110KV供电系统继电保护作用浅析中英文翻译资料
- 格式:pdf
- 大小:1.77 MB
- 文档页数:10
电力系统继电保护论文中英文资料Relay protection development present situation[Abstract ]reviewed our country electrical power system relay protection technological devil orpiment process,has outlined the microcomputer relay protection technology achievement, pro posed the future relay protection technological development tendency will be: Computerizes, n networked,protects, the control,the survey,the data communication integration and the artificial I intellectualization.[Key word ]relay protection present situation development,relay protections future development1 relay protection development present situationThe electrical power system rapid development to the relay protection proposed unceasingly t he new request,the electronic technology,computer technology and the communication rapid development unceasingly has poured into the new vigor for the relay protection technology de velopment,therefore,the relay protection technology is advantageous, has completed the deve lopment 4 historical stage in more than 40 years time。
浅析110 kV电力继电保护技术作者:兰颖王向伟来源:《世纪之星·交流版》2015年第05期[摘要]文章介绍了当前电力系统110 kV继电保护装置技术要求,如何使电力系统继电保护装置做到高效,安全,可靠的运行将是一个重要问题,对我国电力系统的发展有着重要的意义。
[关键词]110kV;继电保护;装置;技术分析一、继电保护的概述与基本任务继电保护主要是指确保电力系统供电可靠性和保障电气设备安全。
继电保护的可靠性是指保护装置在预定时间内在规定条件下完成规定功能的能力。
一般要求继电保护装置满足选择性、可靠性、速动性和灵敏性要求,能在电网发生故障时快速、可靠地动作,有效遏制系统状态进一步恶化,起到保障电网安全的作用。
继电保护系统主要根据电气元件发生故障时电力系统的电气量的变化情况构成保护动作,即该系统由一套或者几套相互独立的继电保护装置经某种方式相连接构成。
继电保护的首要任务是在被保护元件发生故障时,确保该元件的继电保护装置向距故障元件最近且具有脱离故障功能的断路器迅速、准确地发出跳闸命令,使故障元件能够及时、快速地从电力系统中剥离,从而尽可能地降低电力系统元件本身损坏。
这样,可以最大限度地降低故障元件对电力系统安全稳定供电的影响。
其次,继电保护还能够在一定程度上反映电气设备的不正常运行状态。
当设备运行维护条件不当或者设备不正常运行时,继电保护能够发出警示信号,便于自动装置进行调节、自动切除某些危险设备或者提醒值班人员进行及时处理。
二、110 kV继电保护装置技术要求1.继电保护装置的设置基本要求。
按照电力企业110kV 供电系统的设计规范要求,在110kV 的供电线路、配电变压器和分段母线上一般应设置以下保护装置:(1)110kV 线路应配置的继电保护。
110kV 线路一般均应装设过电流保护。
当过电流保护的时限不大于0.5~0.7s,并没有保护配合上的要求时,可不装设电流速断保护;自重要的变配电所引出的线路应装设瞬时电流速断保护。
中文2012字110Kv power supply system relay protection function brief analysis Not only the 110Kv power supply system relay protection function brief analysis electrical power system security and the reliability relate electrical power system itself the movement, similarly relates in the power transmission scope the factories and mines, the enterprise, whether the inhabitant uses electricity normally.Because simultaneously the electrical power system has the strong connectivity, electrical power system interior any barrier all possibly affects the overall system normal operation, thus we must complete the power supply system practically the relay protection question.First, the 11OKV power supply systemGenerally speaking electrical power system including the electricity generation, changes the electricity, the electric transmission, the power distribution and uses electricity and so on five links, between five links restricted mutually, cooperates mutually has facilitated the electrical power system stability together.But in fact, because these five links not always in the identical place, the identical time complete, the electric transmission must surmount the vast area, simultaneously the electrical power system must not carry on the connection with the equipment, thus strengthened its movement environment complexity, causes electrical power system the zero failure rate to guarantee with difficulty.The 110Kv power supply system is in the entire electrical power system important constituent, it whether safe, stable, reliable movement, not only relates the system own movement quality, whether moreover relates in its power transmission scope general user normal prompt using electricity, it the economical normal development and the society is stably taking on the important energy safeguard duty to the power transmission scope in.Therefore the 110KV power supply system design and the movement management must observe national comprehensively the related standard and the standard, as well as correlation area specifically standard standard.In the 110Kv power supply system is containing a subsystems and two subsystems.Two subsystems were opposite in a subsystems are complex, violate the subsystems to include the relay protection installment, the automatic device and the secondary circuit.The relay protection installment is uses for in the power supply system to a subsystems to carry on the surveillance,the survey, the control and the protection, is composed set of special automatic devices by the relay.The reasonable relay protection installment correct establishment to guarantees the 110Kv power supply system the normal operation to have the positive function.Second, the relay protection digs reads and the related principleElectrical power system rapid development to the relay protection to propose unceasingly the new request, the electronic technology, the computer technology and the communication rapid development unceasingly has poured into the new vigor for the relay protection technology development.The relay protection is refers when in the electrical power system electric power part (for example generator, line and so on) or electrical power system itself has occurred the breakdown endangers the electrical power system safe operation, can to the attendant promptly send out the warning signal, or directly to the circuit breaker which controls sends out the trip order to terminate one kind of automated protection which these events develop, the relay protection equipment can monitor the electrical equipment the normal work situation, and sends out the prompt signal differently according to the normal work situation and the equipment movement maintenance condition, in order to the attendant carries on prompt processing, either carries on the adjustment automatically by the protective device, either continues these to move possibly can cause the accident electrical equipment to excise.Response normal work situation relay protection equipment common belt certain time-lag action.The relay protection principle of work mainly has used in the electrical power system the part has when the short circuit or the unusual situation the electrical quantity (electric current, voltage, power, frequency and so on) change as well as in transformer fuel tank when breakdown occurs the massive gas and the oil stream speed increase or the flowing tubing head pressure intensity increase the higher condition.The electrical power system request provides the safekeeping of security for it to continue the electricity installment to have following performance:(1) reliability. The reliability is refers to the protection to be supposed to move time the body should act reliably.Should not when the movement should reliable not act.The reliability is to the relay protection installment performance most basic request.(2) selectivity. The selectivity is refers first by the breakdown equipment logical 'OR' circuit itself protection excision breakdown, when the breakdown equipment logical 'OR' circuit itself protection or the circuit breaker resist moves, only then allows by the neighboring equipment to protect, the line protection or the circuit breaker malfunction protection excision breakdown.In order to guarantee has in the coordinate request protection and the identical protection has the coordinate request two parts (for example start and trip part or block system and movement part) the selectivity to the neighboring equipment and the line, its sensitivity coefficient and the operating time, should coordinate mutually in the ordinary circumstances.(3) sensitivity. The sensitivity is refers when the equipment logical 'OR' circuit occurs by the extent of protection in the metallicity short circuit, the protective device should have the essential sensitivity coefficient, each kind of protection smallest sensitivity coefficient has the specific stipulation in the regulations.Selectivity and sensitive request, through relay protection installation realization.(4) speed. The speed is refers to the protective device to be supposed to excise the short circuit breakdown as soon as possible, its date enhances the system stability, reduces the breakdown equipment and the line damage degree, reduces the breakdown to affect the scope, enhances automatic switches on again with the emergency power supply or the emergency apparatus automatic investment effect and so on.Third, relay protection in 11OKV power supply system Chen Ai function1. The guarantee continues the electricity system the reliability is plays the relay protection installment role the premise. Continues the electricity system the reliability is plays the relay protection installment role the premise.Generally speaking the relay protection reliability mainly by the disposition reasonable, the quality and the technical performance fine relay protection installment as well as the normal movement maintenance and the management guaranteed.2. Relay protection in electrical power system safe operation function. The relay protection mainly has following two points in the electrical power system safe operation function:(1) safeguard electrical power system security.When is protected when the electricalpower system part breaks down, should rapidly accurately for be separated from the breakdown part recent circuit breaker by this part relay protection equipment to send out the trip order, causes the breakdown part to interrupt promptly from the electrical power system, by maximum limit reduces to the electrical power system part itself damage, reduces to the electrical power system safe power supply influence, and satisfies the electrical power system certain specific requests (for example maintenance electrical power system transition condition stable and so on).(2)pair of electrical power system normal work carries on the prompt.Responded the electrical equipment the normal work situation, (whether there is and different e.g. frequent attendant) does send out the signal according to the normal work situation and the equipment movement maintenance condition, in order to the attendant carries on processing, either carries on the adjustment automatically by the equipment, either continues these to move can cause the accident electrical equipment to excise.Response normal work situation relay protection installment permission belt certain time-lag action.(3) pair of electrical power system movement carries on the monitoring.The relay protection is not merely an accident processing and the response installment, simultaneously also is monitors the electrical power system normal operation the installment.The relay protection is the electrical power system safe normal operation important safeguard, at present oneself after obtained the widespread application, along with the science and technology unceasing progress, the relay protection technology presents day by day to the microcomputer, the network, the intellectualization, protects, the control, the survey and the data communication integration development tendency.110KV供电系统继电保护作用浅析电力系统的安全性和可靠性不仅关系到电力系统本身的运行,同样关系到送电范围内的厂矿、企业、居民能否正常用电。
电力系统继电保护外文及翻译编辑整理:尊敬的读者朋友们:这里是精品文档编辑中心,本文档内容是由我和我的同事精心编辑整理后发布的,发布之前我们对文中内容进行仔细校对,但是难免会有疏漏的地方,但是任然希望(电力系统继电保护外文及翻译)的内容能够给您的工作和学习带来便利。
同时也真诚的希望收到您的建议和反馈,这将是我们进步的源泉,前进的动力。
本文可编辑可修改,如果觉得对您有帮助请收藏以便随时查阅,最后祝您生活愉快业绩进步,以下为电力系统继电保护外文及翻译的全部内容。
Power System ProtectionsThe steady—state operation of a power system is frequently disturbed by various faults on electrical equipment. To maintain the proper operation ofthe power system, an effective, efficient and reliable protection scheme is required。
Power system components are designed to operate under normal operating conditions。
However, due to any reason, say a fault, there is an abnormality, it is necessary that there should be a device which senses these abnormal conditions and if so, the element or component where such an abnormality has taken place is removed, i。
电力系统继电保护外文及翻译Power System ProtectionsThe steady-state operation of a power system is frequently disturbed by various faults on electrical equipment. To maintain the proper operation of the power system, an effective, efficient and reliable protection scheme is required. Power system components are designed to operate under normal operating conditions.However, due to any reason, say a fault, there is an abnormality, it is necessary that there should be a device which senses these abnormal conditions and if so, the element or component where such an abnormality has taken place is removed, i.e. deleted from the rest of the system as soon as possible. This is necessary because the power system component can never be designed to withstand the worst possible conditions due to the fact that this will make the whole system highly uneconomical. And therefore, if such an abnormality takes place in any element or component of the power system network, it is desirable that the affected element/component is removed from the rest of the system reliably and quickly in order to restore power in the remaining system under the normal condition as soon as possible.The protection scheme includes both the protective relays and switching circuits, i.e. circuit breakers. The protective relay which functions as a brain is a very important component. The protective relay is a sensing device, which senses the fault, determines its location and then sends command to the proper circuit breaker by closing its trip coil. The circuit breaker after getting command from the protective relay disconnects only the faulted element. this is why the protective relay must be reliable, maintainable and fast in operation.In early days, there used to be electromechanical relay of induction disk-type.However, very soon the disk was replaced by inverted cup, i.e.hollow cylinder and the new relay obtained was known as an induction cup or induction cylinder relay. This relay, which is still in use, possesses several important features such as higher speed; higher torque for a given power input an more uniform torque.However, with the advent of electronic tubes, electronic relays having distinct features were developed during 1940s. With the discovery of solid state components during 1950s, static relays with numerous advantages were developed. The use of digital computers for protective relaying purposes has been engaging the attention of research and practicing engineers since layer 1960s and 1980s. Now, the microprocessor/mini computer-based relaying scheme, because of its numerous advantages such as self –checking feature and flexibility, has been widely used in power system all over the world.The overall system protection is divided into following sections: (i)Generator protection,(ii)Transformer protection,(iii)Bus protection,(iv)Feederprotection,(v)Transmission line protection.Basic Requirements to Protective RelaysAny protection scheme, which i.e. required to safeguard the power system components against abnormal conditions such as faults, consists basically of two elements(i)Protective relay and (ii) Circuit breaker .The protective relay which is primarily the brain behind the whole scheme plays a very important role. Therefore proper care should be taken in selecting an appropriate protective relay which is reliable, efficient and fast in operation. The protective relay must satisfy the following requirements:⑴ since faults on a well designed and healthy system are normally rare, therelays are called upon to operate only occasionally. This means that therelaying scheme is normally idle and must operate whenever fault occurs. Inother words, it must be reliable.⑵ Since the reliability partly depends upon the maintenance, the relay mustbe easily maintainable.⑶ The palpation of the relay can be in two ways. One is the failure to operatein case a fault occurs an second is the relay operation when there is no fault.As a matter of fact, relay must operate if there is a fault and must notoperate if there is no fault.⑷Relaying scheme must be sensitive enough to distinguish between normaland the faulty system.Protective RelaysThe function of the protective relay is to sense the fault and energize the tripcoil of the circuit breaker. The following types of the protective relays are usedfor the apparatus such as synchronous machines, bus bar, transformer and theother apparatus and transmission line protection.(1) Over current relays,(2) Under voltage relays,(3) Under frequency relays,(4) Directional relays,(5) Thermal relays,(6) Phase sequence relays such as(i)negative sequence relays and, (ii)zerosequence relays,(7) Differential relays and percentage differential relays,(8) Distance relays such as (I)plane impedance relays,(ii)angle impedance relay,i.e. Ohm or reactance relays,(iii)angle admittance relays,i.e. Mho relaysand ,(iv)offset and restricted relays,(9)Pilot relays such as (i) wire pilot relays,(ii)carrier channel pilotrelays,(iii)microwave pilot relays. There are different types of the relayingscheme based on construction. They are:(i)electromechanicaltype,(ii)thermal relays,(iii) transduction relays,(iv)rectifier bridgerelay,(v)electronic relays,(vi)digital relaying schemes.电力系统继电保护电力系统的稳态运行经常会因各种电力设备配故障原因而被扰乱。
浅谈110kV变电站继电保护的应用作者:张本鑫古户强来源:《中国新技术新产品》2016年第04期摘要:变电站是电力系统中对电能的电压和电流进行变换的场所,而变电站运行过程中,为了确保电力系统运行安全,需要采用一些继电保护装置来确保变电站输配电线路安全。
本文就110kV变电站的继电保护应用进行了相关的分析。
关键词:变电站;继电保护;应用中图分类号:TM77 文献标识码:A随着我国现代社会的进步与发展,高压线路架设的数量也越来越多,对线路运行安全也越来越高。
变电站作为电压转变的地方,变电站运行安全与否直接关系到了电力系统的安全运行。
为了保证电力系统运行安全,在系统中应用继电保护有着重大意义。
1 110kV变电站继电保护的意义在我国社会发展的过程中,电力有着巨大的作用,没有电,社会就得不到正常发展,社会生活以及社会生产就不能正常进行。
近年来,我国社会用电需求越来越大,加大变电站的继电保护既是我国现代社会发展的内在要求,同时也是我国电力事业发展的内在要求。
然而伴随着电力规模的扩大,电力运行安全问题也日益突出,在电力系统中,电气设备的增加会加大电力运行负荷,再加上一些外力因素的影响,使得电力系统出现安全问题,进而影响到我国社会的可持续发展。
基于电力在社会中发展中的重要性,在电力系统中,继电保护技术是电力系统能否正常运行的关键。
随着社会的进步以及经济的发展,高压线路也不断增多,给电力系统的运行造成了巨大的威胁,一旦电力系统出现安全隐患,不仅会威胁到供配电的正常供应,同时还会威胁到人民的生命财产安全。
继电保护作为电力系统安全运行的重要保障,加大继电保护的运行有着巨大意义。
继电保护可以保证电力系统的正常运转,当电力系统出现故障时,能有自动保护电力系统的正常运行,减少故障带来的损失,进而为电力企业带来经济效益和社会效益。
2 110kV变电站的继电保护2.1 变压器的继电保护在110kV变电站运行中,变压器的作用就是将一种登记的电压变换成同频率的另一种等级的电压是变电站中的中心设备。
毕业设计(论文) 外文翻译外文题目: Protection Relay 中文题目:继电保护学院名称:电子与信息工程学院专业:电气工程及其自动化班级:电气082继电保护摘要:继电保护非常重要,因为大部分的用户,是从分布线和分配制度以来,比任何其他部分的系统更容易受到破坏。
回顾我国电力系统继保护技术发展的过程中,概述了微机继电保护技术的成就,提出了未来继电保护技术发展趋势将是:计算机化,电网络化,保护,控制,调查结果显示,数据通信一体化和人工智能化。
关键词:继电保护,继电保护现状发展,继电保护的未来发展一、继电保护原理及现状电力系统的迅速发展对继电保护不断提出新的要求,电子技术,计算机技术的快速发展不断为继电保护技术的发展注入新的活力,因此,继电保护技术是有利的,在40多年的时间里已完成发展了4个历史阶段。
建国后,我国继电保护学科、继电保护设计、继电器制造工业和继电保护技术队伍从无到有,在大约10年的时间里走过了先进国家半个世纪走过的道路。
50年代,我国工程技术人员创造性地吸收、消化、掌握了国外先进的继电保护设备性能和运行技术,建成了一支具有深厚继电保护理论造诣和丰富运行经验的继电保护技术队伍,对全国继电保护技术队伍的建立和成长起了指导作用。
阿城继电器厂引进消化了当时国外先进的继电器制造技术,建立了我国自己的继电器制造业。
因而在60年代中我国已建成了继电保护研究、设计、制造、运行和教学的完整体系。
这是机电式继电保护繁荣的时代,为我国继电保护技术的发展奠定了坚实基础。
自50年代末,晶体管继电保护已在开始研究。
60年代中到80年代中是晶体管继电保护蓬勃发展和广泛采用的时代。
其中天津大学与南京电力自动化设备厂合作研究的500kv晶体管方向高频保护和南京电力自动化研究院研制的晶体管高频闭锁距离保护,运行于葛洲坝50 0 kv线路上,结束了500kv线路保护完全依靠从国外进口的时代。
在此期间,从70年代中,基于集成运算放大器的集成电路保护已开始研究。
Fundamentals of protection practiceThe purpose of an electrical power system is to generate and supply electrical energy to consumers. The system should be designed and managed to deliver this energy to the utilization points with both reliability and economy. As these two requirements are largely opposed, it is instructive to look at the reliability of a system and its cost and value to the consumer.One hand ,The diagram mast make sure the reliability in system design,. On the other hand, high reliability should not be pursued as an end in itself, regardless of cost, but should rather be balanced against economy,taking.Security of supply can be bettered by improving plant design, increasing the spare capacity margin and arranging alternative circuits to supply loads. Sub-division of the system into zones. each controlled by switchgear in association with protective gear. provides flexibility during normal operation and ensures a minimum of dislocation following a breakdown.The greatest threat to the security of a supply system is the short circuit,which imposes a sudden and sometimes violent change on system operation. The large current which then flows, accompanied by the localized release of a considerable quantity of energy, can cause fire at the fault location, and mechanical damage throughout the system, particularly to machine and transformer windings. Rapid isolation of the fault by the nearest switchgear will minimize the damage and disruption caused to the system.A power system represents a very large capital investment. To maximize the return on this outlay. the system must be loaded as much as possible. For this reason it is necessary not only to provide a supply of energy which is attractive to prospective users by operating the system ,but also to keep the system in full operation as far as possible continuously, so that it may give the best service to the consumer, and earn the most revenue for the supply authority. Absolute freedom from failure of the plant and system network cannot be guaran- teed. The risk of a fault occurring, however slight for each item, is multiplied by the number of such items which are closely associated in an extensive system, as any fault produces repercussions throughout the network. When the system is large, the chance of a fault occurring and the disturbance that a fault would bring are both so great that withoutequipment to remove faults the system will become, in practical terms, inoperable. The object of the system will be defeated if adequate provision for fault clearance is not made. Nor is the installation of switchgear alone sufficient; discriminative protective gear, designed according to the characteristics and requirements of the power system. must be provided to control the switchgear. A system is not properly designed and managed if it is not adequately protected.Protective gearThis is a collective term which covers all the equipment used for detecting,locating and initiating the removal of a fault from the power system. Relays are extensively used for major protective functions, but the term also covers direct-acting a.c.trips and fuses.In addition to relays the term includes all accessories such as current and voltage transformers, shunts, d.c.and a.c. wiring and any other devices relating to the protective relays.In general, the main switchgear, although fundamentally protective in its function, is excluded from the term protective gear, as are also common services, such as the station battery and any other equipment required to secure opera- tion of the circuit breaker. ReliablityThe performance of the protection applied to large power systems is frequently assessed numerically. For this purpose each system fault is classed as an incident and those which are cleared by the tripping of the correct circuit breakers and only those, are classed as 'correct'. The percentage of correct clearances can then be determined.This principle of assessment gives an accurate evaluation of the protection of the system as a whole, but it is severe in its judgement of relay performance, in that many relays are called into operation for each system fault, and all must behave correctly for a correct clearance to be recorded. On this basis, a performance of 94% is obtainable by standard techniques.Complete reliability is unlikely ever to be achieved by further improvements in construction. A very big step, however, can be taken by providing duplication of equipment or 'redundancy'. Two complete sets of equipment are provided, and arranged so that either by itself can carry out the required function. If the risk of an equipment failing is x/unit. the resultant risk, allowing for redundancy, is x2. Where x is small the resultant risk (x2) maybe negligible.It has long been the practice to apply duplicate protective systems to busbars, both being required to operate to complete a tripping operation, that is, a 'two-out-of-two' arrangement. In other cases, important circuits have been provided with duplicate main protection schemes, either being able to trip independently, that is, a 'one-out-of- two' arrangement. The former arrangement guards against unwanted operation, the latter against failure to operate.These two features can be obtained together by adopting a 'two-out-of-three' arrangement in which three basic systems are used and are interconnected so that the operation of any two will complete the tripping function. Such schemes have already been used to a limited extent and application of the principle will undoubtedly increase. Probability theory suggests that if a power network were protected throughout on this basis, a protection performance of 99.98% should be attainable. This performance figure requires that the separate protection systems be completely independent; any common factors, such as common current transformers or tripping batteries, will reduce the overall performance. SELECTIVITYProtection is arranged in zones, which should cover the power system completely, leaving no part unprotected. When a fault occurs the protection is required to select and trip only the neareat circuit breakers. This property of selective tripping is also called 'discrimination' and is achieved by two general methods:a Time graded systemsProtective systems in successive zones are arranged to operate in times which are graded through the sequence of equipments so that upon the occurrence of a fault, although a number of protective equipments respond, only those relevant to the faulty zone complete the tripping functiopn. The others make incomplete operations and then reset.b Unit systemsIt is possible to design protective systems which respond only to fault conditions lying within a clearly defined zone. This 'unit protection' or 'restricted protection' can be applied throughout a power system and, since it does not involve time grading, can be relatively fast in operation.Unit protection is usually achieved by means of a comparison of quantities at theboundaries of the zone. Certain protective systems derive their 'restricted' property from the configuration of the power system and may also be classed as unit protection. Whichever method is used, it must be kept in mind that selectivity is not merely a matter of relay design. It also depends on the correct co-ordination of current transformers and relays with a suitable choice of relay settings, taking into account the possible range of such variables as fault currents. maximum load current, system impedances and other related factors, where appropriate.STABILITYThis term, applied to protection as distinct from power networks, refers to the ability of the system to remain inert to all load conditions and faults external to the relevant zone. It is essentially a term which is applicable to unit systems; the term 'discrimination' is the equivalent expression applicable to non-unit systems.SPEEDThe function of automatic protection is to isolate faults from the power system in a very much shorter time than could be achieved manually, even with a great deal of personal supervision. The object is to safeguard continuity of supply by removing each disturbance before it leads to widespread loss of synchronism, which would necessitate the shutting down of plant.Loading the system produces phase displacements between the voltages at different points and therefore increases the probability that synchronism will be lost when the system is disturbed by a fault. The shorter the time a fault is allowed to remain in the system, the greater can be the loading of the system. Figure 1.5 shows typical relations between system loading and fault clearance times for various types of fault. It will be noted that phase faults have a more marked effect on the stability of the system than does a simple earth fault and therefore require faster clearance.SENSITIVITYSensitivity is a term frequently used when referring to the minimum operating current of a complete protective system. A protective system is said to be sensitive if the primary operating current is low.When the term is applied to an individual relay, it does not reter to a current or voltage setting but to the volt-ampere consumption at the minimum operating current.A given type of relay element can usually be wound for a wide range of setting currents; the coil will have an impedance which is inversely proportional to the square of the setting current value, so that the volt-ampere product at any setting is constant. This is the true measure of the input requirements of the relay, and so also of the sensitivity. Relay power factor has some significance in the matter of transient performance .For d.c. relays the VA input also represents power consumption, and the burden is therefore frequently quoted in watts.PRIMARY AND BACK-UP PROTECTIONThe reliability of a power system has been discussed in earlier sections. Many factors may cause protection failure and there is always some possibility of a circuit breaker failure. For this reason, it is usual to supplement primary protection with other systems to 'back-up' the operation of the main system and to minimize the possibility of failure to clear a fault from the system.Back-up protection may be obtained automatically as an inherent feature of the main protection scheme, or separately by means of additional equipment. Time graded schemes such as overcurrent or distance protection schemes are examples of those providing inherent back-up protection; the faulty section is normally isolated discriminatively by the time grading, but if the appropriate relay fails or the circuit breaker fails to trip, the next relay in the grading sequence will complete its operation and trip the associated circuit breaker, thereby interrupting the fault circuit one section further back. In this way complete back- up cover is obtained; one more section is isolated than is desirable but this is inevitable in the event of the failure of circuit breaker. Where the system interconnection is more complex, the above operation will be repeated so that all parallel infeeds are tripped. If the power system is protected mainly by unit schemes, automatic back-up protection is not obtained, and it is then normal to supplement the main protection with time graded overcurrent protection, which will provide local back-up cover if the main protective relays have failed, and will trip further back in the event of circuit breaker failure.Such back-up protection is inherently slower than the main protection and, depending on the power system con- figuration, may be less discriminative. For the most important circuits the performance may not be good enouugh, even as a back-up protection, or, in some cases, not even possible, owing to the effect of multiple infeeds. In these casesduplicate high speed protective systems may be installed. These provide excellent mutual back-up cover against failure of the protective equipment, but either no remote back-up protection against circuit breaker failure or, at best, time delayed cover.Breaker fail protection can be obtained by checkina that fault current ceases within a brief time interval from the operation of the main protection. If this does not occur, all other connections to the busbar section are interrupted, the condition being necessarily treated as a busdar fault. This provides the required back-up protection with the minimum of time delay, and confines the tripping operation to the one station, as compared with the alternative of tripping the remote ends of all the relevant circults.The extent and type of back-up protection which is applied will naturally be related to the failure risks and relative economic importance of the system. For distribution systems where fault clearance times are not critical, time delayed remote back-up protection is adequate but for EHV systems, where system stability is at risk unless a fault is cleared quickly, local back-up, as described above, should be chosen.Ideal back-up protection would be completely indepen_ dent of the main protection. Current transformers, voltage transformers, auxiliary tripping relays, trip coils and d.c. supplies would be duplicated. This ideal is rarely attained in practice. The following compromises are typical:a. Separate current transformers (cores and secondary windings only) are used for each protective system, as this involves little extra cost or accommodation compared with the use of common current transformers which would have to be larger because of the combined burden.b. Common voltage transformers are used because duplication would involve a considerable increase in cost, because of the voltage transformers themselves, and also because of the increased accommodation which would have to be provided. Since security of the VT output is vital, it is desirable that the supply to each protection should be separately fused and also continuously supervised by a relay which wil1 give an alarm on failure of the supply and, where appropriate, prevent an unwanted operation of the protection.c. Trip supplies to the two protections should be separately fused. Duplication of tripping batteries and of tripplng coils on circuit breakers is sometimes provided. Trip circuitsshould be continuously supervised.d. It is desirable that the main and back-up protections (or duplicate main protections) should operate on different princlples, so that unusual events that may cause failure of the one will be less likely to affect the other./viewforum.php?f=20继电保护原理发电并将电力供应给用户这就是电力系统的作用。
变电站中英文资料对照外文翻译文献综述XXXns are an essential part of electrical power systems。
servingas the interface een high-voltage n lines and lower-voltage n lines。
They play a critical role in XXX homes。
businesses。
and industries.Types of nsThere are several types of ns。
including n ns。
n ns。
and customer XXX to the end-users and step down the voltage for n to XXX a single customer or group of customers.XXXns consist of us components。
including transformers。
circuit breakers。
switches。
XXX are used to step up or step down thevoltage of the electricity。
XXX are used to control the flow ofXXX to the system.XXXXXX stages。
including site n。
layout design。
equipment n。
XXX n lines。
land availability。
and environmental ns。
The layout design involves determining the placement of equipment。
XXX appropriate transformers。
circuit breakers。
and other components。
关于110kV变电站继电保护要点分析摘要:继电保护技术在110kV变电站中发挥着重要的作用,是电力变电站运行管理中不可或缺的一部分。
我们对变电站的设备的相关影响因素进行分析,了解110kV变电站继电保护技术的实施要点,能够保证电力供应的正常运行,为变电站的正常运行提供一个相对稳定的环境,从而为社会和用户提供更安全的用电服务,加强社会经济的进一步发展。
鉴于此,本文主要分析110kV变电站继电保护要点。
关键词:110kV;变电站;继电保护1、继电保护的作用一旦电力系统出现突发性故障,继电保护装置就会及时作出自动的报警和反事故应对措施,可以有效地阻止电力系统的故障和相关问题出现,从而避免电力系统事故问题进一步扩大,充分发挥保护其他电力元器件的重要作用。
从总体角度分析,对故障和问题进行及时发现和故障阻止是继电保护所发挥的重要作用,同时也是具体采用的操作方法。
继电保护装置不仅仅可以有效防止事故问题的出现,还可以及时进行电力故障报警,提醒继电保护和运维人员及时进行故障处理。
继电保护装置能反映电力系统的工作是否正常,可以根据所保护的元件的工作情况,以信号的形式发出,去向相关工作人员反映,以便工作人员进行处理。
也可以让继电保护装置进行自动化处理,将那些继续运行可能会发生故障的元件继续隔离开来。
继电保护可以确保110kV变电站的安全性和可靠性。
2、110kV变电站继电保护要点分析2.1、继电保护技术在110kV变电站中的具体应用继保装置包括开入单元,出口单元,接收单元和中央处理器四个部分,通过对这几个部分的控制就能够实现对110kV变电站的一次设备保护。
110kV变电站的继电保护技术主要是利用电子互感器装置来完成对整个电网系统的控制,如果发现电网系统中出现故障,继电保护装置会立即发现发生故障的元件,并对此元件进行自动隔离,使元件的受损程度降到最小范围。
继电保护技术是通过数据信号来完成与电子互感器信息传输。
在对110kV变电站进行检测时,电子互感器首先检测出相关的数据信号,并利用光纤线路对检测出的数据进行传输到110kV变电站的保护测控装置处,继电保护装置对这些数据进行接收和处理,信息的传输过程中就可以直接了解到变电站的具体运行情况。
电力系统继电保护(英文简介) xx年xx月xx日contents •继电保护基本概念与原理•电力系统继电保护组成与功能•电力系统继电保护技术•电力系统继电保护发展历程与趋势•电力系统继电保护的未来挑战与对策目录01继电保护基本概念与原理继电保护是电力系统中的一种自动装置,用于检测和切除电力系统中的故障或异常运行,以防止系统稳定破坏和设备损坏,从而保证电力系统的安全稳定运行。
继电保护定义根据保护原理和应用范围,继电保护可分为输电线保护、变压器保护、发电机保护、母线保护、电动机保护等。
继电保护分类继电保护基本定义与分类反应原理继电保护装置通过检测电力系统中的电流、电压、频率等参数的变化来判断系统是否出现故障或异常,当这些参数超过预定范围时,继电保护装置会发出报警信号或切除故障部分。
工作原理继电保护装置一般由测量部分、逻辑部分和执行部分组成。
测量部分负责检测电力系统的参数变化,逻辑部分根据测量部分的输出进行逻辑判断,并发出相应的动作信号,执行部分则根据信号切除故障或异常部分。
继电保护工作原理继电保护装置可以快速检测和切除系统中的故障或异常运行,防止系统稳定破坏和设备损坏,保障电力系统的安全稳定运行。
保障电力系统的安全稳定运行继电保护装置可以有效地提高电力系统的可靠性,因为它可以在系统出现故障或异常时,自动地隔离故障部分,保证非故障部分的正常运行,避免因系统故障而引起的停电等影响。
提高电力系统的可靠性继电保护的重要性02电力系统继电保护组成与功能用于检测电力系统中的故障或异常状态,并转化为数字或逻辑信号。
继电保护装置的组成测量元件根据测量元件提供的信号,按照一定的逻辑关系判断是否发生故障,并输出相应的指令。
逻辑元件接收到逻辑元件的指令后,快速切除故障部分,保证非故障部分的正常运行。
执行元件各类继电保护的功能当电流超过预定值时,自动断开电源以防止设备损坏和故障扩大。
过电流保护电流速断保护方向保护差动保护当电流超过预定值时,立即断开电源以防止故障扩大。
110kV变电所的继电保护应用110kV变电所的继电保护应用摘要:自人类进入“电气时代〞之后,电作为一种高效的能源倍受青睐。
在近些年的表现尤为突出,在国内外电力系统迅猛开展的同时,变电所所面临的继电保护应用的问题也变得有些严峻,文章将就110kV变电所的继电保护应用作一些阐述说明。
关键词:110kV;变电所;继电保护应用供电系统在对设备或者大型的系统进行电力输出时,意外或者故障性的出现供电故障是不可防止的。
因此,必须在供电系统出现故障的时候及时有效的断开电力系统,防止二次伤害,参加继电保护系统是十分有必要的。
1 继电保护系统应用的根底保护任务在正常运转的被保护系统用电单位出现突发性用电故障时,继电保护系统能够准确判断出现故障的单位,而且能在极短的时间内迅速找到并切断本用电单位的有效供电闸门。
与此同时,尽量不影响其他被保护单位,发生故障的单位做到完全隔离,这样的继电保护单位既要将生命财产的平安放在第一位,也能够尽量减少损失。
而且,继电保护系统时与用电系统联系在一起的,因此,减少其对供电系统的影响也是不得不考虑的,同时,还能够满足某些特定要求。
当然,被保护的用电单位发生故障并不一定就是同一种情况,因此,继电保护系统还需要判断出不同的故障情况转变为不同的故障信号给工作人员或者本身的控制系统,以对不同的故障做出及时有效的处理。
从上面所述来看,继电保护系统必须具备及时准确有效的特点。
2 继电保护应用之变压器保护2.1 接地保护在国内目前110kV变电所主要使用的继电保护设备中性接地系统的保护机构中,正常情况下与零序电流保护协同工作,在被保护的用电设备发生故障时,接地系统在将局部电流接入地下的同时,回把故障信号反响给电闸控制系统或者立即跳闸。
2.2 过负荷保护在三相供电系统中的继电保护最常用的就是过负荷保护,因为三相电在大多数情况下都是兑成的,因此继电保护装置可以把过负荷保护器安装在其中的一相电流上,通过确定时间的延迟来反映供电系统的运行情况,这样可以自行处理简单的额用电故障。
论述风力发电场110kV升压站继电保护分析风力发电是一种环保、可再生的能源,具有取之不尽、用之不竭的优点,因此在全球范围内得到了广泛的发展和应用。
风力发电场的建设离不开高压输电线路和变电站的支持,其中110kV升压站作为风力发电场的重要组成部分,起着将风电场产生的电能升压输送到主网的功能。
而在升压站的运行中,继电保护是保障系统安全和稳定运行的重要技术手段。
一、继电保护的作用和意义继电保护是电力系统中的一项重要技术,其主要作用是在系统发生故障时,通过快速而准确的动作来隔离故障,避免故障扩大,保护电力设备和人身财产的安全。
在风力发电场110kV升压站中,继电保护系统的作用主要体现在以下几个方面:保护设备:继电保护系统可以通过对设备的电压、电流、频率等参数进行监测和分析,一旦发现设备存在故障,可以快速做出动作,保护设备免受损坏。
保护系统:继电保护系统能够对电力系统的各个部分进行监控和保护,一旦出现故障,可以迅速隔离故障点,避免故障对系统的进一步影响。
提高系统安全性:继电保护系统的准确、可靠的动作可以有效提高系统的安全性,保障系统的稳定运行。
减少故障损失:通过对系统进行有效的保护和隔离,可以减少故障对系统的损失,提高电网的可靠性。
继电保护系统的作用和意义在风力发电场110kV升压站中尤为重要,其良好的性能和可靠的动作对保障电网的安全运行起着至关重要的作用。
1. 过流保护过流保护是继电保护系统中最基本的一种保护方式。
在风力发电场110kV升压站中,过流保护可以通过对电流进行监测和分析,一旦发现电流超过设定值,就能够迅速进行动作,实现对系统的及时保护。
其主要应用场景包括短路故障和负荷故障,能够有效地保护设备和系统的安全运行。
风力发电场110kV升压站涉及的风力发电系统具有一定的波动性,因此系统频率的稳定性对于系统的安全运行至关重要。
通过过频保护,可以对系统频率进行监测和分析,一旦发现频率超出设定范围,就能够迅速进行动作,保障系统频率的稳定运行。
浅析110kV电力系统的继电保护随着经济的快速发展,我国的电力事业取得了非常显著地成就。
电力是国家发展立足的根本,是人们生活的保障,是国防的必须条件,因此我们必须要将电力事业发展好。
文章就是基于目前的这种状况,具体的分析了当前我国110kV 电力系统的继电保护,目的是为了更好地促进我国朝着国际化方向迈进。
标签:110kV;继电保护;电力系统1 概述由于电力行业高速前进,整个体系的传输量不断的变大,而且电压的级别也开始变高,体系对于机电保护的精准性等有了非常高的规定。
继电保护在整个电力体系中起到非常关键的作用。
其运作是不是安稳等,使用者的用电规定是不是能够确保,而且关乎到整个体系的运作是不是良好。
电力系统由发电、变电、输电、配电和用电等五个环节组成。
所有种类的电气装置有机的融合起来,因为其覆盖范围非常的广,而且运作氛围繁琐,同时又由于多项要素的干扰,电气生产问题就很容易发生了。
电力体系的各项活动是在同一时间中开展的,所有出现的不利现象的话,都会对整个体系的运作带来非常多的负面效益。
因为该体系涵盖一次体系以及二次体系。
同时因为一次的非常的单一,而且便于查看,在分析以及布局上非常的方便。
然而二次的就比较的繁琐了,而且它还涵盖非常多的继电装置等。
所谓继电保护装置就是在供电系统中用来对一次系统进行监视、测量、控制和保护,由继电器来组成的一套专门的自动装置。
要想保证该体系的运作顺利,就应该设置该项装置。
2 体系的继电保护装置2.1 其布局规定2.1.1 110kV线路应配置的继电保护通常来讲,其要设置过电流措施。
如果该时间能够控制在0.7s之内的话,并没有保护配合上的要求时,可不装设电流速断保护;自重要的变配电所引出的线路应装设瞬时电流速断保护。
2.1.2 配电变压器应配置的继电保护(1)当配电变压器容量小于400kV A 时:一般采用高压熔断器保护;(2)当配电变压器容量为400~630kV A,高压侧采用断路器时,应装设过电流保护,而当过流保护时限大于0.5s 时,还应装设电流速断保护;(3)当配电变压器容量为800kV A 及以上时,应装设过电流保护。
基于110千伏电力系统继电保护技术分析摘要随着我国经济的持续发展,电力负荷增长幅度较大,传输电压越来越高,因此电力系统对于继电保护的可靠性提出了更高的要求。
为了确保110kV 电力系统的正常运行,必须对二次电力系统的继电保护装置进行正确的设计,监测保护一次电力系统,提高110kV电力系统的故障及保护设计水平。
本文就110KV电力系统继电保护技术方面进行分析。
关键词110kV电力系统;继电保护;二次电力系统1 引言随着我国经济的快速发展,为了避免电力传输损耗,110kV电力系统中存在大量的不同功能电力设备,电力系统容易发生不同的电气故障,影响电力系统的正常运行,因此,继电保护技术对于110kV电力系统的安全可靠运行具有重要的现实意义[1]。
2 继电保护系统应用分析在正常运转的被保护系统用电单位出现突发性用电故障时,继电保护系统能够准确判断出现故障的单位,在极短的时间内迅速找到并切断本用电单位的有效供电闸门。
与此同时,尽量不影响其他被保护单位,发生故障的单位做到完全隔离,尽量减少生命财产的安全损失。
且继电保护系统时与用电系统联系在一起的,因此,减少其对供电系统的影响能满足某些特定要求[2]。
3 有关继电保护技术分析继电保护技术可以有效保证110kV电力系统安全可靠地运行,当110kV电力系统因为短路等故障处于不正常工作状态时,继电保护装置能及时诊断故障并向控制器发出故障信号,控制系统及时对电力系统相关故障区域进行处理,以保障非故障区域正常工作。
在110kV电力系统中,继电保护技术主要通过以下两种方式进行系统保护:快速实现电力系统的电压调节,保证供电电压稳定,使得终端系统的电力供应不受影响;通过继电保护装置快速切除电力系统故障区域,减轻由于故障对用电设备的影响,保证重合闸的快速完成。
因此电力系统对继电保护技术存在一定的技术要求。
继电保护速动性要求保护系统能够快速对故障反应,快速实现故障切除;继电保护可靠性要求保护系统能可靠工作,提高电力系统的可靠性;继电保护选择性要求保护系统首先对自身保护区域实现可靠的故障反应,不跨区域发生误动问题[3]。