热水网路水力计算表
- 格式:xls
- 大小:263.50 KB
- 文档页数:6
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
6-7848.829.21259.64.4013.950.6445.0
5-61145.339.412524.04.4028.400.9494.4
4-51229.742.315010.75.6016.300.6941.4
3-42130.873.320023.48.4031.840.6322.7
2-32273.378.22004.48.4012.790.6725.8
1-22447.784.220028.08.4036.400.7330.2
A-13052.3105.030024.58.4032.910.9047.0
总计124.648.00172.59
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
21-2234.91.2404.00.974.970.2835.9
20-2166.92.35025.31.3026.600.3440.5
19-2098.83.4504.01.305.300.5091.4
16-19136.64.77050.02.0052.000.3631.6
15-16165.75.7704.52.006.500.4446.2
14-15191.96.67017.62.0019.600.5162.1
13-14218.07.5804.02.556.550.4132.1
7-13244.28.48070.33.3173.610.4640.2
总计179.715.43195.13
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
10-11157.05.40703.62.005.600.4241.6
9-10302.310.408016.72.5519.230.5761.5
8-9447.715.401004.03.307.300.5747.0
7-8604.720.801003.03.306.300.7785.9
总计27.311.238.4附录6 热水网路水力计算表
主干线水力计算表
10、9A号楼支线水力计算表
2、9B号楼支线水力计算表7号楼支线水力计算表Gdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht
Gdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht
Gdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
33-3434.91.2404.00.974.970.2835.9
32-3364.02.25017.61.3018.900.3336.2
31-3295.93.3504.01.305.300.4986.4
30-31125.04.37017.62.0019.600.3326.6
29-30154.15.3704.02.006.000.4140.1
26-29189.06.57074.23.2077.360.5060.2
25-26220.97.6804.52.557.050.4232.9
24-25244.28.48017.62.5520.150.4640.2
23-24270.39.3804.02.556.550.5149.2
6-23296.510.28026.02.5528.550.5659.2
总计173.520.97194.43
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
38-3920.30.7324.00.754.750.2437.6
37-3837.81.34016.60.9717.560.3041.7
36-3752.31.8402.40.973.370.4284.2
35-3664.02.2501.61.302.900.3336.2
5-3584.32.9503.01.304.320.4366.8
总计27.65.332.9
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
51-5226.20.9321.40.752.190.3160.4
50-5146.51.64015.90.9716.850.3765.8
49-5075.62.6504.01.305.300.3853.4
48-49101.73.57017.62.0019.600.2718.0
47-48130.84.5704.02.006.000.3529.1
45-47159.95.57031.83.2035.000.4343.1
总计74.710.2284.94
58-5926.20.9321.40.752.190.3160.4
57-5846.51.64015.90.9716.850.3765.8
56-5775.62.6504.01.305.300.3853.4
53-56101.73.57017.62.0019.600.2718.0
45-53159.95.57031.82.0033.800.4343.11A、1B、4号楼支线水力计算表3号楼支线水力计算表
Gdl
dlzhlR
)/(mPas)(m)(m)(mmQ
)(kW)/(ht)/(m)(mGdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht
Gdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht总计70.77.0277.74
43-45322.711.18034.13.3137.410.6070.0
42-43497.117.11004.53.307.800.6357.9
41-42630.821.710017.63.3020.900.7993.2
40-41764.526.31254.04.408.400.6141.2
4-40901.231.012526.04.4030.400.7358.4
总计377.153.19430.27
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
64-6529.11.0324.00.754.750.3473.1
63-6449.41.7404.00.974.970.3975.4
62-6369.82.4508.81.3010.100.3545.6
61-6290.13.1504.01.305.300.4670.0
60-61113.43.9704.02.006.000.3022.2
3-60142.44.9703.02.005.000.3828.9
总计27.88.336.1
序号负荷流量公称直径管长局部阻力当
量长度之和折算长
度流速比摩阻
123456789
72-7329.11.0321.40.752.190.3473.1
71-7252.31.84016.00.9716.970.4284.5
70-7181.42.8504.01.305.300.4162.0
67-70110.53.87011.62.0013.600.2921.2
2-67174.46.07074.62.0076.600.4751.2
总计107.67.02114.665号楼支线水力计算表6号楼支线水力计算表
Gdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht
Gdl
dlzhlR
)/(mPa)/(sm)(m)(m)(m)(mmQ
)(kW)/(ht管 段 的
压力损失
10
628
2681
675
723
330
1099
1547
7682管 段 的
压力损失
10
178
1077
484
1643
300
1217
210
2959
8070管 段 的压力损失10
233
1183
343
541
2299.9P)(Pa
P)(Pa
P)(Pa管 段 的
压力损失
10
178
684
458
521
241
4657
232
810
322
1690
9794管 段 的
压力损失
10
179
732
284
105
289
1588.2管 段 的
压力损失
10
132
1109
283
353
175
1509
3560
132
1109
283
353
1457P)(PaP)(Pa
P)(Pa3334
2619
452
1948
346
1775
20927管 段 的
压力损失
10
347
375
461
371
133
145
1831.2管 段 的
压力损失
10
160
1434
329
288
3922
6133P)(Pa
P)(Pa