璃窗传热系数,W/(m2·℃),K w =5.9 W/(m2·℃)Aw-———-—- 窗口面积,m2;tc(τ)--———-—外玻璃窗的冷负荷温度的逐时值,℃,由《暖通空调》附录2-10查得;cw——-—--—玻璃窗传热系数的修正值;由《暖通空调》附录2-9查得,单层金属窗框 cw=1。
0td——--———地点修正值;4.3。
4 透过玻璃窗的日射得热引起的冷负荷Qc(τ) = CαAwCsCiDjmaxCLQ式中:Cα--——-—- 有效面积系数,由《暖通空调》附录2-15查得;Aw—-———-—窗口面积,m2;Cs--—--—- 窗玻璃的遮阳系数,由《暖通空调》附录2-13查得;Ci—-——-—- 窗内遮阳设施的遮阳系数,由《暖通空调》附录2—14查得;Djmax-—----—日射得热因数,由《暖通空调》附录2-12查得30纬度带的日射得热因数;CLQ——--—-—窗玻璃冷负荷系数,无因次;4.3.5 照明散热形成的冷负荷荧光灯 Qc(τ) =1000n1n2NCLQ式中 :Q --————-灯具散热形成的冷负荷,W;N--———--照明灯具所需功率,W;n1—--——-—镇流器消耗公率系数,明装荧光灯n1=1。
2;n2--—---—灯罩隔热系数;n2=1。
0CLQ---—-—-照明散热冷负荷系数,可有附录2—22查得;注:与由于客房、办公室的空调系统仅在有人时才运行,取CLQ=1.4.3.6 人体散热形成的冷负荷人体显热散热形成的冷负荷Qc(τ)=qsnφCLQ式中:qs------- 不同室温和劳动性质成年男子显热散热量;n ——--——- 室内全部人数;φ-—---—- 群集系数,由《暖通空调》表2—12查得;CLQ—-——-——人体显热散热冷负荷系数,由《暖通空调》附录2—23查得;人体潜热散热引起的冷负荷Qc(τ) =qlnφ式中:ql-—--—-—不同室温和劳动性质成年男子潜热散热量, W;n,φ——---—-同式5—6-1;4。
3.7 设备散热形成的冷负荷办公室,指挥中心,调处中心,爱心门诊设备散热为13 W/㎡,大厅设备散热量为5 W/㎡公式。
4.4 湿负荷的计算人体散湿量可按下式计算:mw1=0。
278nψg×10-3 g/s式中: mw1—--——--人体散湿量, g/s;; g --—-——- 成年男子的小时散湿量,g/h;n -----—- 室内全部人数;ψ——-—-—- 群集系数;4。
5 新风负荷计算4.5.1 新风冷负荷Qc.o =Mo(iw—in)式中: Qc.o-——-——-夏季新风冷负荷,KW;Mo—---—--新风量,kg/s;i w -—----—室外空气的焓值,kJ/kg ; i n ——---—-室内空气的焓值,kJ/kg ; 4。
5。
2 新风湿负荷4。
6夏季空调计算结果汇总根据以上各项计算公式,得到夏季空调冷湿负荷结果如下,详细计算请参考附录Ⅰ:最大值出现在下午四点。
五 空调处理过程的计算5。
1 全空气系统设计计算5。
1.1 夏季送风状态点和送风量空调系统送风状态和送风量的确定可在i-d 图上进行,具体步骤如下:1) 在i —d 图上找出室内状态点N ,室外状态点W2)根据计算出的室内冷负荷Q 和湿负荷W 求出根据计算出的室内冷负荷Q 和湿负荷W 求出WQ =ε,再过N 点画出此过程线ε3)采用最大温差送风即(露点送风),画出相对湿度90%等相对湿度线,该线与ε线交于O 点,O 为送风状态点。
4)由G G W =NWNC 确定新风和回风的混合状态点c ,连接c 点和o 点。
如图所示:5.1.2 以第2层大厅为例进行设计计算1′ 热湿比WQ =ε=0021.03.34=34691kJ/kg 2′ 确定送风状态点在i-d 图上确定N 点,i n =55kJ/kg ,d n =11。
54g/kg, 过N 点作ε=16333线, 采用机器露点送风,确定送风状态点O ,t o =17。
6℃,i o =46。
25kJ/kg ,d o =11。
26g/kg 3′ 计算送风量 送风量G=o n i i Q -=2.5186.583.34-=0.952kg/s (4112。
64m 3/h ) 新风量G W =270 m 3/h 4′ 确定新回风混合状态点 由G G W =NW NC =137411407=10%可用作图法在NW 线上确定c 点,i c =56。