6 64调试检查单

  • 格式:pdf
  • 大小:536.04 KB
  • 文档页数:4

6.64型滤器调试确认单// Commissioning check list
A。

Item Installation滤器安装检查Y N A-1:All parts free of damage 所有部件无缺损
A-2: All the connecting pipes have been connected and tightened
所有管路都已连接并上紧
A-3: Air pipe has been flushed and without any dirty
空气管路已确认干净无任何杂质
A-4: 0.4 ~1.0 Bar compressed air supply is available
0.4~1.0Bar的净洁干燥压缩空气已接到。

A-5: inlet and outlet oil pipes have been flushed and without any dirty
进出口管路已确认干净无任何杂质
A-6: There is no any external forces and torques on the connection flanges to make
sure the filter house no twisted
进出口管路没有对滤器本体产生额外的应力
A-7:the flushing oil pipe are correctly installed: The pipe must also be laid with an inclination and without any counterpressure
冲洗油排出管路安装正确:大小符合图纸要求,不能向上有弯头,不建议安
装任何阀门(尤其是截止阀)总之:要没有背压。

B。

Item Electric installation电气项目安装检查Y N B-1: All the connecting cables has been connected correctly
所有的电缆已经正确接好
B-2: Cable and their connections free of damage
线缆和接头无缺损
B-3: Main supply to switch box connected and checked?
主电源已连接并检查无误
B-4:All parameters set correctly
各参数设定正常(如可设定参数见附件二,参数设置如附件三)
C。

Function check and test 功能检查测试Y N C-1: Timer Flushing normally( by set the timer parameters to 5mintines.)
模拟定时冲洗正常(如定时冲洗参数减小到5分钟
C-2: DP flushing normally
模拟压差冲洗正常(见附件一) 或者采用精密压力泵。

C-3: Manual flushing (by Push the Manual flushing button)
手动强制反冲功能正常(按下控制箱强制冲洗按键)
C-4: Motor fault alarm test by reduce the P9 to 200mA
模拟马达过载报警(把参数P9减少到200mA, 再按下冲洗按键)
C-5:DP too high alarm
模拟压差过高报警(见附件一) 或者采用精密压力泵。

C-6: the air bottle pressure can drop to zero during flushing
观察在冲洗时,空气储气罐的压力能降到零
6.64型滤器调试确认单// Commissioning check list
附件一:DP flushing and DP too high alarm 模拟压差冲洗和压差过高报警。

1. star oil pump 起动泵
2. shut off the outlet pressure measure pipe 关断到压差指示器管路(测量滤器出口压力的管路)
3. Open a connector carefully to release the pressure 松开这个管路上的一个接头以释放压力。

4. Observe when the DPI red color reaches half, comes DP back flushing
压差指示器红色过一半时,出现压差反冲洗。

5. Observe when the DPI gets full red, comes ‘DP too high alarm’
当压差指示器全红时,出现‘压差过高’报警。

6.64型滤器调试确认单// Commissioning check list
附件二:如何读取和修改2200控制箱的参数
•Read Parameters
,Until the Green ‘operation’LED is
Pushing and together, about 3 seconds
Extinguished 。

The first display line shows the parameter and the second line shows the parameter
value. All parameters can now be displayed by repeatedly pressing the key or .
•Setting level - Changing and saving parameters
In order to access the setting level "Changing and saving parameters", press the middle key until the
green "Operation" LED flashes (approximately 3 seconds).The parameter can now be changed by
repeatedly pressing the key or . In order to "Selecting and viewing parameters", press the middle key until the green "Operation" LED is
extinguished (approximately 3 seconds).
•Return to operation level
In order to access the operation level, press keys and together until
the green "Operation" LED lights up (approximately 3 seconds)
6.64型滤器调试确认单
// Commissioning check list
附件三:参数设置:。