第四部分Masterpact 空气断路器选型指南4-1Masterpact MT空气断路器组成124 5 371. 二次端子盖2. 电压线圈3. 灭弧栅4. 电动储能机构马达5. Micrologic 控制单元6. 前面板7. 开关本体8. 抽架4-24-3Masterpact MT空气断路器选型表COM: 通信选件 MCH: 电动机构 MX: 分励线圈 XF: 合闸线圈 MN: 欠压线圈CB: 二次接线端子盖板 CDP: 门框PF: “准备合闸”触点 (更多附件,详见样本MT Masterpact MT0606, 08, 10, 12, 16, 20, 25, 32, 40, 40b, 50, 63N1N1, N2, H1, H1b,H2, H3, L13P 3P (可不标 , 4PD/OD/O (抽出式,可不标 , F (固定式MIC 2.0AMicrologic 控制单元 (可不标 2.0,5.0, 6.02.0A, 5.0A, 6.0A, 7.0A, 2.0E, 5.0E, 6.0E,5.0D, 6.0D5.0P,6.0P,7.0P,5.0H, 6.0H, 7.0H附件++4-4Masterpact MT N1从 630 到 1600AMasterpact MT N2, H1,H1b, H2, H3, L1从 800 到 4000Ap Masterpact MT N1 型,从 630A 到 1600A是同一种尺寸。
p Masterpact MT N2, H1, H1b, H2, H3, L1型,从 800A ~ 4000A 是同一种尺寸。
p Masterpact MT H1, H2 型,从 4000A ~ 6300A是同一种尺寸。
056477056472E 58891E 58892Masterpact MT断路器的主要规格Masterpact MT H1, H2从 4000 到6300A056473E 58893Micrologic 控制单元的选择4-5Mic E Mic E4-6 0564084-7 4-80564********功能和特性(1 垂直后连接 , 其他连接方式参见温度降容表。
ABB EntrelecSommaireBU0402061SNC 160 003 C0205SummarySelection guide ....................................................................................page 1Screw clamp ........................................................................................page 2Feed through and ground terminal blocks .......................................................page 2 - 5 to 10Single pole, multiclamp terminal blocks..........................................................................page 4Feed through terminal blocks - Double-deck................................................................page 11Feed through terminal blocks - Triple-deck...................................................................page 12Three level sensor, terminal blocks without ground connection...................................page 13Three level sensor, terminal blocks with ground connection ........................................page 14Terminal blocks for distribution boxes, double deck + protection .......................page 15 - 16Interruptible terminal blocks for neutral circuit......................................................page 17 - 18Distribution : phase, ground terminal blocks .......................................................page 19 to 21Single pole or four pole distribution blocks..........................................................page 22 to 24Heavy duty switch terminal blocks with blade......................................................page 25 - 26Heavy duty switch terminal blocks with push-turn knob..............................................page 26Heavy duty switch terminal blocks with contact control pull lever...............................page 29Heavy duty switch terminal blocks with blade - Double-deck .....................................page 27Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.)or 6.35x25.4 mm (1/4x1 in.) and 6.35x32 mm (1/4x11/4 in.) fuse s.........................................page 28 - 29Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuses -Double-dec k.....................................................................................................................page 27Terminal blocks for test circuits with sliding bridge ......................................................page 30Terminal blocks for metering circuits.............................................................................page 31ESSAILEC terminal blocks.............................................................................................page 32Safety connection terminal blocks ................................................................................page 33Miniblocks for EN 50045 (DIN 46277/2) rail ..........................................................page 34 - 35Spring clamp ......................................................................................page 36Angled terminal blocks - Feed through and ground .....................................................page 36Feed through and ground terminal blocks ...........................................................page 37 to 41Feed through terminal blocks - Double deck ................................................................page 42Terminal blocks for sensors / actuators ........................................................................page 42Terminal blocks for distribution boxes...........................................................................page 43Switch terminal blocks for neutral conductor........................................................page 44 - 45Heavy duty switch terminal blocks with blade..............................................................page 46Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuse s....page 47Miniblocks Spring clamp ......................................................................................page 48 to 52ADO - Screw clamp ...........................................................................page 53Feed through and ground terminal blocks ...........................................................page 53 to 56Feed through and ground terminal blocks - Double-deck............................................page 57Heavy duty switch terminal blocks with blade..............................................................page 58Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuse s ......page 59 - 60Miniblocks ADO - Screw clamp............................................................................page 61 to 65ADO - ADO .........................................................................................page 66Feed through and ground terminal blocks ...........................................................page 66 to 69Feed through and ground terminal blocks - Double-deck............................................page 70Terminal blocks for sensors / actuators ........................................................................page 71Heavy duty switch terminal blocks with blade..............................................................page 72Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuse s ......page 73 - 74Miniblocks ADO - ADO .........................................................................................page 75 to 79Accessories ADO ...........................................................................................................page 80Power terminal blocks .............................................................page 81 to 84Quick-connect terminal blocks .................................................page 85 - 86Terminal blocks for railway applications ................................page 87 to 97Pluggable terminal blocks .....................................................page 98 to 100Accessories......................................................................................page 101Marking..................................................................................page 102 to 104GrossAutomation(877)268-3700··*************************PR30PR3.Z2PR3.G2PR5PR4PR1.Z2Rated wire size :Rated wire size :Rated wire size :Rated wire size :Mounting railsShield terminals forcollector barMarking tableHorizontal Rated wire size :0.5 to 16 mm² (22 to 8 AWG)Rated wire size :Rated wire size :Rated wire size :P a g e t o 29e30 t o 32ag e e3P a ge 8 t o 60a g e6t o 6574P a ge 7 t o 79P a ge 9P a g P a gGrossAutomation(877)268-3700··*************************2ABB Entrelecd010830402051SNC 160 003 C0205MA 2,5/5 - 2.5 mm² blocks - 5 mm .200" spacingAccessoriesGrossAutomation(877)268-3700··*************************3ABB Entrelec D010740402051SNC 160 003 C0205M 4/6 - 4 mm² blocks - 6 mm .238" spacingAccessoriesGrossAutomation(877)268-3700··*************************4ABB EntrelecD011030402051SNC 160 003 C0205M 4/6.3A - 4 mm² blocks - 6 mm .238" spacingM 4/6.4A - 4 mm² blocks - 6 mm .238" spacingGrossAutomation(877)268-3700··*************************5ABB Entrelec D010840402051SNC 160 003 C0205M 6/8 - 6 mm² blocks - 8 mm .315" spacingAccessoriesGrossAutomation(877)268-3700··*************************6ABB EntrelecD010850402051SNC 160 003 C0205M 10/10 - 10 mm² blocks - 10 mm .394" spacingAccessoriesGrossAutomation(877)268-3700··*************************7ABB Entrelec D010860402051SNC 160 003 C0205M 16/12 - 16 mm² blocks - 12 mm .473" spacingAccessoriesGrossAutomation(877)268-3700··*************************8ABB EntrelecD010870402051SNC 160 003 C0205M 35/16 - 35 mm² blocks - 16 mm .630" spacingGrossAutomation(877)268-3700··*************************M 95/26 - 95 mm² blocks - 26 mm 1.02" spacingM 70/22.P - 70 mm² ground block with rail contact - 22 mm .630" spacingSelection35 mm / 1.37"12 mm / 0.47"14-30 Nm / 124-260 Ib.in 1.2-1.4 Nm / 10.6-12.3 Ib.in1000600600415400400577070240 mm 2500 MCM 500 MCM 10 mm 2 6 AWG 6 AWG IEC UL CSANFC DIN0.5 - 160.5 - 100 AWG-600 MCM 2 AWG-500 MCM 50 - 30035 - 24018-6 AWGD 150/31.D10 - 150 mm² blocks - 31 mm 1.22" spacingCharacteristicsD 240/36.D10 - 240 mm² blocks - 36 mm 1.41" spacingSelectionWire size main circuit mm² / AWG VoltageV Current main circuit A Current outputARated wire size main circuit mm² / AWG Rated wire size outputmm² / AWG Wire stripping length main circuit mm / inches Wire stripping length output mm / inches Recommended torque main circuit Nm / Ib.in Recommended torque outputNm / Ib.inSolid Stranded Solid Stranded Wire size output mm² / AWG9.5 mm / .37"0.5-0.8 Nm / 4.4-7.1 Ib.in5003003003220204 mm 212 AWG12 AWG0.2 - 422-12 AWG 22-12 AWG 0.22 - 4IEC ULCSANFC DINCharacteristicsWire size mm² / AWGSolid Stranded D 4/6.T3 - 4 mm² blocks - 6 mm .238" spacingSelectionVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inM 4/6.T3.P - 4 mm² block - 6 mm .238" spacingD 2,5/6.D - 2.5 mm² blocks - 6 mm .238" spacingD 2,5/6.DL - 2.5 mm² blocks - 6 mm .238" spacingD 2,5/6.DPA1 - 2.5 mm² blocks - 6 mm .238" spacingD 2,5/6.DPAL1 - 2.5 mm² blocks - 6 mm .238" spacingD 4/6... - 4 mm² blocks - 6 mm .238" spacingD 4/6.LNTP - 4 mm² closed blocks - 17.8 mm .700" spacingMA 2,5/5.NT- 2.5 mm² block - 5 mm .200" spacingAccessories**SFB2 : 16 to 35 mm² 6 to 2 AWG H= 3 mm/.12"M 10/10.NT- 10 mm² block - 10 mm .394" spacingAccessories(1) Except for M 35/16 NT (closed block)*SFB1 : 0.5 to 35 mm² 18 to 2 AWG H= 7 mm/.28"**SFB2 : 16 to 35 mm² 6 to 2 AWG H= 3 mm/.12"MB 4/6... - 4 mm² blocks - 6 mm .238" spacingMB 6/8... - 6 mm² blocks - 8 mm .315" spacingMB 10/10... - 10 mm² blocks - 10 mm .394" spacingBRU 125 A - 35 mm² block - 27 mm 1.063" spacingBRU 160 A - 70 mm² block - 35.2 mm 1.388" spacingBRU 250 A - 120 mm² blocks - 44.5 mm 1.752" spacingBRU 400 A - 185 mm² block - 44.5 mm 1.752" spacingAccessoriesAccessoriesBRT 80 A - 16 mm² block - 48 mm 1.89" spacingBRT 125 A - 35 mm² block - 48 mm 1.89" spacingBRT 160 A - 50 mm² block - 50 mm 1.97" spacing9.5 mm / .37"0.5-0.6 Nm / 4.4-5.3 Ib.in4003003002010104 mm 210 AWG 12 AWG 0.5 - 422-10 AWG20-12 AWG0.5 - 2.5IEC ULCSANFC DINMA 2,5/5.SNB - 2.5 mm² blocks - 5 mm .200" spacingCharacteristicsM 4/6.SNB - 4 mm² blocks - 6 mm .238" spacingSelectionWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inSolid StrandedM 6/8.SNB - 6 mm² blocks - 8 mm .315" spacing - blade switchingSelectionAccessoriesM 4/8.D2.SF - for fuses 5x20 mm .197x.787 in. and 5x25 mm .197x.984 in. -4 mm² blocks - 8 mm .315" spacingM 4/6.D2.SNBT - 4 mm² blocks - 6 mm .238" spacing - blade switchM 4/8.SF- 4 mm² blocks - 8 mm .315" spacingM 4/8.SFL - 4 mm² blocks - 8 mm .315" spacing12 mm / .472"1.2-1.4 Nm / 10.6-12.3 Ib.in800(1)60060016252510 mm 210 AWG8 AWG0.5 - 1622-10 AWG 22-8 AWG 0.5 - 10IEC ULCSANFC DINCBD2SML 10/13.SF - for fuses 6.35x25.4 mm 1/4x1 in. and 6.35x32 mm 1/4x11/4 in. -10 mm² blocks - 13 mm .512" spacingSelectionAccessoriesCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inSolid Stranded (1) Insulation voltage of terminal block - operating voltage : according to fuse.M 4/6.D2.2S2... - 4 mm² blocks - 6 mm .238" spacing11 mm / .43"0.8-1 Nm / 7.1-8.9 Ib.in50060030306 mm 28 AWG0.5 - 1022-8 AWG0.5 - 6IECULCSANFC DINM 6/8.ST... - 6 mm² blocks - 8 mm .315" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inSolid Stranded M 6/8.STA - 6 mm² blocks - 8 mm .315" spacing(3)Only for M 6/8.STAM 4/6.ST- 4 mm² blocks - 6 mm .236" spacingBNT...PC...(2) Only for M10/10.ST-SnThe PREM IUM solution for testing the secondary circuits of current or voltage transformers.ESSAILEC, approved by the major electricity utilities, remains the premium choice for the energy market.Implemented in the transformers secondary circuits, ESSAILEC thanks to its intelligent “make before break” design eases and secures any intervention. Cutting the energy supply is avoided with zero risk for the operator.The plug and socket connection cuts cost installation as well as in-situ wiring errors. ESSAILEC is ideal for the wiring of sub-assemblies in the secondary circuits.ESSAILEC terminal blocksProtection relays,Protection relays,Testing :The ESSAILEC socket supplies energy to the protection or counting devices. The insertion of the test plug, which is connected to the measurement equipment, allows the testing of the devices, without perturbing the circuit.ESSAILEC blocks are well adapted to current or voltage measurement :-Current sockets with make before break contacts and pre-wired test plug for current measures-Voltage sockets with open contacts and pre-wired test plug for voltage measures-Up to 4 ammeters or 4 voltmeters connected to the test plugDistributing :The ESSAILEC plug is continuously mounted on the socket to supply current or voltage to secondary circuits sub assemblies.ESSAILEC blocks extreme versatility allow :-Safe current distribution with current socket with mobile contacts since the secondary circuit is not cut when plug is removed-Voltage or polarity distribution with dedicated voltage or polarity socket with closed contactESSAILEC is designed to offer :Great flexibility :-Connection multi contacts « plug and play »-Panel, rail, rack fixed mounting or stand-alone connector -Two wiring technologies, up to 10 mm²Extreme reliability :-Non symmetric blocks -Coding accessories -IP20 design -Locking system -Sealed coverR S T NFor technical characteristics and complete part numbers list, please ask for the ESSAILEC catalog10005006003225254 mm 21.65 mm²12 AWG 13 mm / .51"IECB.SCSANFC DINTS 50-180.5 - 0.8 Nm /4.4 - 7.1 Ib.in0.2 - 422-12 AWG0.22 - 40.5 - 1.50.28 - 1.6580050060041252562.512 AWG 13 mm / .51"0.8 - 1 Nm / 7.1 - 8.9 Ib.inIECB.S CSANFC DINTS 50-180.5 - 1020-12 AWG0.5 - 60.28 - 2.590050060046406510 mm 26 mm² 6 AWG 14 mm / .55"IECB.S UL/CSANFC DINTS 50-181.2 - 1.4 Nm / 10.6 - 12.3 Ib.in0.5 - 1620 - 6 AWG0.5 - 100.28 - 6M 4/6.RS - 4 mm² blocks - 6 mm .238" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping lengthmm / inches Recommended torque (screw)Nm / Ib.inSolid wire Stranded wire Solid wire Stranded wire Screw clampLugsM 6/8.RS - 6 mm² blocks - 8 mm .315" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping lengthmm / inches Recommended torque (screw)Nm / Ib.inSolid wire Stranded wire Solid wire Stranded wire Screw clampLugspending M 10/10.RS - 10 mm² blocks - 10 mm .394" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping lengthmm / inches Recommended torque (screw)Nm / Ib.inSolid wire Stranded wire Solid wire Stranded wire Screw clampLugspending SelectionAccessories(1) Only for block M 4/6.RS (4) For blocks M 4/6.RS and M 6/8.RS(2) Only for block M 6/8.RS(3) Only for block M 10/10.RSDR 1,5/4 - 1.5 mm² blocks - 4 mm .157" spacingDR 1,5/5... - 1.5 mm² blocks - 5 mm .200" spacing。
施耐德断路器选择1进线和分段断路器-空气断路器1.1一般规定变压器容量S≤800kV A,断路器选用MT06~16N 分断能力I cu=I cs=50kA, I cw=36kA (1s)控制单元选用Micrologic 5.0A变压器容量S ≥1000kV A,断路器选用MT20~40H1-H2分断能力I cu=I cs=65-100kA,I cw=65-85kA (1s)控制单元选用Micrologic 5.0A1.2应用举例配电变压器S9-630KV A, 4.5%,二次侧额定电流I n2=909A,最大工作电流I2max=957A,二次侧最大三相短路电流I k=17.91kA,最小16.2kA1.2.1进线断路器选用MT12N2, 1250A,4P空气断路器,额定电流I n=1250A(1)过载长延时保护-反时限,t=k/I2整定电流:I r=1.05×957=1005A,取I r=0.8I n=1000A(整定范围500 ~ 1250A)即0.4~1.0I n长延时整定时间(6I r的动作时间)要与以下条件配合:1)应躲过最大一台电动机起动时间,或自动再起动时间;2)变压器二次侧最大短路时,过载保护动作时间不小于0.4s,即K=179102⨯0.45=(6⨯I r)2⨯t r=60002⨯t r得t=4.01s取t r=4 s或t r=8 s(级差为4s)当变压器过载1.3倍,即I=1.3⨯957=1244A时,若t r=4s保护动作时间:t=(60002⨯4)÷12442=93 s 可见,太保守-完全没有发挥变压器的过载能力取t r=8s(2)短路短延时保护整定电流I sd的整定应取以下两种情况最大者:1)一台变压器带总负荷(不含最大电动机负荷)加上最大一台电动机的起动电流;2)一台变压器带50%总负荷,加上另一段母线上电动机自动再起动电流;有时,为了简化计算,可取2.0~2.5倍变压器额定电流,即认为变压器最大尖峰电流不超过额定电流的2~2.5倍。
新型低压空气断路器和负荷开关400A 〜4000AEasyPact MVS追求品质 简单选择产品简介施耐德电气中国Schneider Electric China 北京市朝阳区望京东路6号施耐德电气大厦邮编: 100102电话: (010) 8434 6699传真: (010) 8450 1130Schneider Electric Building, No. 6, East WangJing Rd., Chaoyang District Beijing 100102 P.R.C.Tel: (010) 8434 6699Fax: (010) 8450 1130由于标准和材料的变更,文中所述特性和本资料中的图像只有经过我们的业务部门确认以后,才对我们有约束。
本手册采用生态纸印刷2012.12SCDOC1708施耐德电气中国版权所有 998-6373客户关爱中心热线:400 810 1315性能出众品质如一性能可靠,配置灵活,通用性强。
品质如一,保护全面,值得信赖。
产品+服务+解决方案的超值组合。
建 筑工 业住 宅能 源海 事选型指南MVS04N3D20控制回路电压:0 : 机械储能(无线圈)1 : 电动储能/AC110V 2 : 电动储能/AC220V 3 : 电动储能/AC380V 4 : 电动储能/DC220V 5 : 电动储能/DC110V 6 : 电动储能/DC48V 7 : 电动储能/DC24V控制单元20 : MVS Trip System 2.0 二段保护50 : MVS Trip System 5.0 三段保护60 : MVS Trip System 6.0 三段保护+接地故障5A : MVS Trip System 5.0A 三段保护 +电流表6A : MVS Trip System 6.0A 三段保护 +电流表+接地故障5V : MVS Trip System 5.0V 三段保护 +电压表6V : MVS Trip System 6.0V 三段保护 +电压表+接地故障00 : 负荷开关,无控制单元型式D : 抽屉式; F : 固定式极数3 : 3 极;4 : 4 极断路器分断类型N : 50kA; H : 65kA; T : 85kA; S :负荷开关断路器额定电流 (范围:04/400A-40/4000A)断路器类型断路器型号附件数量可增加OF 触点(***)CB 二次端子罩EIP 相间隔板PF 合闸准备触点MN 失压线圈位置触点(****)VSPO(*)本体OFF 位置锁VBP 按钮锁定装置VSPD 抽架退出位置钥匙锁VPEC 抽架门联锁VPOC抽架摇入联锁接线方式(**)CCS 证书MVS □□□□□□□□+□+□+□+□+□ AC110V □ AC220V □ AC380V □ DC220V □ DC110V □ DC48V □ DC24V +□ CE 连接□ CD 退出□ CT 实验+□+□+□+□ 左侧□ 右侧+□+□ 水平接线□ 垂直接线+ □x □MVS □□□□□□□□+□+□+□+□+□ AC110V □ AC220V □ AC380V □ DC220V □ DC110V □ DC48V □ DC24V +□ CE 连接□ CD 退出□ CT 实验+□+□+□+□ 左侧□ 右侧+□+□ 水平接线□ 垂直接线+ □x □MVS □□□□□□□□+□+□+□+□+□ AC110V □ AC220V □ AC380V □ DC220V □ DC110V □ DC48V □ DC24V+□ CE 连接□ CD 退出□ CT 实验+□+□+□+□ 左侧□ 右侧+□+□ 水平接线□ 垂直接线+ □x □本体锁(锁芯)□ 一锁一匙x □(*) 选择“本体OFF 位置锁”选项后再选择具体“锁芯”的配置。
施耐德断路器选择1进线和分段断路器-空气断路器1.1一般规定变压器容量S≤800kV A,断路器选用MT06~16N 分断能力I cu=I cs=50kA, I cw=36kA (1s)控制单元选用Micrologic 5.0A变压器容量S ≥1000kV A,断路器选用MT20~40H1-H2分断能力I cu=I cs=65-100kA,I cw=65-85kA (1s)控制单元选用Micrologic 5.0A1.2应用举例配电变压器S9-630KV A, 4.5%,二次侧额定电流I n2=909A,最大工作电流I2max=957A,二次侧最大三相短路电流I k=17.91kA,最小16.2kA1.2.1进线断路器选用MT12N2, 1250A,4P空气断路器,额定电流I n=1250A(1)过载长延时保护-反时限,t=k/I2整定电流:I r=1.05×957=1005A,取I r=0.8I n=1000A(整定范围500 ~ 1250A)即0.4~1.0I n长延时整定时间(6I r的动作时间)要与以下条件配合:1)应躲过最大一台电动机起动时间,或自动再起动时间;2)变压器二次侧最大短路时,过载保护动作时间不小于0.4s,即K=179102⨯0.45=(6⨯I r)2⨯t r=60002⨯t r得t=4.01s取t r=4 s或t r=8 s(级差为4s)当变压器过载1.3倍,即I=1.3⨯957=1244A时,若t r=4s保护动作时间:t=(60002⨯4)÷12442=93 s 可见,太保守-完全没有发挥变压器的过载能力取t r=8s(2)短路短延时保护整定电流I sd的整定应取以下两种情况最大者:1)一台变压器带总负荷(不含最大电动机负荷)加上最大一台电动机的起动电流;2)一台变压器带50%总负荷,加上另一段母线上电动机自动再起动电流;有时,为了简化计算,可取2.0~2.5倍变压器额定电流,即认为变压器最大尖峰电流不超过额定电流的2~2.5倍。
施耐德电气选型手册施耐德低压电器选型接触器:I<=7.5A LC1-D0922M5C I<=98A LC1-D11522M5C I<=10A LC1-D1222M5CI<=128A LC1-D15022M5C; I<=15.3A LC1-D1822M5C I<=145A LC1-D17022M5CI<=21A LC1-D2522M5C I<=175A LC1-D20522M5C I<=27.2A LC1-D3222M5C I<=210A LC1-D24522M5C I<=34A LC1-D4022M5C I<=260A LC1-D30022M5C I<=42.2A LC1-D5022M5C ; I<=350A LC1-D41022M5C I<=55.5A LC1-D6522M5C I<=410A LC1-D47522M5C I<=68A LC1-D8022M5C I<=540A LC1-D62022M5C I<=82A LC1-D9522M5C 热继电器:I<=0.16A LRD-01C I<=18A LRD-21C I<=0.25A LRD-02C I<=24A LRD-22CI<=0.40A LRD-03C I<=32A LRD-32C I<=0.63A LRD-04C I<=38A LRD-35C I<=1A LRD-05C I<=50A LRD-3357CI<=1.6A LRD-06C I<=65A LRD-3359CI<=2.5A LRD-07C I<=70A LRD-3361CI<=4A LRD-08C I<=80A LRD-3363CI<=6A LRD-10C I<=104A LRD-4365 I<=8A LRD-12C I<=120A LRD-4367I<=10A LRD-14C I<=140A LRD-4369I<=13A LRD-16C空气开关:电机的: 配电的:I<=11A NSX100HMA12.5 3P I<=13A NSX100HTM16 3PI<=23A NSX100HMA25 3P I<=18A NSX100HTM25 3PI<=45A NSX100HMA50 3P I<=29A NSX100HTM32 3PI<=70A NSX100HMA80 3P I<=35A NSX100HTM40 3PI<=90A NSX100HMA100 3P I<=45A NSX100HTM50 3PI<=140A NSX160HMA160 3P I<=55A NSX100HTM63 3PI<=230A NSX250HMA250 3P I<=70A NSX100HTM80 3PI<=360A NSX400HMIC2.3M 400 3P I<=90A NSX100HTM100 3PI<=570A NSX630HMIC2.3M 630 3P I<=110A NSX160HTM125 3PI<=140A NSX160HTM160 3PI<=180A NSX250HTM200 3PI<=225A NSX250HTM250 3PI<=360A NSX400HMIC2.3 400 3P I<=600A NSX630HMIC2.3 630 3P 三、中间继电器40、31、22CA2-DN??M5C常闭接点数量常开接点数量四、框架断路器:I=800A 型号:MT08N13P MIC 5.0AI=1000A 型号:MT10N13P MIC 5.0AI=1250A 型号:MT12N13P MIC 5.0AI=1600A 型号:MT16H13P MIC 5.0AI=2000A 型号:MT20H13P MIC 5.0AI=2500A 型号:MT25H13P MIC 5.0AI=3200A 型号:MT32H13P MIC 5.0AI=4000A 型号:MT40H13P MIC 5.0ATD101B(分体式,P<=45kW)TD101BB(分体式,P>45kW,用三只电流互感器)TD101B-#-M(#用数字1~5代替,1:1A、2:6.3A、3:25A、4:63A、5:100A)(M代表有4~20mA输出,不输出时取消M)TD101BB-#-M(#用数字6~7代替,6:200A、7:400A)(M代表有4~20mA输出,不输出时取消M) 并注明电流互感器的变比。
2(停产无替代?)Masterpact MW 空气断路器选型表框架电流06:630A 20:2000A 08:800A 25:2500A 10:1000A 32:3200A 12:1250A 40:4000A 16:1600A 2:Micrologic2.0MW二段保护5:Micrologic5.0MW三段保护A:Micrologic5.0A MW三段保护+电流表MW 06 3 F 2 33:3极4:4极F:固定式D:抽屉式控制回器电压2:AC220V3:AC380V1:DC110V4:DC220VCompact NS塑壳断路器选型表(合用于配电保护)脱扣器类型TM:热磁脱扣器(用于NS100,160,250)STR22SE电子脱扣器(用于NS100,160,250)STR23SE电子脱扣器(用于NS400,630)STR53UE电子脱扣器(用于NS400,630)NS 100 N STR22SE 100 3P F FC 附件壳架电流规格100 160 250 400 630 分断能力可选N:25-50KAH:70KAL:150KANS80惟独H型脱扣器额定电流(参见脱扣器选择表)极数可选3P4P安装方式F:固定式P:插入式W:抽出式联接方式FC:板前方式RC:板后方式多种联接附件可选取详见样本1、分励/失压线圈2、多功能辅助开关3、电动操作机构4、漏电保护模块5、电流表模块6、电流互感器模块7、延伸旋转手柄Compact NS塑壳断路器选型表(合用于电动机保护)脱扣器类型MA:电磁脱扣器(用于NS80-630)STR22ME:电子脱扣器(用于NS100,160,250)STR43ME:电子脱扣器(用于NS400,630)NS 100 H MA 50 3P F FC 附件壳架电流规格80 100 160 250 400 630 分断能力可选N:25-45KAH:70KAL:150KANS80惟独H型脱扣器额定电流(参见脱扣器选择表)极数可选3P4P安装方式F:固定式P:插入式W:抽出式联接方式FC:板前方式RC:板后方式多种联接附件可选取详见样本1、分励/失压线圈2、多功能辅助开关3、电动操作机构4、漏电保护模块5、电流表模块6、电流互感器模块7、延伸旋转手柄NS 400一下停产用NSX替代IC65 断路器选型表IC65 N - C 20A / 2P + VE + SD分断能力N:6000A H:10000A L: 15000A 脱扣曲线C型曲线(配电保护)D型曲线(动力保护)额定电流1A2A4A6A10A16A20A25A32A40A50A63A极数1P2P3P4P可配漏电保护附件VE:vigi IC65 ELEVEG:vigi IC65 G ELEVM:vigi IC65 ELM可配电气附件MX:分励脱扣单元MN欠压脱扣单元(瞬动型)MN(s):欠压脱扣单元(延时型)SD:报警接点OF:辅助接点OF+SD/OF:双重切换接点IC65N 2P C(D)1OA NC100H/125H 断路器选型表NC 100H - C 63A / 2P + VM + SD类型NC 100H NC125H 脱扣曲线C型曲线(照明保护)D型曲线(动力保护)额定电流63A80A100A125A极数1P2P3P4P可配漏电保护附件Vigi NC100可配电气附件MX:分励脱扣单元MN:欠压脱扣单元MN(s):欠压脱扣单元(延时型)SD:报警接点OF:辅助接点说明:1、NC 125H的额定电流为125A。