昆山厚声光电A栋暖通空调设计

摘要

本次毕业设计的内容是昆山厚声光电A栋暖通空调设计。昆山厚声光电位于江苏省苏州市,地上四层,总建筑面积18000平方米。整栋大楼主要以办公和生产产间为一体的大楼。该项目空调系统为舒适性空调系统,本设计主要是针对不同的功能房进行空调设计,为室内工作人员提供舒适的工作环境。

针对项目特点,本设计从整个大楼的空调冷负荷计算,从合理设计的角度出发,选择合适的空调系统与方案。设计主要包括冷负荷、湿负荷计算,冷源的选择,空调末端处理设备的选型,水系统的设计、布置与水力计算、管径选取等内容。通过这次设计,我们综合运用理论知识,培养独立创新的能力和解决实际问题的能力。

关键词空调系统、通风舒适、冷负荷、水力计算

Abstract

The content of this graduation design is the project of Kunshan Housheng Photo-electricity Co. Ltd. in building A. Kunshan Housheng Photo-electricity Co. Ltd. is located in Suzhou ,Jiangsu province.There are four floors on the ground and the total construction area is 18,000 square meters.The whole building is mainly used for office and production.It’s air conditioning system of this project is comfortable and this desi gn is mainly aimed at different functional room and providing ease working environment for indoor staff.

In allusion to the characteristics of this project, my design calculated from the whole building’s air conditioning cooling load and from the perspective of the reasonable design, I chose appropriate air conditioning system .My designing mainly including the calculation of cooling load and moisture load, the choice of cold source and air terminal handling equipment, the designing, arrangement, hydraulic computation and diameter selection of water system, and so on. According to this project, we use theoretical knowledge to solve the problem and the aim of it is to improve the ability of innovate and solving the practical problems.

Key words: air conditioning system; comfortable ventilation; cooling load;

hydraulic computation

目录

一、引言 (3)

二、工程概况 (3)

1、工程概述 (3)

2、建筑物的相关资料 (3)

3、设计依据 (4)

4、主要设计内容 (4)

5、设计计算参数 (4)

三、空调冷热源方案的确定 (5)

四、空调系统方案的确定 (5)

4.1车间、办公综合楼空调特点 (5)

4.2方案比较 (6)

4.3方案的确定 (8)

五、空调冷负荷的计算 (8)

5.1冷负荷构成及计算原理 (8)

5.2湿负荷人体散湿量 (11)

5.3根据指标估算法 (12)

六、相关设备的选型与计算 (13)

6.1冷热源机组的选型计算 (13)

6.2风机盘管的选型计算 (14)

6.3水泵的选型计算 (17)

6.4膨胀水箱的选型计算 (18)

七、相关系统管径的选取与计算 (19)

7.1水系统管径的选取与计算 (19)

7.2风系统管径的选取与计算 (22)

八、节能设计 (24)

九、设计系统图 (25)

总结 (27)

致谢 (28)

参考文献 (29)

附录:设计图纸(见后页).................................................................. 错误!未定义书签。

一、引言

暖通空调技术是控制建筑热湿环境、室内空气品质及系统本身产生的噪音的技术。在各类建筑物中,大量采用先进设备和相应配套设备而成的暖通空调系统已成为现代化建筑技术的重要标志之一,是现代建筑创造舒适高效的工作和生活环境所不可缺少的重要基础设施。对这些设备的设计、安装和运行管理不仅直接关系到业主和用户的根本利益,而且也关系到对部环境的保护。由此可见,暖通空调系统在现代建筑中是极其重要的,尤其在现代智能建筑中,暖通空调系统是不可少的组成部分。

二、工程概况

1、工程概述

本建筑是一幢四层高的大楼,地处江苏省苏州昆山市。苏州昆山处我国长江下游地区,属北亚热带季风气候区,四季分明,夏热冬冷,春秋短暂,雨量集中,历年平均气温16℃,主导风向夏季为西南风,冬季为东北风。

本建筑的属性为办公以及生产,总建筑面积约为18000平方米,其中暖通空调设计面积为8129平面米,根据业主要求,设计区域为2-4层。

2、建筑物的相关资料

2.1外装饰:

外墙面采用浅色瓷质外墙面砖饰面,一层沿街柱面粘花岗岩。

2.2楼地面:

a:楼梯间及梯段采用美术水磨石面层。

b:卫生间、厨房(含粗加工)采用防滑地砖面层。

c:其余房间走道、电梯厅均采用铜质砖面层,

3.1内墙面

a、楼梯间采用中级灰砂浆抹灰,白色乳胶漆饰面。

b、电梯厅采用大理石饰面。

c、三~五层轻质隔墙采用乳胶漆饰面。

4.1天棚

房间为中级灰砂浆饰面,刷白色乳胶漆。

5.1 门窗:

窗:采用铝合金窗

门:木门。(防火门需定做)

3、设计依据

3.1气象、水文资料;

3.2各专业有关规范及标准。

《采暖通风与空气调节设计规范》 GB50019-2003

《建筑给水排水及采暖工程施工质量验收规范》GB50242-2002

《通风与空调工程施工质量验收规范》 GB50243-2002

《建筑设计防火规范》 GB50016-2006

《高层民用建筑设计防火规范》 GB50045-95(2005年版)

《江苏省公共建筑节能设计标准》 DGJ32/J96-2010

《公共建筑节能设计标准》 GB50189-2005

4、主要设计内容

4.1空调冷热源方案的确定

4.2空调系统方案的确定

4.3空调冷负荷的计算

4.4相关设备选型与计算

4.5相关系统管径的选取与计算

5、设计计算参数

5.1室外设计参数(上海)

室外计算干球温度:夏季通风:31.2℃;夏季空调:34.4℃;冬季空调:-2.2℃;

室外计算湿球温度:夏季空调:27.9℃;冬季空调室外相对湿度:75%;

注:鉴于相关规范手册上无昆山地区空调室外设计参数,故选取上海地区的室外设计参数作为本项目计算依据。

5.2室内设计参数

房间名称

夏季冬季

新风量人员密度

照明用

电量

设备用

电量

允许

噪声温度

相对

湿度

温度

相对

湿度

(℃) (%) (℃) (%) m^3/h·p (p/m^2) (w/m^2) (w/m^2) dB(A)

办公室25 55 20 - 自然渗透0.17 20 25 50

车间28 60 - - 自然渗透0.50 20 40 60 会议室25 55 20 - 自然渗透0.33 20 30 45

三、空调冷热源方案的确定

空调主机端俗称冷热源系统,是整个系统的核心、根本,合理选用冷热源可以节能、环保,高效、长期运行,使能源最大化利用,因此冷热源的合理选用尤为重要。

项目当地设有大量工业厂房,废汽废水资源较为丰富,利用这一资源,可大大节约系统运行成本,但考虑废气废水余热再利用涉及方面广,牵涉部门较多,初投资大,以及废气废水资源不稳定等诸多因素,觉定不采用溴化锂机组作为空调冷源,不采用废气废水作为空调热源。

对于选用水冷式冷水机组则应提供机房,以确保设备包括冷水机组、冷冻水循环泵、冷却水循环泵正常运行和使用寿命,同时在建筑物地屋面或室外地坪上放有冷却塔设备;水冷式冷水机组制冷量比较大,一般也适合于比较大的项目。而风冷式机组是户外型机组,可以放在建筑物的屋面或室外草坪上,其冷冻水循环泵亦可与机组放在一起,不需占用机房,省却了专用的冷冻机组和锅炉房;其技术经济特点是运行的智能化程度高;运行的可靠性高;安装使用方便、插上电源即可使用,省去了一套复杂的冷却水系统和锅炉加热系统;结构紧凑,外型尺寸小;传热效果好;噪声低;具有夏季供冷水和冬季供热水的双重功能,对于我国幅员辽阔的国土而言,相当大的地区属于夏季需制冷而冬季需制热的范围,这种风冷冷热水机组就特别适用;由于采用空气作为热源和冷源可大大地节约用水,也避免了对水源水质的污染,故此本项目不采用水冷式冷水机组作为空调系统冷热源。

根据以上诸多考虑分析,最终采用风冷机组作为空调冷源。

四、空调系统方案的确定

4.1车间、办公综合楼空调特点

4.1.1建筑特点

车间、办公为一体的综合楼的外围护结构多为钢筋混凝土的框架结构,采用自重的轻型

墙体材料作为外围护结构。车间一般空间比较大,层高较高,无吊顶的操作空间,办公室

由吊顶或架空地板形成办公自动化机器和通讯设备的线性空间,办公楼的净高为2.6m左右。

4.1.2使用特点

车间、办公为一体的的综合楼的使用性质与时间全楼大体一致,所以整幢楼可选择用同

样的空调系统和设备,管理比较方便。一般采用集中或半集中空调系统。

4.1.3车间、办公为一体的综合楼空调系统注意事项

a.分区问题:按建筑物房间用途分为车间区和办公区,车间区和办公区又分别可以分为内区和外区,或按朝向、标准高低、负荷变化以及使用时间等特点划分系统。

b.过度季节问题:过度季节外区可不用冷热源,但内区仍需要降温,这时应用室外空气直接进入内区降温,即节能又简单;或考虑采用一台小容量的制冷机。

c.加班问题:个别办公楼或某层需要节假日加班,为此最好不要设太大的集中空调系统。

d.特殊房间的个别控制问题:用风机盘管系统以便控制。

4.2方案比较

表1全空气系统与空气-水系统方案比较表

比较项目全空气系统空气-水系统

设备布置与机房1.空调与制冷设备可以集中布置在机房

2.机房面积较大层高较高

3.有时可以布置在屋顶或安设在车间柱间

平台上

1.只需要新风空调机房、机房面积小

2.风机盘管可以设在空调机房内

3.分散布置、敷设各种管线较麻烦

风管系统1.空调送回风管系统复杂、布置困难

2.支风管和风口较多时不易均衡调节风量

1.放室内时不接送、回风管

2.当和新风系统联合使用时,新风管

较小

节能与经济性1.可以根据室外气象参数的变化和室内负

荷变化实现全年多工况节能运行调节,

充分利用室外新风减少与避免冷热抵

消,减少冷冻机运行时间

2.对热湿负荷变化不一致或室内参数不同

的多房间不经济

3.部分房间停止工作不需空调时整个空调

系统仍需运行不经济

1.灵活性大、节能效果好,可根据各

室负荷情况自我调节

2.盘管冬夏兼用,内避容易结垢,降

低传热效率

3.无法实现全年多工况节能运行

使用寿命使用寿命长使用寿命较长

安装设备与风管的安装工作量大周期长安装投产较快,介于集中式空调系统与单元式空调器之间

维护运行空调与制冷设备集中安设在机房便于管理

和维护

布置分散维护管理不方便,水系统布

置复杂、易漏水

温湿度控制可以严格地控制室内温度和室内相对湿度对室内温度要求严格时难于满足

空气过滤与净化可以采用初效、中效和高效过滤器,满足室

内空气清洁度的不同要求,采用喷水室时水

与空气直接接触易受污染,须常换水

过滤性能差,室内清洁度要求较高时

难于满足

消声与隔振可以有效地采取消防和隔振措施必须采用低噪声风机才能保证室内要求

风管互相串通空调房间之间有风管连通,使各房间互相污

染,当发生火灾时会通过风管迅速蔓延

各空调房间之间不会互相污染

表2 风机盘管+新风系统的特点表

优点1)布置灵活,可以和集中处理的新风系统联合使用,也可以单独使用

2)各空调房间互不干扰,可以独立地调节室温,并可随时根据需要开停机组,节省运行费用,灵活性大,节能效果好

3)与集中式空调相比不需回风管道,节约建筑空间

4)机组部件多为装配式、定型化、规格化程度高,便于用户选择和安装

5)只需新风空调机房,机房面积小

6)使用季节长

7)各房间之间不会互相污染

缺点1)对机组制作要求高,则维修工作量很大

2)机组剩余压头小室内气流分布受限制

3)分散布置敷设各中管线较麻烦,维修管理不方便

4)无法实现全年多工况节能运行调节

5)水系统复杂,易漏水

6)过滤性能差

适用性适用于旅馆、公寓、医院、办公楼等高层多层的建筑物中,

需要增设空调的小面积多房间建筑室温需要进行个别调节的场合

表3 风机盘管(全水)系统的特点表

优点1)布置灵活,不需要集中处理的新风系统

2)各空调房间互不干扰,可以独立地调节室温,并可随时根据需要开停机组,节省运行费用,灵活性大,节能效果好

3)与集中式空调相比不需回风管道,节约建筑空间

4)机组部件多为装配式、定型化、规格化程度高,便于用户选择和安装

5)不需要新风空调机房,省空间

6)使用季节长

7)各房间之间不会互相污染

缺点1)对机组制作要求高,则维修工作量很大

2)机组剩余压头小室内气流分布受限制

3)分散布置敷设各中管线较麻烦,维修管理不方便

4)无法实现全年多工况节能运行调节

5)水系统复杂,易漏水

6)过滤性能差

7)室内空气品质不高

适用性适用于旅馆、公寓、车间、办公楼等高层多层的新风品质要求不高,或有新风自然渗透的建筑物中,需要增设空调的小面积多房间建筑室温需要进行个别调节的场合

本设计为车间、办公为一体的综合楼的空调系统设计,系统的选定应注意档次和安全的要求,按负担室内空调负荷所用的介质来分类可选择四种系统——冷剂系统、全空

气系统、空气—水系统、全水系统。冷剂系统它是由制冷系统蒸发器直接放于室内消除室内的余热和余湿,由于制冷剂与室内空气直接换热,从而引起室内人体舒适感较差,一般小型场所;全空气系统分一次回风式系统和二次回风式系统,该系统是全部由处理过的空气负担室内空调冷负荷和湿负荷,一般适用于大型公共场所;空气—水系统分为再热系统和诱导器系统并用、全新风系统和风机盘管机组系统并用,一般应用较为广泛;全水系统即为风机盘管机组系统,全部由水负担室内空调负荷;

由于本项目对空气品质要求不高,所以采用全水系统,新风采用自然渗透。

4.3方案的确定

本车间、办公为一体的综合楼采用风机盘管全水系统,分成两个区,车间区和办公区。因为车间与办公楼的热湿要求不同,结构空间不同,车间采用单冷空间,冬季不需要向室内供暖,办公室采用冷暖空调,夏季供冷,冬季供热!

风机盘管空调方式,这种方式风管小,可以降低房间层高,占用空间少,使用也较灵活,但维修工作量大,如果水管漏水或冷水管保温不好而产生凝结水,对线槽内的电线或其它接近楼地面的电器设备是一个威胁,因此要求确保管道安装质量,对于该系统所存在的缺点,可在设计当中根据具体的问题予以解决和弥补。

五、空调冷负荷的计算

5.1冷负荷构成及计算原理

该幢楼东外墙、西外墙、南外墙、北外墙、东外窗、南外窗与外界空气接触,其余各面均与同一室温的空调房间接触,所以不计算与相邻房间的传热。墙、窗、人体、照明的冷负荷分别计算如下:

5.1.1围护结构瞬变传热形成冷负荷的计算方法

1)外墙和屋面瞬变传热引起的冷负荷

在日射和室外气温综合作用下,外墙和屋面瞬变传热引起的逐时冷负荷可按下式计算:

LQ

=F·K·(t l n- t n) W

1

式中:LQ1——外墙和屋面瞬变传热引起的逐时冷负荷,W;

F——外墙和屋面的面积,㎡;

K——外墙和屋面的传热系数,W/(㎡·℃),可根据外墙和屋面的不同构造,可在相关表中查取;

t

——室内计算温度,℃;

n

t

l n

——外墙和屋面冷负荷计算温度的逐时值,℃,根据外墙和屋面的不同类型分别在外墙冷负荷温度表中查取

必须指出:上述式中的各围护结构的冷负荷温度值都是以北京地区气象参数为依据计算出来的,因此对不同地区和不同情况应按下式进行修正:

t'

l n =(t

l n

+ t

d

) ·k a· k p℃(4.2)

式中: t d——地区修正系数,℃,查相关表;

k

a

——不同外表面换热系数修正系数,查相关表;

k p——不同外表面的颜色系数修正系数,查相关表;

2)内墙,楼板等室内传热维护结构形成的瞬时冷负荷

当空调房间的温度与相邻非空调房间的温度大于3℃时,要考虑由内维护结构的温差传热对空调房间形成的瞬时冷负荷,可按如下传热公式计算:

LQ2=F·K·(t l s- t n) W

式中:F——内维护结构的传热面积,m2;

K——内维护结构的传热系数,W /( m2·k) ;

t

n

——夏季空调房间室内设计温度,℃;

t

l s

——相邻非空调房间的平均计算温度,℃。

t'

l s

按下式计算 t'l s=t +t l s℃

式中:t——夏季空调房间室外计算日平均温度,℃;

t

l s

——相邻非空调房间的平均计算温度与夏季空调房间室外计算日平均温度的差值,当相邻散热量很少(如走廊)时, t l s取3 ℃,;当相邻散热量在23~116W /m2时,t l s

取5 ℃。

3)外玻璃窗瞬变传热引起的冷负荷

在室内外温差的作用下,玻璃窗瞬变热形成的冷负荷可按下式计算:

LQ

3

=F·K·(t l – t n) W

式中:F——外玻璃窗面积,m2;

K——玻璃的传热系数,W /( m2·k) ;

本设计单层玻璃K=6.26 W /( m2·k) ;

t

l

——玻璃窗的冷负荷温度逐时值,℃,查表;

t

n

——室内设计温度,℃。

不同地点对t l按下式修正:t l’=t l+t d

式中:t d——地区修正系数,℃,查表。

5.1.2 透过玻璃窗的日射得热引起的冷负荷

透过玻璃窗进入室内的日射得热形成的逐时冷负荷按下式计算:

LQ

4

=F·C Z·D j.max·C LQ W

式中:F ——玻璃窗的净面积,是窗口面积乘以有效面积系数Ca , 本设计单层钢窗C a=0.85;

C Z ——玻璃窗的综合遮挡系数C Z =C s ·C n ;

其中,C s —玻璃窗的遮挡系数,由相关表查得,6mm 厚吸热玻璃C s =0.89; C n —窗内遮阳设施的遮阳系数,由相关查得,中间色活动百叶帘C n =0.6;

D j.max ——日射得热因数的最大值,W/m 2,由相关表查得;

C LQ ——冷负荷系数,可由相关表查得。

5.1.3 设备散热形成的冷负荷

设备和用具显热形成的冷负荷按下式计算:

Q 7=Q q +Q ·C LQ W 式中:Q 7——设备和用具实际的显热形成的冷负荷,W ;

Q q ——设备和用具的实际显热散热量,W ; C LQ ——设备和用具显热散热冷负荷系数;

如果空调系统不连续运行,则C LQ =1.0。

设备和用具的实际显热散热量按下式计算 1)电动设备

当工艺设备及其电动机都放在室内时:

Q =1000·n 1·n 2·n 3·N /η 当只有工艺设备在室内,而电动机不在室内时:

Q =1000·n 1·n 2·n 3·N 当工艺设备不在室内,而只有电动机放在室内时:

Q =1000·n 1·n 2·n 3·1η

η

- N

式中:N ——电动设备的安装功率,kW ;

η——电动机效率,可由产品样本查得;

n 1——利用系数,是电动机最大实效功率与安装功率之比,一般可取0.7~0.9可

用以反映安装功率的利用程度;

n 2——电动机负荷系数,定义为电动机每小时平均实耗功率与机器设计时最大实

耗功率之比;

n 3——同时使用系数,定义为室内电动机同时使用的安装功率与总安装功率之比,

一般取0.5~0.8。

2)电热设备散热量

对于无保温密闭罩的电热设备,按下式计算:

Q =1000· n 1·n 2·n 3·n 4·N 式中:n 4——考虑排风带走热量的系数,一般取0.5;

其中其他符号意义同前。

3)电子设备散热量

计算公式Q=1000·n1·n2·n3·N ,其中系数n2的值根据使用情况而定,本设计对计算机n2取1.0。

5.1.4照明散热形成的冷负荷

根据照明灯具的类型和安装方式的不同,其冷负荷计算式分别为:

白炽灯:LQ5=1000·N·C LQ W

荧光灯:LQ5 =1000·n1·n2·N·C LQ W

式中:LQ5——灯具散热形成的冷负荷,W;

N——照明灯具所需功率,KW;

n 1——镇流器消耗功率系数,当明装荧光灯的镇流器装在空调房间内时,取n

1

=1.2;当暗装荧光灯镇流器装设在顶棚内时,可取n

1

=1.0;本设计取

n

1

=1.0;

n

2

——灯罩隔热系数,当荧光灯上部穿有小孔(下部为玻璃板),可利用自然

通风散热与顶棚内时,取n

2=0.5~0.8;而荧光灯罩无通风孔时,取n

2

=0.6~0.8;本设计取n

2

=0.6;

C

LQ

——照明散热冷负荷系数。

本设计照明设备为暗装荧光灯,镇流器设置在顶棚内,荧光灯罩无通风孔,功率为30w/m2。设备负荷为40 w/m2。

5.1.5人体散热形成的冷负荷

人体散热引起的冷负荷计算式为:

LQ

6

=q s·n·n’·C LQ +q l·n·n’ W

式中:LQ6——人体散热形成的冷负荷,W;

q

s

——不同室温和劳动性质成年男子显热散热量,W;

n——室内全部人数;

n’——群集系数,办公楼群集系数为0.93;

C

LQ

——人体显然散热冷负荷系数,人体显然散热冷负荷系数。

5.2湿负荷人体散湿量

人体散湿量可按下式计算:

D=n·n’·w·10-3 kg/h

式中:D——人体散湿量,kg/h;

n’——群集系数,办公楼群集系数为0.93;

w——成年男子的小时散热量,kg/(h·p);26℃时,极轻劳动成年男子的小时散

热量为0.109 kg/(h·p)。

5.3根据指标估算法

在设计工程图纸时,根据经验得到单位冷量指标,估算房间所需的冷热负荷,此幢楼的具体配置表如下:

空调系统配置表

江苏厚聲光電A棟

楼层房间名称房间

面积

单位冷

指标内机形式内机型号台数

制冷量

单位制冷

负荷

内机总制冷量m2W/m2W/台W/m2W

二层离子溅射车间184 180 WA卧室暗装FP-238 3 13200 215.22 39,600 辅助1 23 180 WA卧室暗装FP-85 1 4720 205.22 4,720 清洗车间150 180 WA卧室暗装FP-170 3 9700 194.00 29,100 老化车间63 180 WA卧室暗装FP-238 1 13200 209.52 13,200 辅助3 25 180 WA卧室暗装FP-102 1 5600 224.00 5,600 治具检修间62 180 WA卧室暗装FP-238 1 13200 212.90 13,200 修护房28 180 WA卧室暗装FP-102 1 5600 200.00 5,600 清洗机房71 180 WA卧室暗装FP-136 2 7400 208.45 14,800 白边仓库80 180 WA卧室暗装FP-136 2 7400 185.00 14,800 端涂195 180 WA卧室暗装FP-238 3 13200 203.08 39,600 折粒487 180 WA卧室暗装FP-238 8 13200 216.84 105,600 濺射323 180 WA卧室暗装FP-238 5 13200 204.33 66,000 半成品库56 180 WA卧室暗装FP-204 1 11300 201.79 11,300 堆叠445 180 WA卧室暗装FP-238 7 13200 207.64 92,400

三层

刻线车间73 180 WA卧室暗装FP-136 2 7400 202.74 14,800 制氮机房28 180 WA卧室暗装FP-102 1 5600 200.00 5,600 薄膜镭射车间83 180 WA卧室暗装FP-170 2 9700 233.73 19,400 清洗车间145 180 WA卧室暗装FP-238 2 13200 182.07 26,400 溅射车间73 180 WA卧室暗装FP-136 2 7400 202.74 14,800 溅射车间78 180 WA卧室暗装FP-136 2 7400 189.74 14,800 溅射维修间39 180 WA卧室暗装FP-136 1 7400 189.74 7,400 镭射车间751 180 WA卧室暗装FP-238 12 13200 210.92 158,400 印刷车间1190 180 WA卧室暗装FP-238 18 13200 199.66 237,600 网板室107 180 WA卧室暗装FP-170 2 9700 181.31 19,400 全检室108 180 WA卧室暗装FP-170 2 9700 179.63 19,400 生管室124 180 WA卧室暗装FP-238 2 13200 212.90 26,400

四层烧结区903 180 WA卧室暗装FP-238 14 13200 204.65 184,800

印刷区1277 180 WA卧室暗装FP-238 20 13200 206.73 264,000 晶片办公室142 180 WA卧室暗装FP-238 2 13200 185.92 26,400

生管办公室75 180 WA卧室暗装FP-136 2 7400 197.33 14,800

晶片会议室84 220 WA卧室暗装FP-170 2 9700 230.95 19,400

交接班室55 180 WA卧室暗装FP-204 1 11300 205.45 11,300

交接班室56 180 WA卧室暗装FP-204 1 11300 201.79 11,300

张网室91 180 WA卧室暗装FP-170 2 9700 213.19 19,400

曝光室29 180 WA卧室暗装FP-102 1 5600 193.10 5,600

网板室98 180 WA卧室暗装FP-170 2 9700 197.96 19,400

膏品室54 180 WA卧室暗装FP-170 1 9700 179.63 9,700

维修间32 180 WA卧室暗装FP-102 1 5600 175.00 5,600

基板暂放区70 180 WA卧室暗装FP-238 1 13200 188.57 13,200

物品放置区37 180 WA卧室暗装FP-136 1 7400 200.00 7,400

导体库135 180 WA卧室暗装FP-238 2 13200 195.56 26,400 汇总A栋二、三、四层8129 140 204.04 1,658,620 空调总冷负荷大约为1658620W,单位空调面积冷负荷:204.04W/m2,总冷负荷大约为

1367560W,单位空调面积冷负荷:168.23W/m2.

六、相关设备的选型与计算

6.1冷热源机组的选型计算

6.1.1冷热源机组选取一般规定

1)冷热源机组的选择应根据制冷工质的种类、装机容量、运行工况、节能效果、环保安全以及负荷变化情况和运转调节要求等因素确定;

2)确定冷热源机组容量时,应考虑不同朝向和不同用途房间的空调峰值负荷同时出现的可能性,以及各建筑的用冷工况的不同,乘以小于1的负荷修正系数。该系数一

般采用0.8~0.9左右,特别情况下有时采用1;

3)制冷装置和冷水系统的冷损失应根据计算确定,概略计算时按下列数值选用:氟利昂直接蒸发式系统5%~10%,间接式系统 10%~15%;

4)当采用多台相同型号的制冷机时,单台容量调节的下限产冷量大于建筑的最小负荷时,应选用一台小型的制冷机来适应低负荷的需要。;

5)并联的冷水机组至少应选一台节能显著、自动化程度高、调节性能好的冷水机组。

6.1.2冷热源机组的选型计算

1)初选机型。根据制冷系统负荷Q0=1658.620KW,结合建筑物的构造和用途进行综

合考虑,分单冷区和冷暖区,单冷区负荷Q01=901.920KW,冷暖区负荷Q01=756.700KW。

因为根据业主选取的品牌为台湾国祥模块式风冷冷水(热泵)机组,SKMS-040模块比较经济实惠,室内机同时使用率为1,所以选择7台台湾国祥SKMS-040模块式风冷冷水机组,6台湾国祥SKMS-040模块式风冷热泵机组。

2)该系统机组的设计工况为:冷冻水进水温度为12℃,出水温度为7℃。

3)根据SKMS-040的性能表,在设计工况下,即冷冻水进出口温度为12℃、7℃时机组的制冷量为130.0KW。

在设计工况下,单冷区7台机组的总制冷量为Q=7×130.0=910.0KW> 901.920KW,冷暖区6台机组的总制冷量为Q=6×130.0=780.0KW>756.700KW满足要求。

4)根据SKMS-040的性能表查得,机组在标准制冷运行,其有关性能参数如下:制冷量:130.0KW,制热量:144.0KW

进水温度:12℃,出水温度:7℃

流量:22.4m3/h

接管通径:65mm

水阻损失:1.0MPa

机组尺寸:长(A)2460 宽(B)2445 高(C)2120

6.2风机盘管的选型计算

6.2.1风机盘管的性能与结构

风机盘管是空调设备的主要组成部分,用于外供冷水、热水,是一种将风机和表面式换热盘管组装在一起的装置,型式有卧室、立式和顶置式等数种,是分散安装在每一个需要空调的房间内,对房间直接送风,具有供冷、供热或分别供冷和供热的功能,其风量一般为250m3/h~2500m3/h,出风口静压一般小于100Pa的机组。为了缩小外形和体积以及降低气流噪声,多采用贯流式风机并用多级电机驱动,以便对风量的调节。以下为卧室暗藏风机盘管、立式明装风机盘管的结构图和风机盘管机组的分类:

6.2.2风机盘管的选型

1)根据整幢楼各房间的吊顶装修布置类型,选择卧式暗装;

2)因每个房间的出风口与风机盘管连接是通过风管的,有较大的风阻力,所以选择高静压;

3)因双盘管造价高、体积大,综合考虑选择单盘管,双管制水系统

最终选择卧式暗装高静压双管制风机盘管

6.2.2风机盘管冷热负荷计算

一般规定:选择风机盘管时,须根据不同的新风供给方式来计算冷负荷。当单独设计新风系统时,若新风参数与室内参数相同,则可不计入新风的冷热负荷,若新风参数夏季低于室内,冬季高于室内,则机组须扣除新风分担的负荷。若依靠渗透或墙洞引进的新风,则应计入新风负荷。

由于风机盘管用久后管内积垢,管外积尘,影响传热效果,冷热负荷须按以下表进行修正:

风机盘管的计算方法

1)根据室内、外空气设计参数,计算得出的房间冷负荷Q和湿负荷W值;然后根据设计要求,确定房间的新风量以及新风被处理后的状态点,计算得到新风负荷。

2)根据房间冷负荷Q和湿负荷W以及新风量和新风被处理后的状态点,得到房间的送风量和送风状态点。

3)根据风机盘管样本,查得其名义冷量和名义热量,根据风量修正、工况修正及污垢修正,求得风机盘管实际工况下的冷、热量。

4)当其大于或等于计算冷负荷时则满足要求;当其小于计算冷负荷时则需增风机大盘管继续校核

以辅助3车间为例:

1)空气处理方案及有关参数的查取,采用新风直入式空气处理方式,新风机组不承担室内负荷,空气处理过程如下图所示:

由t N =26℃, Φ=50%得h N =52.5 KJ/Kg ,t NS =18.6℃; 由t w =35℃,t ws =28.3℃得h W =91.2 KJ/Kg ;

查h-d 图t NL =14.9℃,t N -t NL =26-14.9=11.1>10℃,则取送风温度差为Δt =10℃;则

t l’(F)=26-10=16℃,由t l’(F)=16℃,Φl’(F)=90%,在h-d 图上定出风机盘管机器露点L ’(F),得h l’(F)=44.9 KJ/Kg 。

2)房间所需冷量(包括新风) Q =6520 W 3)房间所需新风冷负荷 CL W 5 =1940W

4)风机盘管所需冷量 Q F =Q - CL W 5 =6521-1940=4580W 5)风机盘管所需风量

L F = Q F /[1.2·(h N - h l’(F))]=4.58/[1.2×(52.5-44.9)]=0.502m 3/s=1807 m 3/h 6)选择风机盘管

所选的风机盘管要求当进水温度为7℃时,进风参数DB/WB=26/18.6℃,L F =1807 m 3/h ,Q F =4580 W 。

根据所需风量及中等风速选型原则,初选型号为FP-102的标准型风机盘管一台,进水温度为7℃时查得风机盘管的冷量为5400×0.91=4914W ,满足要求。故选FP-102的标准型风机盘管一台,其水压降为18.5kpa 。

用同样方法确定其他房间风机盘管型号,也可用冷量经验值的方法结合所选品牌台湾国祥的风机盘管的规格确定每个房间的风机盘管的型号大小,见P12页配置表。

6.3水泵的选型计算

水泵分冷冻水泵和冷却水泵,因选用的主机为风冷热泵(冷水)机组,无需冷却塔系统,故无冷却水泵,只需冷冻水泵的选型计算。根据选型原则,选择三台冷冻水泵(两用一备),选用离心式清水泵。水泵所承担的供回水管网最不利环路为二层最西面管路。

6.3.1水泵流量的确定

单台风冷热泵(冷水)机组的额定水流量为22.4m 3/h ,单冷区由7台风冷冷水模块组成,根据水泵工作时,取流量储备系数1β =1.1。则单台水泵设计流量V =1.1×(22.4×7)/2=86.24m 3/h 。冷暖区由6台风冷冷水模块组成,则单台水泵设计流量V =1.1×(22.4×6)/2=73.92m 3/h 。

6.3.2水泵扬程H 的确定

水泵扬程H 按下式计算:H =2β· Hmax (8.2) 式中:H ——水泵扬程,m;

H max ——水泵所承担的最不利环路的水压降,m H 2O;

2β——扬程储备系数取2β=1.1。

总压降max H 为供回水管网最不利环路的水压降,可以按照以下公式估算水泵的扬

程:

H max=△P1+△P2+0.05·L·(1+K) m H

0 (8.3)式

2

中:△P1——冷水机组蒸发器的水压降,m H20;

△P2——最不利环路中并联空调末端装置中水压损失最大者的水压降,m H20;

K——最不利环路中局部助力当量长度总和与该环路管道总度的比值,

本设计K=0.6[1]。

冷水机组蒸发器的水压降△P1=60KPa=6.0mH20。最不利环路中并联空调末端装置中水压损失最大者△P2是FP-204风机盘管,它的水压降△P2=33KPa=3.3m H20。环路中各种管件的水压降和沿程压降之和按估算法计算:水系统为同程式,最不利环路总长约为280m。

最不利环路总阻力约为:

H max=6.0+3.3+0.05×280×(1+0.6)=31.7 mH

O。

2

水泵设计扬程为H =1.1×31.7=34.87 mH2O。

O,单冷区水泵的流量为73.92m 所以单冷区水泵的流量为86.24m 3/h,扬程为25mH

2

3/h,扬程为25mH

O,根据以上算出的流量、扬程值选出具体的水泵设备厂家型号。

2

6.3.3冷冻水泵配管布置

进行水泵的配管布置时,应注意以下几点:

1)安装软性接管:在连接水泵的吸入管和压出管上安装软性接管,有利于降低和减弱水泵的噪声和振动的传递。

2)出口装止回阀:目的是为了防止突然断电时水逆流而时水泵受损。

3)水泵的吸入管和压出管上应分别设进口阀和出口阀;目的是便于水泵不运行能不排空系统内的存水而进行检修。。

4)水泵的出水管上应装有温度计和压力表,以利检测。如果水泵从地位水箱吸水,吸水管上还应该安装真空表。

5)水泵基础高出地面的高度应小于0.1m,地面应设排水沟。

6.4膨胀水箱的选型计算

膨胀水箱用来贮存水系统中的膨胀水量,同时起恒定水系统压力。在机械循环系统中,接至循环水泵吸入口前连接处的压力,无论系统在不工作或运行时,都是恒定的。循环管应接到系统点前的水平回水干管上,该点与定压点之间保持1.5~3m的距离,这样可防止寒冷天气水箱里的水冻结。膨胀水箱应考虑保温,在膨胀管、循环管和溢水管上,严禁安装阀门,以防止系统超压,水箱水冻结或水从水箱溢出。

本设计中只选用一个膨胀水箱,膨胀水箱连在回水管上。

膨胀水箱的有效容积为:

V t V p c =α..max ? L

式中 α?水的体积膨胀系数,0.0006,1/℃

max t ??考虑系统内水受热和冷却时水温的最大波动值,

一般以20℃水温算起; C V ?系统内的水容量,L

最大温差出现在冬天供暖的时候,所以取max t ? =45-20=25℃

C V 只可按下表确定

系统内的水容量l/m 2(建筑面积)

系统类型 全空气系统 与机组结合使用的方式

供冷时 0.40~0.55 0.70~1.30 供暖时 1.25~2.00

1.20~1.90

取C V =1.5

建筑面积大约为18000m 2,取系统内的水容量为18000×1.5/1000=27m 3,故 V P =0.0006×25×27=0.405m 3 则本系统的膨胀水箱有效容积可取0.5m 3。

注意:膨胀水箱应加盖和保温,常用带有网格线铝箔帖面的玻璃棉作保温材料,保温层厚度为25mm 。

通气管

补水管循环管

膨胀管

排污管

信号管

溢流管图8.3 膨胀水箱

七、相关系统管径的选取与计算

7.1水系统管径的选取与计算

7.1.1水系统的比较、选择

空调水系统比较表

类型 特征 优点 缺点

闭式 管路系统不与大气相接触,仅在系统最高点设置膨胀水箱 与设备的腐蚀机会少;不需克服

静水压力,水泵压力、功率均低。

系统简单

与蓄热水池连接比

较复杂

开式 管路系统与大气相通 与蓄热水池连接比较简单 易腐蚀,输送能耗大

同程式

供回水干管中的水流方向相同;经过每一管路的长度相等 水量分配,调度方便,便于水力平衡 需设回程管,管道长度增加,初投资稍高 异程式 供回水干管中的水流方向相

反;经过每一管路的长度不相

等 不需设回程管,管道长度较短,管路简单,初投资稍低 水量分配,调度较难,水力平衡较麻烦

两管制 供热、供冷合用同一管路系统 管路系统简单,初投资省

无法同时满足供热、

供冷的要求

三管制 分别设置供冷、供热管路与换热器,但冷热回水的管路共用 能同时满足供冷、供热的要求,

管路系统较四管制简单

有冷热混合损失,投

资高于两管制,管路

系统布置较简单

四管制 供冷、供热的供、回水管均分开设置,具有冷、热两套独立的系统 能灵活实现同时供冷或供热,

没有冷、热混合损失

管路系统复杂,初投

资高,占用建筑空间

较多

本系统设计可以采用双管制供应冷冻水,且具有结构简单,初期投资小等特点。同时考虑到节能与管道内清洁等问题,可以采用闭式系统,不与大气相接触,仅在系统最高点设置膨胀水箱,管路不易产生污垢和腐蚀,不需要克服系统静水压头,水泵耗电较小。

由于设计属于多层建筑,因此可以采用同层同程式水系统,由于各并联环路的管路总长度基本相同,各用户盘管的水阻力大致相等,所以系统的水力稳定性好,流量分配均匀,只有层与层的的管路有稍微之差。

本设计采用的是风冷热泵(冷水)机组,机组布置在顶层的方案。供回水立管均采用同程式,各层水管也采用同程式。定压补水系统采用膨胀水箱,膨胀水箱置于顶层。

7.1.2水利计算与管径选取

冷冻水水管的水力计算的方法一般步骤如下: 1)定各管段的计算流量

管段的计算流量就是该管段所负担的各个房间的计算流量之和,以此计算流量确定管段的管径和压力损失。

a 、各房间的计算流量可用下式确定

)

(21ττρ-=

c Q

G m 3/h

式中:C ——水的质量比热,c=4.1868kJ/kg ℃;

Q ——冷负荷,kW ;

1τ、2τ——设计的供回水温度。

ρ--水的密度,kg/m 3

b 、可根据客房间布置的风机盘管的流量累计计算(一般情况下,在算管径时根据此方法)

暖通空调设计毕业设计说明书

摘要 本设计为哈尔滨望江集团办公楼空调系统工程设计。哈尔滨望江集团办公楼属中小型办公建筑,本建筑总建筑面积4138m2,空调面积2833m2。地下一层,地上八层,建筑高度33.9m。全楼冷负荷为191千瓦,全楼采用水冷机组进行集中供给空调方式。 此设计中的建筑主要房间为办公室,大多面积较小,且各房间互不连通,应使所选空调系统能够实现对各个房间的独立控制,综合考虑各方面因素,确定选用风机盘管加新风系统。在房间内布置吊顶的风机盘管,采用暗装的形式。将该集中系统设为风机盘管加独立新风系统,新风机组从室外引入新风处理到室内空气焓值,不承担室内负荷。风机盘管承担室内全部冷负荷及部分的新风湿负荷。风机盘管加独立新风系统由百叶风口下送和侧送。水系统采用闭式双管同程式,冷水泵三台,两用一备;冷却水泵选三台,两用一备。 在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。 依据相关的空调设计手册所提供的参数,进一步完成新风机组、水泵、热水机组等的选型,从而将其反应在图纸上,最终完成整个空调系统设计。 关键词:风机盘管加独立新风系统;负荷;管路设计;制冷机组:冷水机组

Abstract The design for the Harbin Wangjiang Design Group office building air conditioning system. Harbin Wangjiang Group is a small and medium-sized office building office buildings, the total floor area of building is 4138m2, air-conditioned area is 2833m2. There are eight floor of the building, building height is 33.9m. Cooling load for the entire floor, 191 kilowatts, the whole floor using Central Cooling Chillers to focus on the way . This design of the main room of the building for office, most of them is very small, and the rooms are not connected, the selected air-conditioning system should be able to achieve independent control of each room, considering the various factors to determine the selection of fan-coil plus fresh air system. Arrangement in the room ceiling fan coil units, using the dark form of equipment. Set the focus on fan-coil system, plus an independent air system, fresh air from the outdoor unit to deal with the introduction of a new wind to the indoor air enthalpy value, do not bear the load of indoor. All bear the indoor fan-coil cooling load and part of its new rheumatoid load. Fan-coil plus an independent air system sent by the Venetian and the under side air delivery. Closed water system with a dual-track program, three cold-water pump, dual-use a prepared; cooling pumps three elections, one prepared by dual-use. In the cooling load calculation based on the completion of the selection of host and fan coil units, and air volume, the calculation of water, the wind pipe and water pipes to determine the specifications of the road and check the resistance to the most disadvantaged and the loop to determine the pressure head new fans and pumps. Based on the relevant manuals provided by air-conditioning design parameters, and further completion of the new air units, water pumps, hot water units, such as the selection, which will be reflected in their drawings, the final design of the entire air-conditioning system Key words: PAU+FCU systems; load; pipeline design; refrigeration machine; Chillers

暖通空调毕业设计指导书

暖通空调毕业设计 一、设计题目综述 本设计是综合楼中央空调系统设计。 由建筑学专业作土建设计,提供AUTOCAD土建图,由建筑环境与设备工程专业同学确定设备机房、管井的位置和面积、防火分区与空调系统分区的关系,以及围护结构的热工性能合理性等问题,然后进行建筑设备系统设计。 二、建设地点 建筑地点自行确定,有关地段的环境、规划要求、高度限制,地面停车要求等自行考察确定。 三、使用面积分配组成 四、建筑设备系统设计任务 1.设计内容 综合楼空调设计: (a)、设计整个建筑的暖通空调系统 要求: [1]客房、公共、餐饮、康乐部分全年采用空调; [2]行政后勤、工程部分冬季采暖、夏季空调;车库全年通风。 [3]防排烟方案设计. (b)、设计整个建筑的冷热源系统。热源需要考虑全年生活热水需要。 (c)、设计整个建筑的暖通空调、冷热源系统的自动控制系统。 2.设计人员 每组平均2人,选出一名设计组长。 3.提交成果 (1)设计计算、说明书一份。说明书及计算书部分打印装订好,并提交电子版。

(2)施工图纸一套,内容至少包括: [1]施工图首页和设备清单 [2]裙房各层的送、回风管道和供暖管道的平、剖面图;(主要设备布置平、剖面图) [3]裙房一套风系统的轴测图; [4]冷、热源机房的平、剖面图;(燃油锅炉房平、剖面图)。 [5]裙房冷却水与冷冻水系统轴测图;(燃油锅炉房系统图) [6]空调机房的平、剖面图(包括风系统与水系统); [7]标准层的平面图,包括空调风系统、水系统、供暖系统、生活热水系统; [8]标准层空调机房的平、剖面图; [9]空调冷冻水系统的轴测图;(给排水系统图) [10]采暖系统的轴测图; [11]自动控制系统与冷、热源控制系统原理图。 个人施工图要求: 每人出图12~15张,类型必须包括:(1)风系统平面(2)水系统图(3)冷热源或空调机房图(平面图和局部剖面图)(4)自控系统原理图(5)防排烟系统方案图教师可根据具体情况对不同的组员指定用绘图仪出不同的图, 设计进度和考核形式 (1)两周方案确定与论证,有方案评审答辩,教师任评审专家; (2)三周初步设计,有初步设计评审答辩,教师任评审专家; (3)七周施工图设计,有最终验收答辩,教师任评审专家。 暖通空调毕业设计指示书一、方案阶段与可行性研究(共2周) 根据当地的具体条件初步确定空调系统与采暖系统的可能形式以及冷、热源的可能形式,并进行投资估算,对建筑设计和对城市环境保护的影响给出评价。提出几个可行的方案,并进行论证比较,为甲方最终决策提供依据。 设备容量要通过负荷计算后决定。如果土建的详细资料未确定,可采用冷负荷指标、热负荷指标等进行估算。 步骤: (一)基础部分(第一周完成) 1.根据主要功能区面积采用冷负荷和热负荷估算指标估算各空间的冷热负荷; 2.初步确定可能的冷热源形式、空调系统形式和系统分区; 3.与建筑师商讨确定冷热源机房、空调机房、管井、冷却塔的位置,并检查面积是否合适;要考虑服务半径、噪声、防火分区的影响。

暖通空调毕业设计开题报告

1.课程设计的意义 通过本次的课程设计,使自己拥有一定的暖通空调设计能力;了解一些相关的规范和条例;熟悉并掌握暖通空调设计流程;同时使自己的思维更加的严谨,态度更加的认真,为以后的社会工作奠定了扎实的基础。 2.文献综述 随着国民经济的快速持续发展,作为支柱产业之一的建筑业也得到迅猛发展。而作为建筑业的重要组成部份的暖通空调业,其新产品、新技术、新材料更是层出不穷。暖通空调业发展所遵循的原则,概括起来就是:节能、环保、可持续发展,保证建筑环境的卫生与安全,适应国家的能源结构调整战略,贯彻热、冷计量政策,创造不同地域特点的暖通空调发展技术。因此,如何结合设计的需要,重视相关技术,并有选择而合理的应用在我们的设计中,满足业主要求,提高设计水平,是我们必须努力做到的。 2.1.暖通空调变工况点优化控制及能量管理探讨 2.1.1.工况点优化控制 暖通空调变工况点优化控制问题的研究近年来在我国被重视。S.W.Wang 提出了一种基于整个系统环境的预测响应及能量运行来改变暖通空调系统控制,设定点的系统方法,并用遗传算法对系统进行优化控制,同时优化多个设定点来改善系统响应和降低系统能耗[1],后来他又采用自适应性控制理论对某海水冷却。空调系统进行了优化控制研究,采用带指数遗忘的最小二乘法参数辨识方法和基因遗传优化算法,对空调系统的空气处理单元进行了优化控制研究[2]。罗启军等人提出了一项动态的优化技术在一个指定期间内,能得到使目标函数( 运行成本或者峰值能耗) 最小的房间温度曲线,该算法还给出了暖通空调设备的最佳开/关时间[3]。K.T.Chan 等人提出用遗传算法对风冷制冷机的冷凝温度设定点进行优化控制以提高制冷机的效率[4]。此外,有许多研究者用人工神经网络来模拟暖通空调系统中各个设备的非线性特性,用于实现对整个空调系统的优化控制。目前,研究者们将更多先进的建模方法和智能优化方法引入到了暖通空调的优化控制中,更加注重变工况点的在线优化控制。何厚建等人对已建的暖通空调各关键设备的静态模型采用用实数编码的遗传算法建立了水系统工作点优化控制策略[5]杨晓平等人采用模糊聚类和RBF方法建立了空气处理单元的动态数学模型,以最终舒适性为目标优化空气处理单元的温湿度和送风压力[6]。孙一坚根据空调负荷变化对一级泵水系统进行变流量控制,取得了显著效果[7]。总之国内的学者更多探讨的是把智能方法引入控制系统的优化中,仿真研究多,实践成果少。

暖通空调毕业设计

1.工程概况及主要设计参数 (1) 1.1 工程概况 (1) 1.2 基本设计参数 (1) 1.3 设计依据 (3) 2.空调系统的负荷计算 (3) 2.1空调房间的冷负荷计算 (3) 2.2湿负荷计算 (8) 2.3热负荷计算 (9) 3系统方案确定 (18) 3.1系统的分区 (18) 3.2空调系统的分类 (19) 3.3空调系统的比较 (20) 3.4空调系统方式的确定 (24) 3.4 空调房间送风量的确定 (27) 3.5空气处理设备选型 (29) 4.室内气流组织形式的确定及计算 (33) 4.1 送、回风口的型式 (33) 4.2 气流组织形式 (35) 4.3 气流组织的设计计算 (38) 5水系统设计 (44) 5.1水系统简介 (44) 5.2水系统的管路设计计算 (49) 5.4空调水系统水力计算 (51) 5.5系统管材的选择 (54) 6.风管的布置及其水力计算 (55) 6.1风管设计的基本知识 (55) 6.2风管的水力计算 (58) 7.空调制冷机房设计 (63) 7.1空调冷水系统 (63) 7.2热水循环系统.................................................................................. - 66 - 7.3冷冻水系统设计.............................................................................. - 68 - 7.4冷却水系统...................................................................................... - 71 - 7.5循环水系统的补水、定压与膨胀.................................................. - 74 - 7.6 管道的水力计算............................................................................. - 76 -8系统保温及消声、减震........................................................... - 79 - 8.1管道及设备的保温.......................................................................... - 79 -

暖通空调系统介绍

【tips】本文由李雪梅老师精心收编,值得借鉴。此处文字可以修改。 暖通空调系统介绍 好的工作环境,要求室内温度适宜,湿度恰当,空气洁净。暖通空调系统 就是为了营造良好的工作环境,并对大厦大量暖通空调设备进行全面管理 而实施的监控。暖通空调系统的监控内容如下:空调系统的监控 1)新风机组的监控新风机组中空气水换热器,夏季通入冷水对新风降温 除湿,冬季通入热水对空气加热,干蒸汽加湿器用于冬季对新风加湿。对 新风机组进行监控的要求如下: (1)检测功能:监视风机电机的运行/停止状态;监测风机出口空气温、 湿度参数;监测新风过滤器两侧压差,以了解过滤器是否需要更换;监视 新风阀打开/关闭状态; (2)控制功能:控制风机启动/停止;控制空气热水换热器水侧调节阀, 使风机出口温度达到设定值;控制干蒸汽加湿器阀门,使冬季风机出口空 气湿度达到设定值。 (3)保护功能:冬季当某种原因造成热水温度降低或热水停供时,应停止风机,并关闭新风阀门,以防机组内温度过低冻裂空气水换热器;当热水 恢复正常供热时,应能启动风机,打开新风阀,恢复机组正常工作。 (4)集中管理功能:智能大楼各机组附近的DDC控制装置通过现场总线与相应的中央管理机相连,于是可以显示各机组启/停状态,送风温、湿度、各阀门状态值;发出任一机组的启/停控制信号,修改送风参数设定值;任一新风机组工作出现异常时,发出报警信号。 2)空调机组的监控空调机组的调节对象是相应区域的温、湿度,因此送入装置的输入信号还包括被调区域内的温湿度信号。当被调区域较大时,应 安装几组温、湿度测点,以各点测量信号的平均值或重要位置的测量只值 作为反馈信号;若被调区域与空调机组DDC 装置安装现场距离较远时,可

暖通空调毕业设计(论文)任务书

毕业设计(论文)任务书 毕业设计(论文)题目:某市某综合楼空调系统设计 系别能源与动力学院班级建环本121/122 学生姓名学号 指导教师职称 毕业设计(论文)进行地点:校内 任务下达时间: 2015年 12 月 24 日 起止日期:2016年 3 月1日起——至 2016年 6 月日止 教研室主任年月日批准 1、论文的原始资料及依据:

(一)题目来源:某市某综合楼建筑结构图 (二)设计主要技术参数 (1)土建资料 详见建筑图纸。 (2) 气象参数:根据本市的气象资料确定; (3)建筑参数: 外墙体结构:根据地区自行选定,如δ=370 m m红砖,内外抹灰20mm 屋面:根据地区自行选定,如200mm厚混凝土板加12.5mm厚加气混凝土保温层。 外窗:根据地区自行选定,如标准玻璃的单层钢窗,全部挂淡色窗帘,(4)室内空调设计参数:温度t n=26℃; 湿度φn=60%; 风速不大于0.3 m/s。 (5)照明容量: 40W/m2 (6)房间人数:0.5人/m2,群集系数0.92 (三)设计主要技术关键 正确进行空调负荷和新风量的计算,确定出冷气方案,合理地布置管道,并进行水力计算,合理选择及布置设备,做好气流组织。 2、设计(论文)主要内容及要求 通过本次设计使学生系统地掌握空调系统设计的主要方法和步骤,能根据实际情况合理确定空调方案,会计算空调系统的负荷量和新风负荷量,能合理布置管道和设备,了解空调设备的型式及用途,会进行设备的选型,合理进行气流组织,会计算水管、风道的阻力,选取水泵、风机等。使学生能把所学知识灵活运用到实际当中去,让理论与实际相结合,为学生毕业以后的工作打下坚实基础。 主要内容: 空调系统的设计 (1)、由建筑物所在地区确定室内外气象参数; 夏季室内外设计计算参数;室内温度、湿度、风速、新风量等参数。

暖通空调设计规范

一般规定第2.1.1条符合下列条件之一时,应设置空气调节: 一、对于高级民用建筑,当采用采暖通风达不到舒适性温湿度标准时; 二、对于生产厂房及辅助建筑物,当采用暖通风达不到工艺对室内温湿度要求时. 注:本条的"高级民用建筑",系指对室内温湿度、空气清洁程度和噪声标准等环境功能要求较严格,装备水平较高的建筑物,如国家级宾馆、会堂、剧院、图书馆、体育馆以及省、自治区、直辖市一级上述各类重点建筑物。 第2.1.2条在满足工艺要求的条件下,应尽量减少空气调节房间的面积和散热、散湿设备。当采用局部空气调节器或局部区域空气调节能满足要求时,不应采用全室性空气调节。 层高大于是10M的高大建筑物,条件允许时,可采用分层空气调节。 第2.1.3条室内保持正压的空气调节房间,其正压温度值不应大于50Pa(5mmH2O)。

第2.1.4条空气调节房间应尽量集中布置。室内温度和使用要求相近的空气调节房间,宜相邻布置。 第2.1.5条 围护结构最大传热系数[W/(m2.oC)][Kcal/m2.h.°c] 表2.5.1 注:1:表中内寺和楼板的有关数值,仅适用相邻房间的温差大于 3oC时. 2:确定围护结构的传热系数时,尚应符合本规范第3.1.4条的规定. 第2.1.6条 围护结构最小热情性指标表2.1.6

第2.1.7条 外墙、外墙朝向及所在层 次表2.1.7 注:1:室温允许波动范围小于或等于±0.5oc的空气调节房间,宜布置在室温允许波动范围较大的空气调节房间之中,当布置在单层建筑物内时,宜设通风屋顶. 2:本条和本规范第2.1.9条规定的"北向",适用于北纬23.5o以北的地区;北纬23.5o以南的地区,可相应地采用南向.

暖通空调方向毕业设计任务书

暖通空调方向毕业设计任务书 一、设计题目: XX市XX建筑通风空调工程设计。 二、设计任务和目的 学生根据所学基础理论和专业知识,结合实际工程,按照工程设计规范、标准、设计图集和有关参考资料,独立完成建筑所要求的工程设计,并通过设计过程,使学生系统地掌握暖通设计规则、方法、步骤,了解相关专业的配合关系,培养学生分析问题和解决问题的能力,为将来从事建筑环境与设备工程专业设计工作和施工、验收调试、运行管理和有关应用科学的研究及技术开发等工作,奠定可靠的基础。 三、原始资料 1.设计工程所在地区: ①长沙市,②益阳市,③其它地市 2.气象资料(从设计手册中查找): 包括空调室外计算干、湿球温度,冬季室外平均风速及主导风向等。 3.建筑资料 建筑平面图、立面图:图中包括建筑尺寸、维护结构及门窗做法、建筑层高、建筑用途等。 4.室内设计参数: 按照《采暖通风与空气调节设计规范》GB50019-2003要求及《公共建筑节能设计标准》GB500189-2005确定。 5.其他要求: 应根据当地的资源情况,优先考虑新能源的应用。 四、设计内容 1:设计冷热负荷的计算: 室内空调设计时,应按冷热负荷计算方法计算进行围护结构的热工计算,分别计算建筑的冷热负荷,其设计参数详见有关设计手册。 2:算出负荷后,确定系统形式。 3:进行风系统的水力计算。 4:根据所给设计条件以及总冷、热负荷和已经确定的设计方案、设备形式,选择风道

以及末端设备、冷热源设备等。 5:室内设计应包括室内设计参数,室内空调设计方案,设计方案应按照施工图的标准进行绘制,除满足设计规范外,还应符合施工验收规范的要求,尺寸线应完整、闭合。 6:设计应按照设计规范的要求,结合工程实际的需要,考虑防排烟、消防问题,在选择系统和设备时,还应综合考虑当地环保、节能的具体要求。 7:应进行相关方案的对比,得出对比结论。 五、设计要求 1.设计说明书 说明书应有封面、前言、目录、必要的计算过程;计算内容应给出其来源;在确定设计方案时应有一定的技术、经济比较(如设计方案的选择、设备的选型等)说明;内容应分章节,重复计算使用表格方式,参考资料应列出;设计说明书应不少于10000字。要求设计说明书文理通顺、书写工整、叙述清晰、内容完整、观点明确、论据正确,应将建筑概况和设计方案交待清楚。具体要求如下: (1)负荷计算要求有一典型房间的负荷计算采用手算; (2)风管水力计算、水管水力计算要求有一典型系统采用手算; (3)要求开始设计时,必须进行方案选择,应阐明清楚冷热源系统方案选择依据; (4)设计图纸必须与设计计算说明书相符合; (5)严禁抄袭;如若发现,做推迟答辩处理。 2.设计图纸 要求绘制6~8张折合1#图纸,包括计算机绘图和手绘图,其中手绘图纸至少1张(本次设计均为白纸图,不是硫酸图)。图纸应包括设计施工说明、主要设备材料明细表、系统图、冷热源平面、管网平面、剖面图、大样图、纵断图、水压图等。设计图纸要求图面整洁,图纸内容布置合理,图文全部采用工程字体,尽量选用标准图号,标题栏按照统一规定格式绘制,图例及绘图方法执行国家有关制图规范。具体要求如下: (1)图纸目录 1张 (2)设计施工说明 1张 (3)暖通风系统、水系统平面图根据需要(4)冷热源机房布置平面图、流程图等必须的系统图根据需要(5)必须的设备平破剖面图根据需要 六、设计期限

工商银行杭州支行办公楼空调工程设计暖通空调毕业设计论文

中国工商银行杭州支行办公楼空调工程设计

毕业设计(论文)原创性声明和使用授权说明 原创性声明 本人郑重承诺:所呈交的毕业设计(论文),是我个人在指导教师的指导下进行的研究工作及取得的成果。尽我所知,除文中特别加以标注和致谢的地方外,不包含其他人或组织已经发表或公布过的研究成果,也不包含我为获得及其它教育机构的学位或学历而使用过的材料。对本研究提供过帮助和做出过贡献的个人或集体,均已在文中作了明确的说明并表示了谢意。 作者签名:日期: 指导教师签名:日期: 使用授权说明 本人完全了解大学关于收集、保存、使用毕业设计(论文)的规定,即:按照学校要求提交毕业设计(论文)的印刷本和电子版本;学校有权保存毕业设计(论文)的印刷本和电子版,并提供目录检索与阅览服务;学校可以采用影印、缩印、数字化或其它复制手段保存论文;在不以赢利为目的前提下,学校可以公布论文的部分或全部内容。 作者签名:日期:

学位论文原创性声明 本人郑重声明:所呈交的论文是本人在导师的指导下独立进行研究所取得的研究成果。除了文中特别加以标注引用的内容外,本论文不包含任何其他个人或集体已经发表或撰写的成果作品。对本文的研究做出重要贡献的个人和集体,均已在文中以明确方式标明。本人完全意识到本声明的法律后果由本人承担。 作者签名:日期:年月日 学位论文版权使用授权书 本学位论文作者完全了解学校有关保留、使用学位论文的规定,同意学校保留并向国家有关部门或机构送交论文的复印件和电子版,允许论文被查阅和借阅。本人授权大学可以将本学位论文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本学位论文。 涉密论文按学校规定处理。 作者签名:日期:年月日 导师签名:日期:年月日

暖通空调水系统管路设计及管道阀门选型

暖通空调水系统管路设计及管道阀门选型 空调水系统的分类方法很多,按照管道的布置形式和工作原理,一般可归纳为以下几种主要类型: 按原理可分为:闭式循环和开式循环; 按供回水管道数量分为:两管制、三管制和四管制; 按供回水在管道内的流动关系分为:同程式和异程式; 按调节方式可分为:定水量和变水量。 水系统分类 1、闭式循环系统 定义:管路系统不与大气接触,在系统最高点设膨胀水箱并有排气和泄水装置的系统。当空调系统采用风机盘管、诱导器和水冷式表冷器冷却用时,冷水系统宜采用闭式系统。高层建筑宜采用闭式系统。 闭式循环的优点: ?管道与设备不易腐蚀; ?不需为提升高度的静水压力,循环水泵压力低,从而水泵功率小; ?由于没有贮水箱、不需重力回水、回水不需另设水泵等,因而投资省、系统简单。 2、开式循环系统 定义:管路之间有贮水箱(或水池)通大气。自流回水时,管路通大气的系统。空调系统采用喷水室冷却空气时,宜采用开式系统。 开式循环的优点:冷水箱有一定的蓄冷能力,可以减少开启冷冻机的时间,增加能量调节能力,且冷水温度波动可以小一些。

3、两管制水系统 定义:供冷系统和供暖系统采用相同的供水管和回水管,只有一供一回两根水管的系统。 两管制系统的优点:系统简单,施工方便。 缺点:不能同时供冷供暖。 4、三管制水系统 定义:分别设置供冷管路、供热管路、换热设备管路三根水管;其冷水与热水的回水管共用。 三管制系统的优点:三管制系统能够同时满足供冷和供热的要求。

缺点:比两管制复杂,投资也比较高,控制较复杂,且存在冷、热回水的混合损失。 5、四管制水系统 定义:冷水和热水的系统完全单独设置供水管和回水管,可以满足高质量空调环境的要求。 四管制系统的优点:能够同时满足供冷和供热的要求,并且配合末端设备能够实现室内温度和湿度精确控制的要求。 缺点:系统复杂,投资高。

暖通空调毕业设计(论文)任务书解答

毕业设计(论文)任务书 毕业设计(论文)题目:某市某综合楼空调系统设计 系别能源与动力学院班级建环本121/122 学生姓名___________________ 学号 ________________________ 指导教师________ 职称_______________________ 毕业设计(论文)进行地点:校内 _______________________ 任务下达时间:2015 年12 月24 日 起止日期:2016年3月1日起——至2016年6月日止 教研室主任_________________ 年月日批准 1、论文的原始资料及依据:

(一)题目来源:某市某综合楼建筑结构图 (二)设计主要技术参数 (1)土建资料 详见建筑图纸。 (2 )气象参数:根据本市的气象资料确定; (3 )建筑参数: 外墙体结构:根据地区自行选定,如S =370 m m红砖,内外抹灰20mm 屋面:根 据地区自行选定,如200mm 厚混凝土板加12.5mm 厚加气混凝土保温层。 外窗:根据地区自行选定,如标准玻璃的单层钢窗,全部挂淡色窗帘,(4)室内空调设计参数:温度t n=26C; 湿度? n=60% 风速不大于0.3 m/s 。 (5)照明容量:40W/m (6)房间人数:0.5人/m2,群集系数0.92 (三)设计主要技术关键 正确进行空调负荷和新风量的计算,确定出冷气方案,合理地布置管道,并进 行水力计算,合理选择及布置设备,做好气流组织。 2、设计(论文)主要内容及要求通过本次设计使学生系统地掌握空调系统设计的主 要方法和步骤,能根据实际情况合理确定空调方案,会计算空调系统的负荷量和新风负荷量,能合理布置管道和设备,了解空调设备的型式及用途,会进行设备的选型,合理进行气流组织,会计算水管、风道的阻力,选取水泵、风机等。使学生能把所学知识灵活运用到实际当中去,让理论与实际相结合,为学生毕业以后的工作打下坚实基础。 主要内容: 空调系统的设计 1)、由建筑物所在地区确定室内外气象参数; 夏季室内外设计计算参数;室内温度、湿度、风速、新风量等参数。 (2)、空调房间热湿负荷计算;

暖通空调课程设计

空气调节课程设计 说明书 课题名称:济南市某街道办公楼空调系统? 学生学号:? 131807011 ? ? 专业班级:建筑环境与能源应用工程 学生姓名:蔡世坤 学生成绩: ????????? ? 指导教师:?? 崔鹏 ?? 教师职称: 设计日期: _ 2017年1月________ 第一章设计资料 (3) 1.1设计题目 (3) 1.2设计基本参数 (3) 1.2.1室外参数 (3) 1.2.2 土建参数 (4) 第二章负荷计算 (5) 2.1负荷计算基本公式 (5) 2.1.1外墙、屋顶的瞬变传热的冷负荷 (5)

2.1.2内围护冷负荷 (6) 2.1.3外窗玻璃瞬变传导得热形成的的冷负荷 (6) 2.1.4玻璃窗日射得热形成的冷负荷 (7) 2.1.5设备散热冷负荷 (7) 2.1.6灯光照明散热形成的冷负荷 (7) 2.1.7人体散热形成的冷负荷 (8) 第三章空调方案确定和设备选型 (16) 第四章夏季空调过程设计 (20) 4.1送风状态确定 (18) 4.2汇总于下表 (18) 4.3送风量计算 (19) 4.4新风量计算 (20) 4.5总排风量的计算 (20) 第六章房间的气流组织计算 (22) 6.1气流组织计算 (22) 第七章布置风管、进行风管水力计算,水管水力计算 (24) 7.1风管的布置 (24) 7.2风道的设计及水力计算 (25) 参考文献 (27)

摘要 本设计是济南市某街道办公楼空调工程设计,根据此楼功能要求,本建筑需要夏季提供冷负荷。以长远利益为出发点,力求达到技术可靠,经济合理,节能环保、管理方便,功能调整的灵活性及使用安全可靠。在比较各种方案的可行性及水系统形式后,此工程设计采用风机盘管加独立新风系统;水系统采用一次泵、双管制系统:为满足整栋大楼需求,并且为了在运行过程中的节能,本设计冷热源采用风冷热泵模块机组。根据夏季空调计算负荷依次选择机组、末端设备、新风机组、风口,最后还要对空调系统的设备和管路采取消声、防振和保温等措施。 第一章设计资料 1.1设计题目 济南市某街道空调工程设计 1.2设计基本参数 1.2.1室外参数 纬度:28.13 度 经度:112.55度 海拔高度:68mAS 冬季大气压力:1018.3 pa 夏季大气压力:995.6 pa 冬季通风室外计算干球温度:3.5℃

暖通空调工程设计方法与系统论文

《暖通空调工程设计方法与系统》课程论文 学院:土木工程学院 专业:建环101 姓名: 学号:201011013 任课教师: 二〇一三年十二月

暖通空调设计方法的研究 邓玉梅 E-Mail: 摘要: 随着人们生活水平的提高,大家对室内环境品质也越来重视。空调虽然能够为人 们提供舒适的工作环境和生活环境,但是空调工作时所消耗的能源却是相当巨大的。本文 对暖通空调进行概述,对一些建筑采暖通风空调系统设计和系统特点进行研究,从而提出 暖通空调工程的优化设计方法。 关键词:暖通空调设计;优化;研究 Research on HV AC design method Deng Yumei Abstract: As people living standard rise, people are more attention to the indoor environment quality.Air conditioning even though it can provide people with a comfortable working and living environment, but the energy consumed by the air conditioning work is quite huge. In this paper, an overview of the HV AC, building on some of the HV AC system design and system characteristics were studied in order to optimize the design method proposed HV AC engineering. Keywords: HV ACdesigning; optimization; research 1. 引言 随着科学的进步,人们对于暖通系统设计问题不断进行研究和探讨,其中缘由不仅是因为新时期社会发展对于建筑工程的要求不断提高,同时也是为了满足人们所必需的物质生活条件。供暖环境以及条件的不同,会导致不一样的暖通系统的具体设计方案。在实际施工中,暖通系统的设计会受到各种因素制约,从而导致各种不同的问题。而许多的设计工作者缺乏对于问题的总结,可能会导致不同的设计方案出现同样的问题,或许这些问题的出现正是由于某些设计细节的欠妥导致。细节决定成败,希望通过本文能给各位暖通设计工作者以一定的启发,为行业的发展以及规范贡献自己的微薄的力量。 2. 暖通空调工程设计方法

暖通空调专业-毕业设计外文翻译

Refrigeration System Performance using Liquid-Suction Heat Exchangers S. A. Klein, D. T. Reindl, and K. BroWnell College of Engineering University of Wisconsin - Madison Abstract Heat transfer devices are provided in many refrigeration systems to exchange energy betWeen the cool gaseous refrigerant leaving the evaporator and Warm liquid refrigerant exiting the condenser. These liquid-suction or suction-line heat exchangers can, in some cases, yield improved system performance While in other cases they degrade system performance. Although previous researchers have investigated performance of liquid-suction heat exchangers, this study can be distinguished from the previous studies in three Ways. First, this paper identifies a neW dimensionless group to correlate performance impacts attributable to liquid-suction heat exchangers. Second, the paper extends previous analyses to include neW refrigerants. Third, the analysis includes the impact of pressure drops through the liquid-suction heat exchanger on system performance. It is shoWn that reliance on simplified analysis techniques can lead to inaccurate conclusions regarding the impact of liquid-suction heat exchangers on refrigeration system performance. From detailed analyses, it can be concluded that liquid-suction heat exchangers that have a minimal pressure loss on the loW pressure side are useful for systems using R507A, R134a, R12, R404A, R290, R407C, R600, and R410A. The liquid-suction heat exchanger is detrimental to system performance in systems using R22, R32, and R717. Introduction Liquid-suction heat exchangers are commonly installed in refrigeration systems With the intent of ensuring proper system operation and increasing system performance.Specifically, ASHRAE(1998) states that liquid-suction heat exchangers are effective in: 1) increasing the system performance 2) subcooling liquid refrigerant to prevent flash gas formation at inlets to expansion devices 3) fully evaporating any residual liquid that may remain in the liquid-suction prior to reaching the compressor(s) Figure 1 illustrates a simple direct-expansion vapor compression refrigeration system utilizing a liquid-suction heat exchanger. In this configuration, high temperature liquid leaving the heat rejection device (an evaporative condenser in this case) is subcooled prior to being throttled to the evaporator pressure by an expansion device such as a thermostatic expansion valve. The sink for subcooling

我国暖通空调工程设计中存在的问题及解决对策

我国暖通空调工程设计中存在的问题及解决对策摘要:暖通空调工程设计是暖通设计的重要组成部分,在暖通设计中起着至关重要的作用、而现阶段我国暖通空调工程设计面临着不少难题,涉及供暖、排风、噪声超标等方面。本文将从暖通空调工程设计的常见问题入手,为解决这些常见问题提供切实可行的建议。 关键词:暖通空调;难题;对策 abstract: hvac engineering design is an important part of hvac design, hvac design plays a vital role, but the present stage our country hvac engineering design is faced with many problems, involving heating, ventilation, noise exceeds the standard etc. this article from the hvac engineering design and analysis of the main problems, to solve these problems provide the feasible suggestions. key words: hvac; problem; countermeasure 中图分类号:tu83 在暖通空调工程设计领域中,存在的问题也随着暖通空调的大范围应用而呈现,为了最大限度地实现客户的利益,必须及时发现问题并采取积极的对策解决这些问题,达到投入较少资金,保证工程质量,提升工作效率的效果。 1供暖难题以及应对对策 1.1入口装置的难题及解决办法

暖通空调水系统的平衡调节

暖通空调水系统的平衡调节 摘要通过对集中供热和空调水系统流量变化的分析,阐述了选用静态水力平衡阀、动态平衡阀、动态平衡电动调节阀的原因,并介绍了这几种阀门的特性和控制机理,包括控制方式、方法。探讨了这几种阀门的调试过程,提出了暖通空调水系统调试的重要性。 关键词:水力失调静态水力平衡动态水力平衡压差控制调试方法 前言 集中供热和中央空调的水系统运行中,水力失调是常见的问题。水力系统的失调有两方面的含义:一是指虽然经过详细的水力计算并达到规定要求,但在实际运行后,各用户的流量与设计要求不符,这种水力失调是稳定的、根本性的。如不加以解决影响将始终存在。称之为稳态失调。二是指系统运行中,当一些用户的水流量改变时(关闭或调节时),会使其它用户的流量随之变化。这涉及到水力稳定性的概念。对其它用户影响小,则水力失调程度小,水力稳定性好,称之为动态(稳定性)失调。 产生水力失调的原因。管网水力失调的原因是多方面的,归纳起来主要有两种:(1)管网中流体流动的动力源(一般泵、重力差等)提供的能量与设计要求不符。例如:泵的型号,规格的变化及其性能参数的差异,动力电源的波动,流体自由液面差的变化等,导致管网中压头和流量偏离设计值。(2)管网的流动阻力特性发生变化,很多原因会导致管网阻抗发生变化。例如:在管路安装中,管材实际粗糙度的差别,焊接光滑程度的差别,存留于管道中泥沙、焊渣多少的差别,管路走向改变而使管长度的变化,弯头、三通等局部阻力部件的增减等,均会导致管网实际阻抗与设计值偏离。尤其是一些在管网设置的阀门,改变其开度即可能大大改变管网的阻力特性。 水力失调对管网系统运行会产生不利影响。管网系统往往是多个循环环路并联在一起的管路系统。各并联环路之间的水力工况相互影响,必然会引起其他环路的流量发生变化。如果某一管段的阀门开大或关小,必然导致管路流量的重新分配,即引起了水力工况的改变。当某些环路因发生水力失调而流量过小,如锅炉循环系统中水冷壁管路流量分配不均,使部分管束水流停滞则有可能发生爆管事故;在制冷机水循环系统中,蒸发器管束因此可能发生冻管事故。在供热空调系统中流体流量的变化使其负担输配的冷热量改变,即其水力失调必然会导致热力失调。在水力失调发生的同时,管网中的压力分布也发生了变化。在一些特殊情况下,局部管路和设备内的压力超过一定的限值,则可能使之破坏。 空调、采暖水系统中,由于水力失调导致流量分配不合理,区域流量过剩和区域流量不足,造成了某些区域冬天不热、夏天不冷的情况,系统输送冷、热量不合理,从而引起了能源的浪费,为了解决这个问题,提高水泵的扬程,但仍会产生冷热不均及更大的能源浪费。因此必须采用相应的调节阀门对系统的流量分配进行控制和调整。虽然通用阀门如截止阀、球阀等也具有一定的调节能力,但由于调节性能不好以及无法对调节后的流量进行测量和控制。近年来,在越来越多的暖通空调水系统,普遍采用了平衡阀系列产品对水系统的流量分配起到了积极地作用,使管网的运行得到了保证,特别是近年来变流量系统的控制。平衡阀系列产品包括:静态水力平衡阀、动态水力平衡阀等等,下面会和大家一起来分析一下,究竟什么系统需要什么样的水力平衡阀。 静态水力平衡阀 静态水力平衡阀的工作机理 静态水力平衡阀亦平衡阀、手动平衡阀、数字锁定平衡阀、双位调节阀等。它是通过改变阀芯与阀座的间隙(开度),来改变流经阀门的流动阻力以达到流量分配的目的,并配有流量、压差测量装置。其作用的对象是系统的阻力,能够将新的水量按照设计计算的比例平衡分配,各支路同时按比例增减,仍然满足当前气候需要下的部分负荷的流量需求,起到热平衡的作用。 静态水力平衡阀的使用技巧 控制单元的选择