当前位置:文档之家› 热敏电阻式室内火灾报警系统应用开发

热敏电阻式室内火灾报警系统应用开发

热敏电阻式室内火灾报警系统应用开发
热敏电阻式室内火灾报警系统应用开发

热敏电阻式室内火灾报警系统应用开发

摘要:本设计基于单片机STC89C52的数字式室内温度控制系统设计,控制程序主要包括主程序、读出温度子程序、按键子程序、控制风机子程序等。通过按钮在实测温度和预设温度之间相互显示,当实测温度达到预设温度上限时报警,同时启动风机,和相应的防火灭火装置。该系统能准确而及时的发现火灾隐患,确保生命和财产的安全。

关键词:单片机,热敏传感器,室内温度监控,数码管,火灾报警。

Thermistor indoor fire alarm system

application development

Abstract: The design is based on single-chip digital STC89C52 indoor temperature control system design, control program includes the main program, subroutines temperature readout, key subroutines, fan control subroutines. Buttons to display each other between the measured temperature and the preset temperature, when the measured temperature reaches the preset temperature limit alarm, start the fan, and the corresponding fire extinguishing devices. The system can accurately and timely discovery of fire hazards, ensure the safety of life and property.

Keywords: SCM, thermal sensors, indoor temperature monitoring, digital control, fire alarm.

1:引言

能够及时而准确的感应出室内是否发生火灾隐患,降低其它正常因素对报警器的影响。现代的许多公共场合都装有火灾报警器,而大部分报警器在某些情况下都会判断失误引起不必要的麻烦,例如室内吸烟等。因此就需要能够正确识别火灾信号火灾报警器

2平台硬件组成

平台的硬件架构如图1所示:

图1 平台硬件构架

硬件由四部分组成,有单片机及其外围电路、LED数码管显示部分、键盘部分以及温度传感器部分。单片机及其外围电路由11.0592MHZ

晶振加上两个30pf的瓷片电容接地;单片机的复位端经电阻下拉接地,然后按钮和电解电容并联接电源;同时P0口接10K排阻上拉LED显示模块这里可以选择1602或12864的液晶显示屏,同时也可以选择使用数码管,考虑到自己操作的方便所以

这里选择用数码管来显示。

按键设计模块,考虑到实验板上有四个按钮,分别接单片机P32、P33、P34、P35端口,而且这里的P33已经同DS18B20的数据DQ端连接上了,所以这里只用剩余的三个按钮。

温度传感器模块→感温型火灾报警器

由于火灾发生时燃烧会产生大量的热量,使得周围温度快速的变高。温度传感器将周围环境温度的变化转换成电信号,处理器通过判断电信号的大小来判断是否发生了火灾,如果发生了火灾就会报警。一般分为定温型(温度达到一定值报警)和温差型(升温幅度达到一定值报警)。一般来说定温型容易受到外界其他因素的干扰,温差型相对抗干扰能力比较强。本设计使用的温度传感器是DS18B20数字温度传感器。它的为测温范围-55℃~+125℃,特别值得注意的是其有0.5℃的固有测温误差,测量误差还是很大的,但作为火灾报警器来说并不要求太高的精度。这种传感器具有价格低廉,体积小,结实耐用等优点,特别是DS18B20

在与单片机连接时不需要任何外围部件,只要要一条线即可实现单片机与DS18B20的连接,使用十分简单,因此在单片机系统中的使用十分广泛。DS18B20有三只引脚,GND,DQ,和VDD。封装后的结构图如图3-7所示。

图3-7 DS18B20数字温度传感器

DS18B20的三个引脚功能如表4所示,其中GND引脚接地,VDD为可选的±5V引脚,在实际中一般接VCC,DQ引脚也就是数据输出引脚可以直接和单片机连接。具体结构仿真如图3-8。

表4 DS18B20详细引脚功能描述

图3-8 DS18B20模块结构图

报警装置使用一个能发出声音的简单元件就行了。考虑到直接能够与所选用的单片机能够兼容,所以选用直流5V的蜂鸣器。

风机:风机用来控制温度,若温度高了,就打开风机,如果温度低了,就关闭风机。

3报警系统分析软件设计

3.1 LED数码管显示

实验板上共有五个数码管,这里使用实验板上的后四个数码管,前三个显示温度值(其中个位显示带小数点),最后一个数码管显示温度符号“℃”[8]。LED显示程序流程图如图9所示:

图9 LED显示流程图

3.2按键设计程序

三个按键,一个功能按键,一个增温按键,一个减温按键,功能按钮选择是显示预测温度还是预设温度。按键设计程

图10 按键设计程序流程图

3.3 DS18B20程序

DS18B20程序流程图如图12所示:

图12 DS18B20程序流程图

3.4 继电器及风机控制

风机控制路程图如图13所示:

图13 风机控制路程图

3.5蜂鸣器程序设计

当实际温度达到预设温度的上限的时候就报警,其报警流程图如图14:

图14 报警流程图

系统调试

硬件这里所用的是单片机实验板,接上电源线然后接上串口线,上电后烧写一个.HEX 文件进入单片机,测试单片机能否烧写正常。接上DS18B20,然后烧入写好的程序,如果能够达到如下的结果[10]:

烧写程序之后就显示当前环境下的温度,通过按钮K1,调节预设温度与环境温度显示之间的调换,此按钮可以在实测温度与预设温度之间的调换。显示实测温度时加温减温按钮不能用,当调到预设温度时,显示的是预测温度(初始化时为25℃),这时调节加温减温按钮可以调节预设温度。当实际温度达到预设值时,报警器报警。当达到这些效果时,就证明了调试成功。

4:结束语

火灾报警器可以保障人们生产与生活的安全,可以及早发现火灾和预防易燃易爆气体爆炸事故发生,因此其具有很好的实用性。本文设计的火灾自动报警系统采用了温度传感器DS18B20相比一般的传感器火灾报警器系统灵敏度更高、在火灾发生的早期就能准确的报警,具有系统安全可靠,误报漏报率低,操作简单,成本低廉等优点。但同时也应该看到正

是因为成本问题,这个系统其实并不完美。如果使用更好的传感器,整个系统可以做的更好。系统除了能自动的在发生火灾隐患的情况下发出警报,还能在传感器失效的情况下通过人工报警按键报警。系统的不足之处在于传感器类型单一,今后将通过其他技术进行改进,应用更智能的传感器进行代替。

参考文献

[1]李萍.《AT89S51单片机原理、开发与应用实例》.中国电力出版社.2008.21-42

[2]路勇.电子电路实践及仿真(第一版).清华大学出版社,2004

[3]岳怡.数字电路与数字电子技术(第一版).西北工业大学出版社,2001.

[4]于京张景璐.《51系列单片机C程序设计与应用实例》.中国电力出版社.2006.60-93

[5]周坚.《单片机C语言轻松入门》.北京航空航天大学出版社.2006.164-171.

[6]刘海涛赵金波晁阳.《80C51单片机C语言程序设计与实例解析》.清华大学出版社.2009.67-78

[7]刘君华,智能传感器系统.西安:西安电子科技大学出版.2000.

火灾自动报警系统设计说明书

目录 1 引言.............................................. 错误!未定义书签。 2 工程概况.......................................... 错误!未定义书签。3火灾自动报警系统设计.............................. 错误!未定义书签。 火灾自动报警系统保护对象分级.................... 错误!未定义书签。 火灾自动报警系统形式的确定...................... 错误!未定义书签。 探测区域和报警区域划分.......................... 错误!未定义书签。 确定火灾探测器的种类、设置部位和数量............ 错误!未定义书签。 火灾探测器种类的选择......................... 错误!未定义书签。 火灾探测器的设置............................. 错误!未定义书签。 手动火灾报警按钮的设置.......................... 错误!未定义书签。 火灾报警控制器和监控系统的选择和系统布线以及工程应用错误!未定义书签。 消防联动控制设计................................ 错误!未定义书签。 火灾应急广播或火灾警报装置设置.................. 错误!未定义书签。4设计体会.......................................... 错误!未定义书签。参考资料............................................ 错误!未定义书签。

火灾自动报警系统方案设计

火灾自动报警系统方案 ●本系统采用控制中心型智能消防报警系统,具有火灾报警、联动控制等功能。系统包括以下内 容:手动报警按钮、感烟探测器、感温探测器、警铃和水流指示器等报警装置,系统同时监视 消火栓按钮、报警阀、压力开关、水流指示器及信号阀等的动作信号。 ●为了便于控制和管理,所有消防信号将显示于总控制屏上,以便一旦发生火灾时,可迅速报告 消防局。 ●消防总控制室内有以下设备:消防系统主机(工作站)、火灾视屏显示屏(LED)、火灾自动报警 系统总控制屏、消防联动控制盘、消防专用电话主机、应急电源配电盘和UPS电源、消防系统 运行记录打印机等。消防控制室可监听所有消防电源设备的状态。另外,消防总控制室内设置 一部直拨消防单位的外线电话,并同时提供与消防电话插孔匹配的手提电话。 (1)火灾报警系统保护目标 ●快速火灾探测 ●准确定位火灾地点 ●及时发出火灾报警信号 ●警示相关人员以实现: ●快速疏散建筑物内人群 ●通知相关部门采取救援措施 ●指示相关消防设备动作以实现: ●自动启动消防泵、喷淋泵等水系统灭火设备 ●联动火灾隔断手段如关闭防火卷帘门和防火阀等 ●开启排烟风机、正压风机等防排烟设备 ●开启应急广播、应急照明和疏散指示系统 (2)系统设计原则 ●系统应符合中国有关法律法规,符合消防管理条例和标准。 ●遵照安全第一、预防为主的原则,火灾自动报警系统应严格保证设备可靠性和系统可靠性,避 免误报。 ●系统应具有先进性和适用性:系统的技术性能和质量指标均达到国际先进水平,且在安装调试、 软件编程和操作使用各方面均简便易行,并适合建筑特点,达到最佳的性能价格比。 ●在系统设计时应明确与建筑设备监控系统、安防系统之间的接口界面,且系统的各项技术规范 均符合相应要求。 ●在设计火灾自动报警系统时应预留该系统与综合信息共享管理系统之间信息数据交换接口,系 统的各项技术规范均符合相应要求。 ●在系统设计时应尽量优化设备配置,考虑了整个建筑全系统的统筹配置,避免设备的重复购置 和管线的混乱局面。 在系统设计时应保留足够的冗余度:探测点与控制点的容量上及回路卡的设置上均应保留不少于20%的扩展余地。报警系统施工主要程序:

火灾自动报警与消防联动系统说明

火灾自动报警及消防联动系统说明 (以下各条中,凡打“√”者为本工程选用) 一、火灾自动报警系统概况(√) 1、原有火灾自动报警系统 原建筑已设有火灾自动报警系统,已通过消防审核,其中首层、二层局部现改造为百胜餐饮()必胜客大信餐厅使用。 原建筑火灾自动报警系统保护等级按一级设置,设计依据按GB50116-1998《火灾自动报警系统设计规》执行。 原有火灾自动报警系统包含火灾自动报警系统、消防联动控制系统、火灾应急广播系统、消防直通对讲系统等。 2、本工程火灾自动报警系统(不含应急照明设计) 首层、二层局部现改造为百胜餐饮()必胜客大信餐厅使用。原自动报警主系统未作变更,于平面只作局部的位置调整。 二、设计依据 本设计系依据:JGJ T16-2008《民用建筑电气设计规》(√),GB50016-2006《建筑设计防火规》(√),GB50045-95(2005年版)《高层民用建筑设计防火规》(),GB50116-2013《火灾自动报警系统设计规》(√),GB50067-97《汽车库、修车库、停车场设计防火规》(),GB50038-2005《人民防空地下室设计规》()等有关规以及建设单位和其他专业提供的有关资料。 三、系统组成 火灾自动报警系统(√),消防联动控制系统(√),火灾应急广播

系统(√),消防直通对讲系统(√); 四、消防控制室 1.具有消防联动功能的火灾自动报警系统的保护对象中应设置消 防控制室。(√) 2.本工程消防控制室设在首层,并设有直接通往室外的出口。(√) 3.本工程消防控制室的报警控制设备由火灾报警控制主机、联动控 制台、CRT显示器、打印机、应急广播设备、消防直通对讲设 备、电源设备等组成。(√) 4.消防控制室可接收感烟、感温、火焰、可燃气体等探测器的火灾 报警信号及水流指示器、检修间、压力报警阀、手动报警按钮、消火栓按钮的动作信号。(√) 5.消防控制室可显示消防水池、消防水箱水位,显示消防水泵的电 源及运行状况。(√); 6.消防控制室的联动控制器应能按设定的控制逻辑向各相关的受 控设备发出联动控制信号,并按收相关设备的联动反馈信号。 (√) 7.消防控制室的新增火灾自动报警设备应能与原有火灾自动报警 设备联网及兼容,且各受控设备接口的特性参数应与消防联动控 制器发出的联动控制信号相匹配。(√) 8.消防控制室应有相应的竣工图纸、各分系统控制逻辑关系说明、 设备使用说明书、系统操作规程、应急预案、值班制度、维护保 养制度及值班记录等文件资料。(√)

火灾报警系统安装施工工艺标准

火灾报警系统安装施工工艺 1 施工准备 2 引用标准 GB50339-2003《智能建筑工程质量验收规范》 GB50166-2007《火灾自动报警系统施工及验收规范》 3 材料设备要求 3.1 钢管、接线盒、桥架、控制及通讯线缆的规格型号、材质及阻燃、耐火特性符合设计要求,通过消防产品专业认证,材质检测报告、合格证等齐全。 3.2 火灾探测器:感烟、感温探测器、可燃气体探测器、红外光束探测器、缆式探测器等应有3C认证、型式认可证书、产品质量正面书等。 3.3 手报、消防电话、模块箱。 3.4 控制台、消防报警主机、计算机、不间断电源、打印机等。 4 主要机具 4.1 施工机具:电钻、砂轮、电焊机、电锤。 4.2 测量器具:水平尺、钢卷尺、钢直尺、万用表、摇表、对线器。 4.3 调试仪器:专用消防报警系统综合调试仪器。 5 作业条件 5.1 预埋管路、接线盒、地面线槽及预留孔洞符合设计要求。 5.2 主机房内土建、装饰作业完工,抗静电地板安装完毕,温、湿度达到使用要求。 5.3 机房内接地端子箱安装完毕。 6 安装工艺 6.1工艺流程: 6.2 钢管、金属线槽及线缆敷设 钢管、金属线槽及线缆敷设请参照进行,火灾自动报警系统中钢管和金属线槽敷设及穿线的还应满足下列要求: 6.2.1 火灾自动报警系统线缆敷设等应根据《智能建筑工程质量验收规范》的规定,对线缆的种类、电压等级进行检查。 6.2.2 对每回路的导线用500V 的兆欧表测量绝缘电阻,其对地绝缘电阻值不应小于20M Ω。 6.2.3 不同类型、不同系统、不同电压等级的消防报警线路不应穿入同一根管内或线槽的同

一槽孔内。 6.2.4 埋入非燃烧体的建筑物、构筑物内的电线保护管与建筑物、构筑物墙面的距离不应小于30mm。 6.2.5 如因条件限制,强电和弱电线路同用一竖井时,应分别布置在竖井的两侧。 6.2.6 在建筑物的吊顶内必须采用金属管、金属线槽。金属线槽和钢管明配时,应按设计要求采取防火保护措施。 6.2.7 暗装消火栓配管时应从侧面进线,接线盒不应放在消火栓箱的后侧。 6.2.8 管线与线槽的的接地应符合设计要求和有关规范的规定。 6.2.9 火灾自动报警系统的传输线路应采用铜芯绝缘线或铜芯电缆,阻燃耐火性能符合设计要求,其电压等级不应低于交流250V。 6.2.10 火灾报警器的传输线路应选择不同颜色的绝缘导线,探测器的“+”线为红色,“-”线应为蓝色,其余线应根据不同用途采用其它颜色区分。但同一工程中相同用途的导线颜色应一致,接线端子应有标号。 6.3 火灾探测器安装要求 6.3.1 火灾探测器安装应符合图纸设计要求。 6.3.2 探测器宜水平安装,当必须倾斜安装时,倾斜角不应大于45°。 6.3.3 探测器的底座应固定可靠。 6.3.4 探测器的连接导线必须可靠压接或焊接,当采用焊接时不得使用带腐蚀性的助焊剂,外接导线应有0.15m 的余量,入端处应有明显标志。 6.3.5 探测器确认灯应面向便于人员观察的主要入口方向。 6.3.6 探测器底座的穿线孔宜封堵,安装时应采取保护措施(如装上防护罩)。 6.3.7 在电梯井、升降机井设置探测器时其位置宜在井道上方的机房顶棚上。 6.3.8 探测器至墙壁、梁边的水平距离,不应小于0.5m探测器周围0.5m 内,不应有遮挡物。 6.3.9 探测器至空调送风口边的水平距离不应小于1.5m;至多孔送风顶棚孔口的水平距离不应小于0.5m。 6.3.10 在宽度小于3m 的内走道顶棚上设置探测器时,宜居中布置。感温探测器的安装间距不应超过10m;感烟探测器的安装间距不应超过15m。探测器距端墙的距离不应大于探测器安装间距的一半。 6.3.11 可燃气体探测器的安装位置和安装高度应依据所探测气体的性质而定: a 当探测的可燃气体比空气重时,探测器安装在下部。可燃气体探测器应安装在距煤气灶4m 以内,距离地面应为0.3m。 b 当探测的可燃气体比空气轻时,探测器安装在上部。当梁高大于0.6m 时,探测器应安装在有煤气灶梁的一侧。 c 在室内梁上设置可燃气体探测器时,探测器与顶棚距离应在0.3m 以内。 6.3.12 红外光束探测器的安装应符合以下要求: a 发射器和接收器应安装在一条直线上。 b 光线通路上应避免出现运动物体,不应有遮挡物。 c 相邻两组红外光束感烟探测器水平距离应不大于14m,探测器距侧墙的水平距离不应大于7m,且不应小于0.5m。 d 探测器光束距顶棚一般为0.3~0.8m,且不得大于1m。 e 探测器发出的光束应与顶棚水平,远离强磁场,避免阳光直射,底座应牢固地安装在墙上。 6.4 缆式探测器的安装应符合以下要求:

消防报警系统设计方案

博物馆消防火灾报警系统工程 施工组织设计方案 1.编制说明、 本设计依据建筑设计研究院有限公司电施设计图纸进行编制。 2.工期 工期目标: 消防火灾报警系统工程工期为40天。 七氟丙烷气体灭火系统工程施工工期为30天。 3.质量目标 本工程质量目标: 消防工程施工质量将严格按有关设计及施工验收规和工程评定标准进行施工,合格率达到时100%,确保火灾自动报警系统质量优良。 4.火灾报警系统设备安装工艺要求 4.1火灾自动报警系统设备安装 (1)消防布线的总体要求: 根据消防弱电施工的规,并结合本工程的实际情况,对消防电气的施工布置如下:布线:火灾自动报警系统的布线,应符合现行标准《电气装置工程施工及验收规》的规定和《火灾自动报警系统设计规》(GBJ116-88)的要求。管线包括各层公共部分及其它层平面报警回路线、工作电源线、控制线等线管的穿线,应采用铜芯绝缘导线或铜芯电缆,当额定工作电压不超过50V时,选用导线的电压等级不应低于250V,额定工作电压超过50V时,导线电压等级

不应低于500V。穿线过程中应按照以下工艺标准及要点进行。 (2)接线箱安装: 穿线完毕后,要对每回路导线用500V的兆欧表测量绝缘电阻,满足不了产品或规GB50166--92要求的(20MΩ),应仔细检查并替换。 要求:平稳,底部距地1.5M。安装前应在距盒底100MM处开一个口,并且开口处无倒刺,然后牢固固定在墙上。 (3)火灾报警探测器的安装 A.火灾探测器安装位置,应符合下列规定: 探测器至墙壁梁边的水平距离,不应小于0.5m: 探测周围0.5m,不应有遮挡物: 探测器至空调送口边的水平距离,不应小于0.5m;至多孔送风顶棚孔口的水平距离,不应小于0.5m; 宽度小于3m的风走道顶棚上设置探测器时,宜居中布置。感温探测器的安装间距,不应超过10;感烟探测器的安装间距,不应超过15。探测器距端墙的距离,不应大于探测器安装间距的一半。 B.探测器底座安装 探测器的底座应固定向牢靠,其导线连接必须可靠压接或焊接。当采用焊接时,不得使用带腐蚀性的助焊剂。 探测器底座的外接导线,应留有不小于15cm的量,入端应有明显标志。 探测器底座的穿结孔宜封堵,安装完毕后的探测器底座应采取保护措施。 探测器在即将调试时方可安装,在安装前应妥善保管,并应采取防尘、防潮、防腐蚀措施。

火灾报警系统施工方案

施工组织设计 投标单位(盖章): 法定代表人(盖章): 编制时间:

目录 1、工程概况┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈2 2、系统介绍┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈2 3、编制依据┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈3 4、施工现场管理┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈3 5、施工人员要求┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈4 6、进度控制┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈4 7、施工工序┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈4 8、质量保证措施┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈18 9、危险源、危险点分析及预防┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈19 10、施工现场文明施工环保的要求┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈20 1、工程概况:

本工程名称: 地点: 2系统介绍: 本消防系统包含了火灾自动报警系统、漏电保护系统、消防广播系统、消防、组成; 2.1、火灾自动报警系统由电感烟探测器、手动报警按钮、各类模块、分机、插孔、扬声器、消火栓按钮、可燃气体探测器、模块箱等设备;本系统设消防控制室。室集中设置自动报警监控、消防及紧急广播设备,消防控制室设置一台火灾报警控制器,其消防及紧急广播系统接入消防控制室消防及紧急广播系统。消火栓启泵线引至一期消防水泵房启动水泵。火灾自动报警系统采用总线制控制中心报警系统,外部设备的全部报警信号送至报警控制器上,经分析判断及确认后,自动或手动发出经编码的联动信号,通过总线及模块启停相应的消防联动设备,同事接收状态反馈信号;系统供电采用220VAC消防电源,及在线式不间断电源供电,由业主提供; 2.2、消防广播系统在消防控制室设置消防广播机柜,在所有防火分区设置消防广播扬声器。在火灾时,可以手动或按程序自动启动消防广播系统; 2.3、消防在手动报警按钮上设有插孔,可直接与消防中心通话,配电室设有专用火警分机; 2.4、消火栓系统在各层消火栓箱设消火栓破碎玻璃按钮,当任一层发生火灾时有人破碎玻璃后,可直接启动消防按纽,并向消防控制中心发出信号;确认火灾后由主机启动消防水泵。 3、编制依据: 3.1、依据:《火灾自动报警系统设计规》GB50116-98 《自动喷水灭火系统施工及验收规》GB50261-2005 《气体灭火系统施工及验收规》GB50166-2007 3.2、依据有关的国家及部颁施工标准及验收技术规 4、施工现场管理组 临建:现场库房及现场加工车间的确定:根据现场的实际情况,经甲方指定我单位的临时

火灾报警系统安装施工方案1

拜耳异氰酸酯和聚醚项目TDI联合装置-基础设施BAYER ISOCYANATE & PET PROJECT TDI TRAIN – INFRASTRUCTURE 火灾报警系统和广播呼叫系统施工方案Work Method of Fire Alarm System And Public Address System 编制:Compiled by: 审核:Reviewed by:

目录 CONTENT 1.工程概况GENERAL STATEMENT (2) 2.编制依据COMPOSE BASIS (4) 3.施工方法MAIN METHOD (4) 4施工方法、技术措施CONSTRUCTION PLAN AND TECHNICAL MEASURE (6) 5.质量保证措施、质量通病及治理QUALITY ASSURANCE MEASURES (8) 6.主要施工机具一览表MAIN TOOLS (9) 7.劳动力计划MANPOWER PLAN (9) 8.安全技术措施及HSE管理SAFETY MEASURE (9)

1.工程概况:General Statement 1.1火灾报警和广播呼叫系统包含C581PCS楼、B551楼建筑物和C593柴油发电机部分,B301新增35/10KV变压器室部分以及该区域的水喷雾系统监控。The fire alarm system and public address system include PCS Building C581, B551 Buildings and Diesel Generator C593. B301 New 35/10KV transformer room and its water spray monitoring system are also included. 1.2 C581&C593火灾报警系统为拜耳TDI联合装置的一个子系统火警系统。C581&C593火警系统设备接入变电所C581楼主接线盘P691SS02。B551火灾报警和广播呼叫系统工程为拜耳TDI联合装置的一个子系统。B551火警系统设备接入变电所B551楼主接线盘P661SS02。Fire alarm system of C581&C593 is a sub-project of BAYER ISOCY ANA TE & PET PROJECT TDI TRAIN. The fire alarm system of C581 &C593 is to be connected to PJB P691SS02 of C 581 substation. Fire alarm & Public system of B551 is a sub-project of BAYER ISOCY ANA TE & PET PROJECT TDI TRAIN. The fire alarm system of B551 is to be connected to PJB P691SS02 of C 551 substation 1.3 C581、B551建筑物内全部采用智能型火灾报警控制设备,包括烟感探测器,手动报警按钮,信号模块和控制模块等。C593柴油发电机采用温感探测器和手动报警按钮保护。The system for C581&B551 adopts intelligent devices including smoke detectors, manual call points, input signal modules and output control modules etc. Diesel Generator C593 is protected by heat detectors& manual call points. 1.4 B301新增火警系统设备接入新增现场接线箱E421SF01VK303,通过信号和电源总线接入B301 变电所原有现场接线箱E421SF01VK301。新增火警设备包括烟感探测器、手动报警按钮、感温电缆、信号模块、控制模块和地址模块等。 New 301 fire alarm system equipment is to be connected to new on-site wiring boxes E421SF01VK303 and to the existing on-site substation B301 junction box E421SF01VK301 through the signal and power bus. New fire equipments include smoke detectors, manual call points, temperature cables, input signal modules and output control modules module addresses etc. 1.5火灾报警系统联动设备的控制输出采用24V直流电源信号或干接点信号,最大接点容量为30V/1A,反馈输入采用干接点信号。火灾报警控制器由UPS消防电源专用回路直接供电。在失电情况下,控制器内置电源将能维持8小时操作。所有火灾报警控制盘、柜应可靠接地,接地电阻小于1Ω。Fire Alarm System linkage devices adopt 24V DC power control output signal or dry contact signals. The maximum contact capacity 30V/1A and feedback input adopts dry contact signal. Primary power supply of fire alarm control panel requires UPS power. FACP shall be equipped with a standby battery, rated to maintain operation for 8 hours after main power supply failure. All the panels and boxes shall be well earthed; the resistance shall be less than 1Ω. 1.6 C581&C593广播喇叭接入广播呼叫分线箱P691WL04,占用一路广播回路线。B551广播喇叭接入广播呼叫分线箱P661WL03,占用一路广播回路线。各楼层广播喇叭连接至垂直IT桥架旁的接线盒。广播系统功率放大器至广播喇叭采用恒压100V输出馈线方式。在屋顶安装无线对讲天线并固定于围栏上,通过同轴电缆接入广播系统盘中的无线对讲基站。在每套柴油发电机房内设1个频闪灯,在消防报警时点亮。The public address systems of C581& C593 building will be connected to junction box P691WL04 and occupy one speaker loop. The public address systems of B551 building will be connected to junction box P691WL03 and occupy one speaker loop. Speakers on the same floor shall be connected in field junction box beside the vertical IT cable tray. The output of digital amplifier to speakers will be

火灾报警系统安装

火灾报警系统安装 1.施工准备: 1.1 图纸会审:此项工作是一步极其严肃的重要技术工作,它能减少施工图中的差错,对提高工程质量有重要的作用。接到图纸后负责施工的专业技术人员认真阅读其内容及要求,把疑难问题整理出来,把图中存在的问题记录下来,在图纸会审和施工交底时解决,也为初期预算的准确率打下基础。 1.2 开工准备: 1.2.1 技术准备:由施工组织设计编写,工程造价预算和施工材料预算的编制,以及施工现场管理人员、施工班组人员、后勤保障措施的定位等软件部分组成。现场办公室、工具房、材料房现场用电,较大型工具的准备和首批必须材料的进场等硬件部分组成。 1.2.2 安装准备:消防自动报警系统安装;各级职能部门及班组人员应在吃透图纸设计要求的基础上按照规范要求,逐级进行交底,具体表现在三个方面:Ⅰ质量要求,Ⅱ进度要求,Ⅲ安全及文明工程要求。施工人员带领班组熟悉施工现场条件,掌握土建和装潢进度的配合要求,及时做好用材料进场计划,按专业施工程序指导班组进入工程施工状态。 1.3.必须具备技术资料审批文件、质量体系认证证书等前置条件。 2、安装程序 3.组织施工 工程开工后,施工人员应根据现场的实际情况和特点,配合班组核对图纸给设备定位,明确线路走向,标高要求及线路在不同部位的安装方式,墙面与顶面配管的结合方式,设备接线盒的安装标高尺寸和固定方式等确保项目的交底。 3.1.穿线导管的施工: (1)镀锌的钢导管,可挠性导管和金属线槽不得熔焊跨接接地线,以专用接地卡跨接的两卡间连线为铜芯软导线,截面积不小于4mm2; (2)当非镀锌钢导管采用螺纹连接时,连接处的两端焊跨接接地线;当镀锌钢导管采用螺纹连接时,连接处的两端用专用接地卡固定跨接接地线; (3)金属线槽不做设备的接地导体,当设计无要求时,金属线槽全长不少于2处与接地(PE)或接零(PEN)干线连接。

火灾自动报警系统设计方案与对策

火灾自动报警系统案 ●本系统采用控制中心型智能消防报警系统,具有火灾报警、联动控制等功能。系统包括以下容: 手动报警按钮、感烟探测器、感温探测器、警铃和水流指示器等报警装置,系统同时监视消火 栓按钮、报警阀、压力开关、水流指示器及信号阀等的动作信号。 ●为了便于控制和管理,所有消防信号将显示于总控制屏上,以便一旦发生火灾时,可迅速报告 消防局。 ●消防总控制室有以下设备:消防系统主机(工作站)、火灾视屏显示屏(LED)、火灾自动报警系 统总控制屏、消防联动控制盘、消防专用主机、应急电源配电盘和UPS电源、消防系统运行记 录打印机等。消防控制室可监听所有消防电源设备的状态。另外,消防总控制室设置一部直拨 消防单位的外线,并同时提供与消防插匹配的手提。 (1)火灾报警系统保护目标 ●快速火灾探测 ●准确定位火灾地点 ●及时发出火灾报警信号 ●警示相关人员以实现: ●快速疏散建筑物人群 ●通知相关部门采取救援措施 ●指示相关消防设备动作以实现: ●自动启动消防泵、喷淋泵等水系统灭火设备 ●联动火灾隔断手段如关闭防火卷帘门和防火阀等 ●开启排烟风机、正压风机等防排烟设备 ●开启应急广播、应急照明和疏散指示系统 (2)系统设计原则 ●系统应符合中国有关法律法规,符合消防管理条例和标准。 ●遵照安全第一、预防为主的原则,火灾自动报警系统应格保证设备可靠性和系统可靠性,避免 误报。 ●系统应具有先进性和适用性:系统的技术性能和质量指标均达到国际先进水平,且在安装调试、 软件编程和操作使用各面均简便易行,并适合建筑特点,达到最佳的性能价格比。 ●在系统设计时应明确与建筑设备监控系统、安防系统之间的接口界面,且系统的各项技术规均 符合相应要求。 ●在设计火灾自动报警系统时应预留该系统与综合信息共享管理系统之间信息数据交换接口,系 统的各项技术规均符合相应要求。 ●在系统设计时应尽量优化设备配置,考虑了整个建筑全系统的统筹配置,避免设备的重复购置 和管线的混乱局面。 在系统设计时应保留足够的冗余度:探测点与控制点的容量上及回路卡的设置上均应保留不少于20%的扩展余地。报警系统施工主要程序:

火灾报警系统方案

火灾报警系统方案 一、消防报警系统方案 共设置了2台智能型火灾报警控制机,控制喷淋泵、消防泵、排烟风机、排烟阀、防火门、空调强切、广播、警铃、气体设备等。 1.对整个消防系统功能性保养内容: ?通过总线连接各自楼层各类设备:检查烟感、温感、功能模块等运行状态,以确保系统高度得可靠性。 ?对各类探测器,通过交互式方案,实现各种环境得参数设置,以保证探测器无误报状态。 ?系统自动以中文显示所有探测器状态及事件。 ?控制主机操作控制面板、内部卡件、联动控制盘及各接插件清洁,系统功能检查,外围报警元件、控制元件得系统功能检查、各联动控制设备得测试检查工作(定期服务)、软件检测,后备电源系统检测,以及软件正常运行维护;消防报警系统有关得故障排除。 ?中文中央图形管理系统工作站、打印机功能检查、软件检测及正常运行维护。 2.对消防联动控制系统进行功能性保养内容: ?消火栓控制系统 确认火警之后,中央手动操作控制柜可远程手动控制启动消火栓泵。每台消火栓水泵得运行故障讯号可在消防控制台及显示屏上显示,在紧急情况下。 ?自动喷淋控制系统 喷淋泵得自动启动由压力开关联动控制,喷淋系统水流指示器得讯号通过信号模块送至控制机,显示及打印记录。当报警确认后,由压力开关自动启动喷淋泵,在消控中心控制柜上反映泵得工作状态,并可进行直接应急手动启动与停止泵。?防排烟控制系统 当走道、电梯厅等处得烟感探测器发出报警讯号,控制机通过软件预设发出指令输出联动信号,手动/自动打开报警层(或及其上下层)排烟阀,同时开启排烟风机与正压送风机,进行机械防排烟。在消防中心手动控制柜上配有排烟阀、排烟风机得启停按钮,作紧急启停操作。 ?空调控制系统 当发生报警时,由主控制机发出指令,给相关楼层得继电器模块,手动/自动切断相关层新风机。 ?非消防电源得控制系统

火灾自动报警系统图集

第一章火灾自动报警系统 说明

典型火灾探测器的安装说明: 1.探测器至墙壁、梁边的水平距离不应小于0.5m。 2.探测器周围0.5m内不应有遮挡物。 3.探测器至空调送风口边的水平距离,不应小于1.5m;至多孔送风顶棚孔口的水平距离不应小于0.5m。 4.在宽度小于3m的内走道顶棚上设置探测器时,宜居中布置。感温探测器的安装间距,不应超过10m;感烟探测器的安装间距,不应超过15m。探测器距端墙的距离,不应大于安装间距的一半。 5.探测器宜水平安装,当必须倾斜安装时,倾斜角度不应大于45°。 6.探测器的底座应固定牢靠,其导线连接必须可靠压接或焊接。当采用焊接时,不得使用带腐蚀性的助焊剂。 7.探测器的“+”线应为红色,“-”应为蓝色,其余线应根据不同用途采用其他颜色区分。但同一工程中相同用途的导线颜色应一致。 8.探测器底座的外接导线,应留有不小于15em的余量,入端处应有明显标志。 9.探测器底座的穿线孔宜封堵,安装完毕后的探测器底座应采取保护措施。 10.探测器的确认灯,应面向便于人员观察的主要入口方向。 11.探测器在即将调试时方可安装,在安装前应妥善保管,并应采取防尘、防潮、防腐蚀措施。

装 说 明 单面支架的电缆隧道、电缆地沟内缆式定温探测器的安装可参见本图。 线型火灾探测器和可燃气体探测器有特殊安装要求的 探测器,应符合现 行有关国家标准的 规定。 1.布线要求(1)信号线DC24V 电源线(2)本探测报警器背面有两个挂孔,可直接装在墙面的安装钉上。探测报警器须安装在使用燃气没备的房间中,安装位置应选择易 发生可燃气体泄漏的位置,并尽可能面向气体扩散的方向。探测报警

火灾自动报警系统设计说明书

1.引言 1.1建筑情况 办公楼内来往人员较多,在其内部还有各种贵重设备、资料、文献等,所以一定要做好防火等工作。建筑面积为347平方米。依据《高层民用建筑防火设计规范》,该建筑为二类建筑,耐火等级为二级。 1.2火灾自动报警系统的作用 火灾自动报警及消防联动系统,作为智能建筑中的一个重要子系统,其重要性是众所周知的。要在智能建筑中创造一个安全舒适的环境,消防安全是其中一个重要的方面。火灾自动报警及消防联动系统,作为火灾的先期预报、火灾的即使扑灭、保障人身和财产安全、起到了不可替代的作用。火灾自动报警系统是人们为了早起发现火灾,而设置在建筑物中或其他场所的一种自动消防设施,是人类同火灾作斗争的有力工具。 2火灾自动报警系统简介 2.1火灾自动报警系统概述 火灾自动报警系统能够在火灾初期,将燃烧产生的烟雾、热量和光辐射等物理量,通过感温、感烟和感光等火灾探测器变成电信号,传输到火灾报警控制器,并同时显示出火灾发生的部位,记录发生火灾的时间。 火灾自动报警系统的组成形式多种多样,它的发展目前可分为三个阶段: 1多线制开关量时火灾探测报警系统。 2总线制可寻址开关量式火灾报警系统。 3模拟量传输式只能火灾报警系统。 目前我国已经开始从传统的开关量式火灾报警技术,跨入具有先进水平的模拟量式只能火灾报警技术新阶段,它的系统的误报率降低到最低限度,并大幅度地提高了报警的准确度和可靠性。 目前火灾自动报警系统有智能型。总线型以及综合型等,这些系统部分区域系统或集中系统,可达到对整个火灾自动报警系统进行监视。但是在目前的实际工程当中传统型的区域报警系统、集中报警系统和控制中心系统仍得到广泛的应用。 2.2火灾自动报警系统的组成 火灾自动报警系统由触发器件、火灾报警装置、火灾警报装置以及具有其他辅助功能的装置组成的火灾报警系统,在火灾自动报警系统中,自动或手动产生火灾报警信号的期间称为触发件,主要包括火灾探测器和手动火灾报警按钮。 3.火灾自动报警系统设计 3.1系统选型 依据《火灾自动报警系统设计规范》将此办公楼定为二级保护对象,根据建筑的实际情况,在楼梯口设置一台楼层显示器,作为区域报警器使用,集中报警控制器及联动控制装置。 我们在本工程的火灾报警系统中采用能美日本原装产品R-22Z智能型系统。根据标书

火灾报警系统设计方案

火灾报警系统设计方案 第一章绪论 1.1本课题研究背景 随着我们社会的不断发展,人们的生活、工作以及我们居住的环境愈来愈相对的集中,火灾发生的可能性也变得日益突出,火灾给人们所造成的损失和危害也越来越不可忽视,对广大人民群众的生命财产安全造成了很大的威胁。世界上很多国家都致力于各种各样的火灾报警系统的研究和实验,人们更加重视对火灾发生的及时发现与报警。2011年,我国公安部消防局公布了当年的全国火灾情况,全国共接到报火灾一共125402起,死亡人数一共1106人,受伤人数有572人,直接造成的财产经济损失有18.8亿元。其中,尤其是在节日期间,燃放烟花原因所造成的火灾有所增多,还有建设施工的工地、以及小作坊和小商店等场所火灾发生的数量较多,同时由于用电用火所引起的火灾,在火灾发生总量上仍然占据了比较大的比重。 统计数据显示,全国较大火灾共接报76起,死亡281人,受伤54人,直接财产损失8468.2万元,与2010年相比,死亡人数增加3.3%。全国公司厂房所发生的火灾6779起;居民住宅一共发生了火灾有48548起;而用作仓储场所引起的火灾一共5463起,人口比较集中的场所所发生火灾12471起,因为交通工具事故所造成的火灾13049起;易燃易爆地方事故所发生的火灾407起;城乡火灾总量下降。全国农村一共发生了火灾38469起,死亡349人,受伤154人,造成直接财产损失有39301.3万元。而城市已共引发火灾有43171起,死亡331人,受伤196人,造成的直接财产损失有55330万元;从以上统计数据可以看出,我国火灾情况不容乐观,因此,传统的火灾报警系统已经越来越不适应当今火灾发生的复杂情况了,而传统的火灾报警系统多采用RS-485总线作为通信方式,通信可靠性比较差。所以现在各国更加注重,更加智能、高效、可靠的型、火灾报警控制系统的开发。现代智能高效的火灾报警系统是一个将信号的检测、传输以及控制集于一体的控制系统, 指引了当今智能火灾报警系统的发展方向[1]。

火灾自动报警系统安装及联动调试

一、适用范围 适用于建筑工程中火灾自动报警系统的安装。不适用于生产和贮存火药、炸药、弹药、火工品等爆炸危险场所火灾自动报警系统的安装。 二、施工准备 2.1 技术准备 参见"21.1 电话插座与组线箱安装"第21.1.2.1条。 2.2 材料设备要求 1.前端部分:控制台、消防报警主机、计算机、不间断电源、打印机等。 2.终端部分:感烟、感温探测器、可燃气体探测器、红外光束探测器、缆式探测器、手动报警按钮、消防电话、模块等。 3. 传输部分:电线电缆、模块箱等。 4.上述设备材料应根据合同技术文件和工程设计文件的要求选型,对设备、材料和软件进行进场验收,并填写设备材料进场检验表。设备应有产品合格证、检测报告、安装及使用说明书、"CCC"认证标识等。如果足进口产品,则需 AHAHAGAHAGAGGAGAGGAFFFFAFAF

提供原产地证明和商检证明,配套提供的质量合格证明,检测报告及安装、使用、维护说明书的中文文本(或附中文译文)。设备安装前,应根据使用说明书进行全部检查,方可安装。 5.镀锌材料:镀锌钢管、镀锌线槽、金属膨胀螺栓、金属软管、接地螺栓。 6.其他材料:塑料胀管、机螺钉、平垫圈、弹簧垫圈、接线端子、绝缘胶布等。 2.3 主要机具 1.安装器具:手电钻、冲击钻、电工组合工具、梯子。 2.测试器具:兆欧表(250V、500V)、对线器、水平尺、小线、线坠。 3.调试仪器:专用消防报警系统综合调试仪器。 2.4 作业条件 1.线缆沟、槽、管、箱、盒施工完毕。 2.主机房内土建、装饰作业完工,温、湿度达到使用要求。 3.机房内接地端子箱安装完毕。 AHAHAGAHAGAGGAGAGGAFFFFAFAF

火灾自动报警系统设计说明

火灾自动报警系统设计说明 一、设计依据 《火灾自动报警系统设计规范》GB50116-2013 二、系统形式 1、本项目采用集中报警系统。 三、消防控制室 1、消防控制室设置在地下车库。 2、系统总结上应设置总线短路隔离器,每只总结短路隔离器保护的火灾探测器、手动火灾报警按钮和模块等消防设备的总数不应超过 32 点;总结穿越防火分区时,应在穿越处设置总结短路隔离器。 3、消防控制室应有相应的竣工图纸、各分系统控制逻辑关系说明、设备使用说明书、系统操作规程、应急预案、值班制度、维护保养制度及值班记录等文件资料。 3、消防控制室内严禁穿过与消防设施无关的电气线路及管路。 4、消防控制室的显示与控制应符合现行国家标准《消防控制室通用技术要求》GB25506的有关规定。 5、消防控制室的信息记录、信息传输应符合现行国家标准《消防控制室通用技术要求》GB25506的有关规定。 四、消防联动控制 1、消防联动控制器应能按设定的控制逻辑向各相关的受控设备发出联动控制信号,并接受相关设备的联动反馈信号。 2、各受控设备接口的特性参数应与消防联动控制器发出的联动控制信号相匹配。 3、消防水泵、防烟和排烟风机的控制设备,除应采用联动控制方式外,还应在消防控制室设置手动直接控制装置。 4、需要火灾自动报警系统联动控制的消防设备,其联动触发信号应采用两个独立的触发装置报警信号的“与”逻辑组合。 5、自动喷水灭火系统、消火栓系统、防烟排烟系统、电梯、火灾警报和消防应急广播系统、消防应急照明和疏散指示系统的消防联动控制应满足《火灾自动报警系统设计规范》 GB50116-2013第4节的有关规定。 6、在确认火灾后应启动建筑内的所有火灾声光警报器;火灾声警报器设置带有语音提示功能时,应同时设置语音同步器。火灾自动报警系统应能同时启动和停止所有火灾声警报器工作。消防应急广播与普通广播或背景音乐广播合用时,应具有 强制切入消防应急广播的功能。 7、消防联动控制器应具有切断火灾区域及相关区域的非消防 电源的功能,当切断正常照明时,应在自动喷淋系统、消火栓 系统动作前切断;还应具有自动打开疏散通道上的由门禁系统 控制的门等的功能;并开启相关区域安全技术防范系统的摄像 机监视火灾现场。 五、火灾警报器与消防应急广播 1、火灾声警报器设置带有语音提示功能时,应同时设置语音 同步器。 2、同一建筑内设置多个火灾声警报器时,火灾自动报警系统 应能同时启动和停止所有火灾声警报器工作。 3、每个报警区域内应均匀设置火灾警报器,其声压级不应小 于60dB,在环境噪声大于60dB的场所,其声压级应高于背景 噪声15dB。 4、扬声器的额定功率不小于3W,在环境噪声大于60dB的场所 设置的扬声器,在其播放范围内最远点的播放声压级应高于背 景躁声15dB。 六、消防专用电话 1、消防专用电话网络应为独立的消防通信系统。 2、消防控制室应设置消防专用电话总机;消防水泵房、配电 间、防排烟机房、消防电梯机房等场所应设置消防专用电话分 机;设有手动火灾报警按钮处应设置消防电话塞孔;消防专用 电话分机应有区别于普通电话的标识。 3、消防控制室应设置可直接报警的外线电话。 七、模块设置 1、模块应设置在金属模块箱中。 2、模块严禁设置在配电(控制)柜(箱)内。 3、本报警区域的模块不应控制其他报警区域的设备。 4、未集中设置的模块附近应有不小于100mm*100mm的标识。 八、供电及接地 1、火灾自动报警系统应设有交流电源和蓄电池备用电源,主 电源采用消防电源,备用电源采用火灾报警控制器和消防联动 控制器自带的蓄电池电源。 2、消防控制室图形显示装置、消防通讯设备等电源由UPS电 源装置供电。蓄电池组的容量应保证火灾报警及联动控制系统 在火灾时满负荷连续工作3h以上。 3、采用公用接地装置,接地电阻值不应大于1欧姆。消防控 制室接地板与建筑接地体之间采用BV-1*25导线连接,并采用 BV-1*4引至各消防电子设备;电子设备的金属外壳、机柜、机 架和金属管、槽等应采用等电位连接。 九、系统布线 1、供电线路、消防联动控制线路应采用450V/750V的耐火铜 芯绝缘线缆,报警总线、消防应急广播和消防专用电话等传输 线路应采用300V/500V阻燃或阻燃耐火铜芯绝缘线缆。 2、线路暗敷时,应采用金属管、可绕(金属)电气导管或B1 级以上的刚性熟料管保护,应并敷设在于保护层厚度不小于 30mm的不燃烧体的结构层内;线路明敷时,应采用金属管、可 绕(金属)电气导管或金属封闭线槽保护。并应采取防火保护 措施;从接线盒、线槽等处引到探测器底座盒、控制设备盒、 扬声器箱的线路均应加金属保护管保护。 3、不同电压等级的线缆不应穿入同一根保护管内,当合用同 一线槽时,线槽内应有隔板分隔。采用穿管水平敷设时,除报 警总线外,不同防火分区的线路不应穿入同一根管内。沿线槽 敷设应采用阻燃耐火型导线,阻燃级别为D级。传输线路应选 择不同颜色的线缆,正极为红色,负极为蓝色或黑色,相同用 途导线的颜色应一致,接线端子应有标号。 十、电气火灾监控系统: 1、剩余电流式电气火灾监控探测器设置在低压配电系统第一 级配电柜(箱)的出线端,在现场取~220V作主电源。探测器 报警值为500mA。电气火灾监控器设置在消防控制室内。 2、功能要求:探测漏电电流、过电流等信号,发出声光信号 报警,报出故障线路地址,监视故障点的变化。储存故障和操 作试验信号且时间不小于十二个月。 十一、其他 1、火灾报警系统应与城市119火灾报警系统联网。 2、设备选择:应采用经国家有关产品质量监督检测单位检验 合格的产品。

相关主题
文本预览
相关文档 最新文档