摘要
本设计的建筑为二十三层的办公综合楼,给排水工程设计包括了室内生活给水系统设计,室内排水系统设计,室内消防给水系统设计,以及雨水系统设计。生活给水系统分为两个区:地下室至三层为低区,采用市政给水管网直接供水;四层至二十三层为高区,利用屋顶高位水箱给系统供水。消防给水系统分为消火栓给水系统和自动喷淋灭火系统,本建筑为一类民用建筑,而其建筑高度≥50m,按《高层民用建筑防火设计规范》规定,室内消火栓用水量和室外消火栓用水量分别取20L/s和15L/s,自动喷淋系统计算用水量为16L/s,自动喷淋系统在屋顶设增压设备。排水系统采用污废合流制,排水系统采用特殊的伸顶通气单立管排水系统,通气冒高出屋顶。给水系统采用PP-R给水管材,消火栓给水系统和自动喷淋灭火系统采用无缝镀锌钢管,排水系统立管采用PPI螺旋排水管,各层排水支管采用普通的UPVC排水管。在地下层设贮水池和加压泵房,地下室另设集水坑,集水坑中设潜污泵,保证污水及时排出。
关键词:建筑 给水 消防 喷淋 排水
Abstract
Work in the complex building for23 floors of trade in the building originally designed, is it drain off water engineering design including room is it supply water
system design , indoor fire control supply water the system is designed and the
indoor drainage system set up to live to give. Life supplies water and is divided
into two districts systematically: The ground lower floor to 3floor are the low
district, adopt the pipe network of municipal water supply and supply water directly;
4are the high district to the 23th Floor, supply water for the system with the
high-order water tank of the roof. Fire control supply water system divide into
fire hydrant supply water system and automatic spray fire extinguishing system,
building this one building, but area its does not exceed 1000m2, stipulate according
to " high-story civil building fire prevention the design specification ", water
consumption of the indoor fire hydrant and outdoor fire hydrant water consumption
fetch 20L/s and15L/s respectively, automatic spray systematic water consumption
fetch 16L/s, automatic spray system set up the pressurized equipment on the roof.
Supply water system adopt PP-R supply water pipe , fire hydrant supply water system
and automatic spray fire extinguishing system adopted and has not sewn the
zinc-plated steel tube , the drainage system sets up and is in charge of adopting
PPI spiral drain pipe, drain off water and prop up in charge of adopting ordinary
UPVC drain piping on the everyth floor. Sets up the storage cistern and pressurizes
in the pump house in the ground lower floor, the basement sets up and collects the
puddle separately , collect and set up and sneak the corrupt pump in the puddle,
guarantee sewages are discharged in time.
Keyword: Building Supply water Fire control Spray
目 录
1.设计任务及设计资料 ·················· 4
设计任务 ······················ 4
设计文件及设计资料 ················ 4
设计成果 ······················ 5
2.设计说明 ························· 6
室内给水系统 ··················· 6
室内消防系统 ···················· 8
室内排水系统 ···················· 11
雨水系统 ······················ 12
3.设计计算 ························· 13
冷水系统计算 ··················· 13
室内消火栓系统计算 ················ 32
室内自动喷淋系统计算 ··············· 38
室内排水系统计算 ················· 41
4.总结 ··························· 58
致谢信 ··························· 59
参考文献 ·························· 60
1设计任务及设计资料
设计任务
根据有关部门的批准,长春市拟建一幢商住楼(详见建筑平面图),该建筑属一类高层建筑,建筑高度69米,地上23层,地下1层。本项目位于长春市,建筑占地面积1138平方米,抗震设防烈度为7级,耐火等级为一级,耐久年限为一级。本工程一层大厅标高为±,相当于国家高程值。
设计的具体项目有:
室内给水系统设计
室内排水系统设计
室内消火栓系统设计
室内自动喷淋系统
设计文件及设计资料
上级主管部门批准的设计任务书
建筑给水排水设计规范
建筑设计防火规范
高层民用建筑设计防火规范
自动喷水灭火系统设计规范
建筑设计资料
建筑物各层平面图,地下1层为设备房、非可燃库房、自行车库、地下贮水池用房。为电梯间顶高度,根据建筑物性质、用途及建筑单位要求,室内设有完善的给排水卫生设备,无集中热水供应系统,。该大楼要求消防给水安全可靠,设置独立的消火栓系统及自动喷水系统,每个消火栓内设按钮,消防时直接启动消防泵。生活水泵采用变频技术及自动化技术。管道根据具体情况采用明敷或暗敷。
城市给水排水资料
本建筑位于我国长春市,建筑高度与功能分配及建筑室内外高差详见条件图纸,城市给水网允许从建筑西侧接入一条DN200的管道,埋深米;城市排水网允许从建筑南面接入一条不大于DN300的管道,接口检查井管底相对标高米。该地区冬季冻土深度米,地下水位深度米。
设计成果:
毕业设计说明书(附计算书)
毕业设计说明书,计算书一般为60—90页,(约万—万字)应包括目录,前言,正文,小结,及参考文献等,学生必须用外语书写毕业设计摘要。在设计过程中学生必须运用计算机进行部分设计运算。具体设计说明书的书写格式参见毕业设计指导书。
毕业设计图纸
毕业设计图纸的数量不得少于10张, 图面应布置合理,正确清晰,用工程字注文,符合制图标准及有关规定。
在绘图能力方面的要求:所有的图纸用CAD软件绘制
在设计深度方面的要求:本毕业设计的深度为施工图设计深度
2设计说明
室内给水系统
室内给水系统方案比较与确定
(1)由《给排水设计手册》可知:内部给水系统应尽量利用外部给水管网的水压直接供水。在外部管网水压不能满足整个建筑或建筑小区的用水要求时,则建筑物的下层或地势较低的建筑,应尽量利用外管网的水压直接供水,上层或地势较高的建筑设置加压和流量调节装置供水。