接地继电器
- 格式:ppt
- 大小:5.75 MB
- 文档页数:17
D型继电器模块的一般特性用户手册和技术说明ABB Network Partner211MRS 750066-MUM EN1995 4 12 发行A版(替换34 SPC 3 EN1)检查:JH批准:TK资料中的数据如有改变,恕不通知。
目录前面板布置----------------------------------------------------------------------------- 21 控制按钮-------------------------------------------------------------------------------- 23 显示------------------------------------------------------------------------------------- 23 显示主菜单-------------------------------------------------------------------------- 23 显示子菜单-------------------------------------------------------------------------- 23 选择器开关组SGF、SGB、SGR -------------------------------------------------- 24 设置------------------------------------------------------------------------------------- 25 设置方式----------------------------------------------------------------------------- 25 例1:继电器运行值的设置 ----------------------------------------------------- 28 例2:继电器开关组的设置 ----------------------------------------------------- 30 记录的信息----------------------------------------------------------------------------- 32 断开测试功能-------------------------------------------------------------------------- 33 例3:输出的强制启动 ----------------------------------------------------------- 35 运行的指示----------------------------------------------------------------------------- 37 故障代码-------------------------------------------------------------------------------- 3722控制按钮继电器模块的前面板上有两个按钮。
接地继电器安装使用说明(成套版)一、接地继电器的用途复极式离子膜电解槽因某种原因故障接地,例如槽框漏液、垫片泄漏、意外搭铁等,由于电槽运行的是强大的直流电流,严重时会因此烧坏电槽的单元槽框。
通过接地继电器可以及时发现这些故障。
避免事故扩大,对电解槽起到安全保障作用。
二、接地继电器的原理接地继电器接线原理见下图:选用两个接地继电器(日本东洋计器MPV-11型, H型和L型各1个)。
一个负责电解槽的正半区保护,一个负责电解槽的负半区保护。
把电解槽和分压电阻接成桥路,VR可变电阻调在中点位置,使分压电阻两边电压相等,每个单元电槽通过软管接到总管上,总管是接地的,每根软管内的电解液存在泄漏电流,造成电槽的中点为虚拟地,因此正常情况两个接地继电器都显示0。
事故状态下,电解槽在A点接地,接地继电器处在桥路中,当接地电压达到+10V或-10V时,发出报警信号。
当接地电压达到+30V 或-30V时,发出整流器跳闸信号。
三、接地继电器的安装接地继电器的安装方式有两种,一种是将接地继电器安装在远控柜上,远控柜一般放置在中控室内,可以将多台电解槽用的接地继电器装在一个柜子里;另一种是将两块接地继电器单独安装在一个小箱子里,放置在整流室直流刀开关箱旁边。
每台电解槽配备一台接地继电器箱,安装在整流所内距地1.5m,由箱顶配保护管作为电缆保护,出线电缆共三根,一根为电源电缆,接到电源配电箱;一根为检测电缆,接到直流母线正负极(如下图),其中M3接地线应接到电槽的接地端子箱,不得接在公用接地网上,以免误动作;一根为信号电缆,接到DCS中控室。
如果接地继电器箱安装地点距离直流母线太远,则应在直流母线下侧安装小型自动开关,以对检测电缆进行保护。
四、接地继电器的使用1、接地继电器报警和跳闸的电压设定:按照电解槽操作手册的规定,在试车阶段,为了避免接地继电器不必要的动作,将接地继电器设定在+40V(红色指针)和-40V(黄色指针),试车结束后将报警设定为+10V(红色指针)和-10V(黄色指针),跳闸整流封脉冲设定为+30V(红色指针)和-30V(黄色指针),表盘报警点设置如下图所示。
继电器接线方法
继电器接线方法:
1. 第一步,将继电器的线圈连接到电源。
通常,继电器上会标有"coil"或"C"的标志,表示线圈引脚。
将正极连接到继电器引脚上的一个线圈引脚(通常为COM引脚),将负极连接到继电器的另一个线圈引脚。
2. 第二步,将继电器的常闭触点(一般标记为NC)连接到需要控制的装置上。
将一个导线连接到继电器触点上,另一端连接到需要控制的装置上的负极(或地线)。
3. 第三步,将继电器的常开触点(一般标记为NO)连接到需要控制的装置上。
将一个导线连接到继电器触点上,另一端连接到需要控制的装置上的正极。
4. 第四步,将电源的正极和继电器的公共接点(通常标记为COM)连接在一起。
将一个导线连接到电源正极,另一端连接到继电器的公共接点。
5. 第五步,将电源的负极和需要控制的装置的负极(或地线)连接在一起。
将一个导线连接到电源负极,另一端连接到需要控制的装置的负极(或地线)上。
6. 最后,通过控制继电器的电源线圈来控制需要控制的装置。
当电流通过继电器的线圈时,触点会发生切换,将常闭触点断开,常开触点闭合,从而控制装置的开关状态。
请注意,具体的继电器接线方法可能因继电器型号、控制装置类型和电路需求而有所不同。
在接线之前,请务必参考相应的继电器和装置的说明书,并严格按照电路图和安全操作规程进行接线。
接地继电器的工作原理
接地继电器是一种用于电气系统的保护装置,它的作用是将电气系统的异常电流迅速引入地线,以确保人身安全和设备的正常运行。
接地继电器的工作原理如下:
1. 接地电流检测:继电器内部有一个电流传感器,用于检测进入设备的电流大小。
当电流超过设定值时,继电器将启动。
2. 电磁机械开关:接地继电器内部包含一个电磁线圈和一个机械开关。
当电流传感器检测到过流时,电磁线圈将受到激励,产生磁场。
3. 开关动作:电磁线圈产生的磁场将吸引机械开关,使其闭合。
闭合的开关将连接接地线,让异常电流通过地线迅速引入地下。
4. 报警信号:一些接地继电器还具有报警功能。
当接地继电器启动时,可以通过报警装置发送信号,以提醒操作人员发生了电气故障。
总之,接地继电器通过电磁机械开关的动作,将异常电流迅速引入地线,从而实现对电气系统的保护。
这种保护装置在电气系统中发挥着重要的作用,可以防止漏电、过载、短路等情况的发生,确保人员的安全,并延长设备的使用寿命。
高压低压配电柜的过电压保护与接地保护原理高压低压配电柜在工业生产和民用建筑中起到了至关重要的作用,它负责将电力从高压输电线路传输到低压供电系统,供给各种电气设备使用。
然而,由于电力系统存在着过电压和接地故障等问题,高压低压配电柜的过电压保护和接地保护成为了必不可少的安全措施。
本文将介绍高压低压配电柜的过电压保护与接地保护原理。
一、过电压保护原理过电压是指在电力系统中,电压超过了正常工作范围或设备所能承受的范围,导致设备受损或工作异常。
过电压保护的主要目的是保护电气设备免受过电压的损害,降低安全事故的发生概率。
过电压保护系统通常由避雷器和保护器两部分组成。
避雷器安装在高压侧,主要用于对抗来自输电线路的大气过电压,将过电压引入地下。
而保护器则安装在低压配电柜内,主要用于保护电气设备免受内部故障产生的过电压的影响。
保护器可以根据不同的过电压类型分为过电压保护和过电流保护。
过电压保护通常由过压继电器实现,它通过监控系统的电压变化,一旦电压超过设定的阈值,就会触发保护动作,切断电气设备的供电,避免设备受损。
而过电流保护则采用过电流继电器实现,它通过监控系统的电流变化,一旦电流异常增大,就会触发保护动作,切断电路供电,避免设备遭受过电流的冲击。
二、接地保护原理接地保护是指将电气设备等与地建立电气连接,以确保人身安全和设备正常工作。
在发生接地故障时,接地保护系统能够及时检测到故障,并采取相应的保护措施,避免电气设备和人员遭受伤害。
接地保护系统主要由接地电阻、接地切换开关和接地继电器组成。
接地电阻通常安装在高压低压配电柜内,它通过将电气设备等接地,将电流引入地下,从而保护人员和设备免受触电和漏电的危害。
接地切换开关则可以实现手动或自动地将电气设备的中性点接地或脱离接地,从而达到接地保护的目的。
接地继电器则负责感知电气设备的接地状态,一旦发生接地故障,就会触发保护动作,切断电路供电,以保护人员和设备的安全。
总结:高压低压配电柜的过电压保护与接地保护原理是保护电气设备和人员安全的重要措施。
突变量接地阻抗继电器动作特性分析摘要在电力系统的输电线路中,短路故障是在所难免的。
如果不能快速切除故障就会造成线路损坏甚至系统崩溃的危险情况。
继电器快速切除故障可以减少被保护线路的损坏程度,提高电力系统运行的稳定性。
常规的接地阻抗继电器不受运行方式变化影响,但是其存在受过渡电阻与系统振荡影响的不足之处。
突变量距离保护原理是一种新型的距离保护原理,而突变量接地阻抗继电器具有不受运行方式和系统振荡影响、抗过渡电阻能力强、有明确的动作方向性等特点。
本论文是通过比较分析突变量接地阻抗继电器的工作原理、动作特性,得出突变量接地阻抗继电器具有原理简单,实现算法容易,灵敏度高,不受系统振荡、抗过渡电阻能力强、有明确的动作方向性等优点。
同时对突变保护所存在的一些问题,提出了解决方案。
并对新型突变量接地阻抗继电器的动作特性进行了MATLAB仿真,得出了相应的结论。
关键词:突变量;接地阻抗继电器;动作特性;MATLAB仿真REACH AND SIMUINK OF THE MUTATIONVARIATION EARTH DISTANCE PROTECTSABSTRACTIn the transmission lines of power system,the short-circuit fault is inevitable.If the line can not be quickly removed it will cause a line fault system damage or even the dangerous situation of System crash.Rapid removed of the relay fault lines can be reduced by the damage to protect and enhance the stability of power system operation.Conventional grounding impedance does not relay operation mode. But it has the shortcoming of being impacted by the transition resistance and the system oscillation.The break variable distance protection theory is brand-new.And the break variable ground impedance relay contains some characteristics,such as far from the system oscillation,strong ability of anti-resistance,a clear direction,etc.In this paper, the author analysis the working principle and the characteristic of the break variable ground impedance relay,then obtain mutation in the volume of grounding impedance have the principle of a simple relay,easy to algorithm,high sensitivity,far from the system oscillation,strong ability of anti-resistance,a clear direction,etc.At the same time,the author also gives the special conditions in a number of mutation in the volume of the protection of the existence of a number of issues,proposes the solution. The MATLAB simulation of the characteristics of the volume of the new mutation and the grounding impedance relay is also presented,and the significance conclusion is obtained.Key words:mutation volume,ground impedance relay,operation characteristic, MATLAB simulation第一章绪论1.1引言我国国民经济的快速发展,用电量的需求越来越大,用户对于用电可靠性的要求也越来越高,因此要求继电保护装置能够更加快速、可靠、有选择性。
SPAJ 142C通用过流及接地保护继电器用户手册及技术说明2SPAJ 142C通用过流及接地保护继电器发布:1997-10-14状态:2002.04.24版本: B (replaces 34 SPAJ 18 EN1)目录特性......................................................................................................................................................2用途......................................................................................................................................................2动作原理..............................................................................................................................................3接线原理图...........................................................................................................................................4接线端子..............................................................................................................................................6模块之间的控制信号............................................................................................................................7信号缩写符说明...................................................................................................................................7动作指示器...........................................................................................................................................8电源与输出继电器模块........................................................................................................................9技术数据..............................................................................................................................................10维护与检修...........................................................................................................................................13备件......................................................................................................................................................13安装尺寸与说明...................................................................................................................................14订货须知..............................................................................................................................................15通用过流及接地保护继电器SPAJ 142C 全套手册包括如下分册:通用过流及接地保护继电器SPAJ 142C D 型继电器模块的一般特性SPCJ 4D29型组合式过电流与接地故障模块特性具定时限或反时限特性的过电流保护具瞬时或定时限特性的电流速断保护具定时限或反时限特性的零序过电流保护具瞬时或定时限特性的零序电流速断保护断路器失灵保护可选择的输出继电器配置灵活的串行通讯功能灵活的功能配置适用于各种不同的应用数字显示整定值、测量值及故障记录值连续的自检功能用途SPAJ 142C 通用过流及接地保护继电器是主要用于电力系统中直接接地、电阻接地或阻抗接地的辐射式电网中,作为有选择性的短路和零序电流接地保护。