南瑞继保网络103报文实例_3375

南瑞继保网络103报文实例_3375
南瑞继保网络103报文实例_3375

103网络规约报文过程表(不够完善需要补充,召波形,动作信息没有)

2008-10-08 09:04:57 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 02 00 2b 00 51 00 00 00 00 00 ff ff

装置心跳报文

2008-10-08 09:04:57 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff d9 01 2b 00 51 00 00 00 00 00 ff ff

装置心跳报文

2008-10-08 09:05:01 装置:RCS9621C-2.02 地址:336 TCP

装置主动上送遥测

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 03 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 02 00 fe f1 ff 0e

05 01 01 0c 02 01 18 00

05 02 01 0c 02 01 10 00

05 03 01 0c 02 01 10 00

05 04 01 0c 02 01 08 00

05 05 01 0c 02 01 10 00

05 06 01 0c 02 01 10 00

05 07 01 0c 02 01 00 00

05 08 01 0c 02 01 00 00

05 09 01 0c 02 01 08 00

05 0a 01 0c 02 01 08 00

05 0b 01 0c 02 01 a0 6a

05 0c 01 0c 02 01 00 00

05 0d 01 0c 02 01 00 00

05 0e 01 0c 02 01 e8 ff

2008-10-08 09:05:06 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1f 00 00 00 90 eb 00 00 01 f0 00 00 50 01 03 00 01 00 50 00 00 00 00 00 ff ff

15 81 2a 50 fe f1 40 01 09 00 01 召扰动数据表

2008-10-08 09:05:06 装置:RCS9621C-2.02 地址:336 TCP

90 eb f2 00 00 00 90 eb 00 00 50 01 00 00 01 f0 04 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 2a 00 fe f1 40 9c

09 00 01 03 01 01 2a

09 01 01 03 01 01 01

09 02 01 03 01 01 02

09 03 01 03 01 01 03

09 04 01 03 01 01 04

09 05 01 03 01 01 a6

09 06 01 03 01 01 80

09 07 01 03 01 01 81

09 08 01 03 01 01 82

09 09 01 03 01 01 08

09 0a 01 11 02 01 c6 69

09 0b 01 11 02 01 c6 3f

09 0c 01 11 02 01 c6 40

09 0d 01 11 02 01 c6 41

09 0e 01 11 02 01 c6 35

09 0f 01 11 02 01 c6 36

09 10 01 11 02 01 c6 37

09 11 01 11 02 01 c6 46

09 12 01 11 02 01 c6 47

09 13 01 11 02 01 c6 3e

09 14 01 11 02 01 c6 38

09 15 01 11 02 01 c6 39

09 16 01 11 02 01 c6 3a

09 17 01 11 02 01 c6 3b

09 18 01 11 02 01 c6 3c

09 19 01 11 02 01 c6 3d

09 1a 01 11 02 01 c6 66

09 1b 01 11 02 01 c6 6a

2008-10-08 09:05:06 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 01 f0 05 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 2a 00 fe f1 40 4e

09 1c 01 11 02 01 c6 61

09 1d 01 11 02 01 c6 62

09 1e 01 11 02 01 c6 bd

09 1f 01 11 02 01 c6 be

09 20 01 11 02 01 c6 bc

09 21 01 11 02 01 c6 bb

09 22 01 11 02 01 c6 92

09 23 01 11 02 01 c6 89

09 24 01 11 02 01 c6 94

09 25 01 11 02 01 c6 98

09 26 01 11 02 01 c6 93

09 27 01 11 02 01 c6 97

09 28 01 11 02 01 c6 16

09 29 01 11 02 01 c6 15

2008-10-08 09:05:07 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 06 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:07 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff da 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:11 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 07 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e

05 01 01 0c 02 01 18 00

05 02 01 0c 02 01 10 00

05 03 01 0c 02 01 08 00

05 04 01 0c 02 01 08 00

05 05 01 0c 02 01 08 00

05 06 01 0c 02 01 10 00

05 07 01 0c 02 01 00 00

05 08 01 0c 02 01 00 00

05 09 01 0c 02 01 08 00

05 0a 01 0c 02 01 08 00

05 0b 01 0c 02 01 a0 6a

05 0c 01 0c 02 01 00 00

05 0d 01 0c 02 01 00 00

05 0e 01 0c 02 01 e8 ff

2008-10-08 09:05:17 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 08 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:17 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff db 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:22 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 09 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00

05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:05:27 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0a 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:27 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff dc 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:32 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0b 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:05:37 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0c 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:38 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff dd 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:42 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0d 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:05:47 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0e 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:48 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff de 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:53 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0f 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 08 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff

2008-10-08 09:05:58 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 10 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:05:58 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff df 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:03 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 11 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 08 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 08 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:06:08 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 12 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:08 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff e0 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 01 f0 00 00 50 01 0a 00 01 00 50 00 00 00 00 00 ff ff

15 81 09 50 fe f5 09 00 总召唤

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb 18 01 00 00 90 eb 00 00 50 01 00 00 01 f0 13 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 09 15

03 01 01 12 06 01 02 24 4f 2a 14 0f

03 02 01 12 06 01 01 24 4f 2a 14 0f

03 03 01 12 06 01 01 24 4f 2a 14 0f

03 04 01 12 06 01 01 24 4f 2a 14 0f

03 05 01 12 06 01 01 24 4f 2a 14 0f

03 06 01 12 06 01 02 24 4f 2a 14 0f

03 07 01 12 06 01 01 24 4f 2a 14 0f

03 08 01 12 06 01 01 24 4f 2a 14 0f

03 09 01 12 06 01 01 24 4f 2a 14 0f

03 0a 01 12 06 01 01 24 4f 2a 14 0f

03 0b 01 12 06 01 01 24 4f 2a 14 0f

03 0c 01 12 06 01 01 24 4f 2a 14 0f

03 0e 01 12 06 01 01 24 4f 2a 14 0f

03 0f 01 12 06 01 01 24 4f 2a 14 0f

03 10 01 12 06 01 01 24 4f 2a 14 0f

03 11 01 12 06 01 01 24 4f 2a 14 0f

03 12 01 12 06 01 01 24 4f 2a 14 0f

03 13 01 12 06 01 01 24 4f 2a 14 0f

03 14 01 12 06 01 01 24 4f 2a 14 0f

03 15 01 12 06 01 01 24 4f 2a 14 0f

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb c4 00 00 00 90 eb 00 00 50 01 00 00 01 f0 14 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 09 0e

0a 01 01 12 06 01 01 24 4f 2a 14 0f

0a 02 01 12 06 01 01 24 4f 2a 14 0f

0a 03 01 12 06 01 01 24 4f 2a 14 0f

0a 04 01 12 06 01 01 24 4f 2a 14 0f

0a 05 01 12 06 01 01 24 4f 2a 14 0f

0a 06 01 12 06 01 01 24 4f 2a 14 0f

0a 07 01 12 06 01 01 24 4f 2a 14 0f

0a 08 01 12 06 01 01 24 4f 2a 14 0f

0a 09 01 12 06 01 01 24 4f 2a 14 0f

0a 0a 01 12 06 01 01 24 4f 2a 14 0f

0a 0b 01 12 06 01 01 24 4f 2a 14 0f

0a 0c 01 12 06 01 01 24 4f 2a 14 0f

0a 0d 01 12 06 01 01 24 4f 2a 14 0f

0a 0e 01 12 06 01 01 24 4f 2a 14 0f

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb f4 00 00 00 90 eb 00 00 50 01 00 00 01 f0 15 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 09 12

04 01 01 12 06 01 01 24 4f 2a 14 0f

04 02 01 12 06 01 02 24 4f 2a 14 0f

04 03 01 12 06 01 01 24 4f 2a 14 0f

04 04 01 12 06 01 02 24 4f 2a 14 0f

04 05 01 12 06 01 01 24 4f 2a 14 0f

04 06 01 12 06 01 01 24 4f 2a 14 0f

04 07 01 12 06 01 01 24 4f 2a 14 0f

04 08 01 12 06 01 01 24 4f 2a 14 0f

04 09 01 12 06 01 01 24 4f 2a 14 0f

04 0b 01 12 06 01 01 24 4f 2a 14 0f

04 0c 01 12 06 01 01 24 4f 2a 14 0f

04 0d 01 12 06 01 01 24 4f 2a 14 0f

04 0e 01 12 06 01 01 24 4f 2a 14 0f

04 0f 01 12 06 01 01 24 4f 2a 14 0f

04 10 01 12 06 01 01 24 4f 2a 14 0f

04 11 01 12 06 01 01 24 4f 2a 14 0f

04 12 01 12 06 01 01 24 4f 2a 14 0f

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb 00 01 00 00 90 eb 00 00 50 01 00 00 01 f0 16 00 2b 00 51 00 00 00 00

00 ff ff 0a 81 09 00 fe f5 09 13 0b 01 01 12 06 01 02 24 4f 2a 14 0f 0b 02

01 12 06 01 02 24 4f 2a 14 0f 0b 03 01 12 06 01 02 24 4f 2a 14 0f 0b 04 01 12 06 01 02 24 4f 2a 14 0f 0b 05 01 12 06 01 02 24 4f 2a 14 0f 0b 06 01 12 06 01 02 24 4f 2a 14 0f 0b 07 01 12 06 01 01 24 4f 2a 14 0f 0b 08 01 12 06

01 02 24 4f 2a 14 0f 0b 09 01 12 06 01 02 24 4f 2a 14 0f 0b 0a 01 12 06 01

02 24 4f 2a 14 0f 0b 0b 01 12 06 01 02 24 4f 2a 14 0f 0b 0c 01 12 06 01 02 24 4f 2a 14 0f 0b 0d 01 12 06 01 02 24 4f 2a 14 0f 0b 0e 01 12 06 01 02 24 4f 2a 14 0f 0b 0f 01 12 06 01 02 24 4f 2a 14 0f 0b 10 01 12 06 01 02 24 4f 2a 14 0f 0b 11 01 12 06 01 02 24 4f 2a 14 0f 0b 12 01 12 06 01 02 24 4f 2a 14 0f 0b 13 01 12 06 01 02 24 4f 2a 14 0f

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb 5c 01 00 00 90 eb 00 00 50 01 00 00 01 f0 17 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 09 14

02 01 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 02 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 03 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 04 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 05 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 06 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 07 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 08 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 09 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 0a 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 0b 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 0c 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 0d 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 0e 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 0f 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 10 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 11 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 12 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 13 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

02 14 01 13 0a 01 01 00 00 00 00 24 4f 2a 14 0f

2008-10-08 09:06:09 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1b 00 00 00 90 eb 00 00 50 01 00 00 01 f0 18 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 0a 00 fe f5 09

2008-10-08 09:06:13 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 19 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 08 00 05 03 01 0c 02 01 08 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:06:18 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1a 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:19 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff e1 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:24 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1b 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 08 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff

2008-10-08 09:06:28 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1c 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:28 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff e2 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:34 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1d 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00

05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:06:38 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1e 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:39 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff e3 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:06:44 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1f 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:06:51 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 20 00 2b 00 51 00 00 00 00 00 ff ff

调定值/修改定值/遥控合/遥控分/变位遥信(soe)/变化遥测

2008-10-08 09:22:57 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 36 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:22:57 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 43 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1f 00 00 00 90 eb 00 00 01 f0 00 00 50 01 8a 00 01 00 50 00 00 00 00 00 ff ff 15 81 2a 50 fe f1 3b 01 01 0001召唤定值(召唤01组定值)

2008-10-08 09:23:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb f5 00 00 00 90 eb 00 00 50 01 00 00 01 f0 37 01 2b 00 51 00 00 00 00

00 ff ff 0a 81 2a 00 fe f1 3b 96

01 00 01 03 01 01 43

01 01 01 07 04 01 00 00 20 41

01 02 01 07 04 01 00 00 8c 42

01 03 01 07 04 01 00 00 80 41

01 04 01 07 04 01 00 00 00 41

01 05 01 07 04 01 00 00 e0 40

01 06 01 07 04 01 00 00 00 41

01 07 01 07 04 01 00 00 c0 40

01 08 01 07 04 01 00 00 00 41

01 09 01 07 04 01 00 00 c0 40

01 0a 01 07 04 01 00 00 c0 40

01 0b 01 07 04 01 00 00 a0 40

01 0c 01 07 04 01 00 00 40 40

01 0d 01 07 04 01 00 00 40 42

01 0e 01 07 04 01 00 00 00 41

01 0f 01 07 04 01 00 00 c0 40

01 10 01 07 04 01 00 00 a0 40

01 11 01 07 04 01 00 00 40 40

01 12 01 07 04 01 00 00 8c 42

01 13 01 07 04 01 cd cc cc 3d

01 14 01 07 04 01 00 00 80 3f

01 15 01 07 04 01 00 00 00 40

2008-10-08 09:23:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb f5 00 00 00 90 eb 00 00 50 01 00 00 01 f0 38 01 2b 00 51 00 00 00 00

00 ff ff 0a 81 2a 00 fe f1 3b d7

01 16 01 07 04 01 00 00 80 3f

01 17 01 07 04 01 00 00 80 3f

01 18 01 07 04 01 cd cc cc 3d

01 19 01 07 04 01 00 00 80 3f

01 1a 01 07 04 01 00 00 80 3f

01 1b 01 07 04 01 00 00 00 40

01 1c 01 07 04 01 00 00 40 40

01 1d 01 07 04 01 00 00 80 3f

01 1e 01 07 04 01 00 00 80 3f

01 1f 01 07 04 01 00 00 00 40

01 20 01 07 04 01 00 00 40 40

01 21 01 07 04 01 00 00 80 3f

01 22 01 07 04 01 00 00 80 3f

01 23 01 07 04 01 00 00 80 3f

01 24 01 07 04 01 00 00 80 3f

01 25 01 07 04 01 00 00 80 3f

01 26 01 02 13 01 ff ff 07

01 27 01 02 13 01 00 00 00

01 28 01 02 13 01 00 00 00

01 29 01 02 13 01 00 00 00

01 2a 01 03 01 01 01

01 2b 01 03 01 01 00

01 2c 01 03 01 01 01

2008-10-08 09:23:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb b6 00 00 00 90 eb 00 00 50 01 00 00 01 f0 39 01 2b 00 51 00 00 00 00

00 ff ff 0a 81 2a 00 fe f1 3b 16

01 2d 01 03 01 01 01

01 2e 01 03 01 01 01

01 2f 01 03 01 01 01

01 30 01 03 01 01 01

01 31 01 03 01 01 01

01 32 01 03 01 01 01

01 33 01 03 01 01 01

01 34 01 03 01 01 01

01 35 01 03 01 01 01

01 36 01 03 01 01 01

01 37 01 03 01 01 01

01 38 01 03 01 01 01

01 39 01 03 01 01 01

01 3a 01 03 01 01 01

01 3b 01 03 01 01 01

01 3c 01 03 01 01 01

01 3d 01 03 01 01 01

01 3e 01 03 01 01 01

01 3f 01 03 01 01 01

01 40 01 03 01 01 01

01 41 01 03 01 01 01

01 42 01 03 01 01 01

2008-10-08 09:23:05 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 3a 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e

05 01 01 0c 02 01 18 00

05 02 01 0c 02 01 10 00

05 03 01 0c 02 01 10 00

05 04 01 0c 02 01 08 00

05 05 01 0c 02 01 10 00

05 06 01 0c 02 01 10 00

05 07 01 0c 02 01 00 00

05 08 01 0c 02 01 00 00

05 09 01 0c 02 01 08 00

05 0a 01 0c 02 01 08 00

05 0b 01 0c 02 01 a0 6a

05 0c 01 0c 02 01 00 00

05 0d 01 0c 02 01 00 00

05 0e 01 0c 02 01 e8 ff (遥测)

2008-10-08 09:23:07 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 3b 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:07 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 44 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:14 装置:RCS9621C-2.02 地址:336 TCP

90 eb 26 00 00 00 90 eb 00 00 01 f0 00 00 50 01 8c 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe f9 3c 01 01 01 01 07 04 01 00 00 70 41 (修改定值,组号为01条目为01)

2008-10-08 09:23:14 装置:RCS9621C-2.02 地址:336 TCP

90 eb 26 00 00 00 90 eb 00 00 50 01 00 00 01 f0 3c 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 2c 00 fe f9 3c 01 01 01 01 07 04 01 00 00 70 41 (修改定值响应)

2008-10-08 09:23:14 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 01 f0 00 00 50 01 8d 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe fa 05 40 (修改定值执行)

2008-10-08 09:23:14 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 50 01 00 00 01 f0 3d 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 28 00 fe fa 05 40 (修改定值执行确认)

2008-10-08 09:23:14 装置:RCS9621C-2.02 地址:336 TCP

90 eb 34 00 00 00 90 eb 00 00 50 01 00 00 ff ff 3e 01 2b 00 51 00 00 00 00 00 ff ff

0a 81 01 00 fe f1 ff 02

03 0f 01 12 06 01 02 bb 63 3b 14 0f

03 10 01 12 06 01 02 bb 63 3b 14 0f (变化遥信,组号为03 条目为0fHex 及10Hex 的两个遥信)

2008-10-08 09:23:16 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 3f 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff (遥测)

2008-10-08 09:23:18 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 40 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:26 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 41 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10

00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff (遥测)

2008-10-08 09:23:27 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 01 f0 00 00 50 01 90 00 01 00 50 00 00 00 00 00 ff ff

0a 81 28 50 fe f9 3d 01 07 01 01 09 01 01 02 (遥控合命令,组号为07 条目为01,双点信息,遥控选择)

2008-10-08 09:23:27 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 50 01 00 00 01 f0 42 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 2c 00 fe f9 3d 01 07 01 01 09 01 01 02(遥控合选择确认) 2008-10-08 09:23:27 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 01 f0 00 00 50 01 91 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe fa 3e 01 07 01 01 09 01 01 02 (遥控合执行)

2008-10-08 09:23:27 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 43 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:27 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 46 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:29 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 50 01 00 00 01 f0 44 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 28 00 fe fa 3e 01 07 01 01 09 01 01 02 (遥控合执行确认) 2008-10-08 09:23:29 装置:RCS9621C-2.02 地址:336 TCP

90 eb 34 00 00 00 90 eb 00 00 50 01 00 00 ff ff 45 01 2b 00 51 00 00 00 00

00 ff ff 0a 81 01 00 fe f1 ff 02 0a 01 01 12 06 01 01 70 9b 3b 14 0f 0a 03

01 12 06 01 02 72 9b 3b 14 0f

2008-10-08 09:23:29 装置:RCS9621C-2.02 地址:336 TCP

90 eb 34 00 00 00 90 eb 00 00 50 01 00 00 ff ff 46 01 2b 00 51 00 00 00 00 00 ff ff

0a 81 01 00 fe f1 ff 02

0a 02 01 12 06 01 02 8b 9b 3b 14 0f (上送变位信息带时标,组号为10,条目为2) 04 01 01 12 06 01 02 8b 9b 3b 14 0f (上送变位信息带时标,组号为4,条目为1) 2008-10-08 09:23:36 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 01 f0 00 00 50 01 92 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe f9 3f 01 07 01 01 09 01 01 01 (遥控分命令,组号为07 条目为01,双点信息,遥控选择)

2008-10-08 09:23:36 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 50 01 00 00 01 f0 47 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 2c 00 fe f9 3f 01 07 01 01 09 01 01 01 (遥控分选择确认)

2008-10-08 09:23:36 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 01 f0 00 00 50 01 94 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe fa 40 01 07 01 01 09 01 01 01 (遥控分执行)

2008-10-08 09:23:36 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 50 01 00 00 01 f0 48 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 28 00 fe fa 40 01 07 01 01 09 01 01 01 (遥控分执行确认) 2008-10-08 09:23:39 装置:RCS9621C-2.02 地址:336 TCP

90 eb 28 00 00 00 90 eb 00 00 50 01 00 00 ff ff 49 01 2b 00 51 00 00 00 00 00 ff ff

0a 81 01 00 fe f1 ff 01

0a 02 01 12 06 01 01 c5 b9 3b 14 0f (变位信息)

2008-10-08 09:23:39 装置:RCS9621C-2.02 地址:336 TCP

90 eb 40 00 00 00 90 eb 00 00 50 01 00 00 ff ff 4a 01 2b 00 51 00 00 00 00 00 ff ff

0a 81 01 00 fe f1 ff 03

0a 03 01 12 06 01 01 c8 b9 3b 14 0f (变位信息,时标里面没有年,时间为15号20点59分47560毫秒)

0a 01 01 12 06 01 02 ce b9 3b 14 0f (变位信息)

04 01 01 12 06 01 01 ce b9 3b 14 0f (变位信息)

2008-10-08 09:23:39 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 4b 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 08 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff (遥测)

2008-10-08 09:23:39 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 4c 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:47 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 4d 01 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 20 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:23:48 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 4e 01 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:23:48 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 48 02 2b 00 51 00 00 00 00 00 ff ff

初始化/遥控失败(就地位置)/遥控成功

2008-10-08 09:26:42 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 59 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:26:51 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 5a 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:27:01 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 00 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:27:02 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 5b 02 2b 00 51 00 00 00 00 00 ff ff

………………

2008-10-08 09:28:46 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 01 f0 00 00 50 01 06 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe f9 42 01 07 01 01 09 01 01 02 (遥控合选择)

2008-10-08 09:28:49 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0c 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 20 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:28:49 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 50 01 00 00 01 f0 0d 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 29 00 fe f9 42 01 07 01 01 09 01 01 02 (遥控合否定确认) 2008-10-08 09:28:54 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 66 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:28:57 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0e 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:28:57 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 0f 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00

05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:29:00 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 01 f0 00 00 50 01 09 00 01 00 50 00 00 00 00 00 ff ff 15 81 09 50 fe f5 17 00 (总查询)

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 10 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 67 02 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb 18 01 00 00 90 eb 00 00 50 01 00 00 01 f0 11 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 17 15

03 01 01 12 06 01 01 4f 36 05 15 0f

03 02 01 12 06 01 01 4f 36 05 15 0f

03 03 01 12 06 01 01 4f 36 05 15 0f

03 04 01 12 06 01 01 4f 36 05 15 0f

03 05 01 12 06 01 01 4f 36 05 15 0f

03 06 01 12 06 01 01 4f 36 05 15 0f

03 07 01 12 06 01 01 4f 36 05 15 0f

03 08 01 12 06 01 01 4f 36 05 15 0f

03 09 01 12 06 01 01 4f 36 05 15 0f

03 0a 01 12 06 01 01 4f 36 05 15 0f

03 0b 01 12 06 01 01 4f 36 05 15 0f

03 0c 01 12 06 01 01 4f 36 05 15 0f

03 0d 01 12 06 01 01 4f 36 05 15 0f

03 0e 01 12 06 01 01 4f 36 05 15 0f

03 0f 01 12 06 01 01 4f 36 05 15 0f

03 10 01 12 06 01 01 4f 36 05 15 0f

03 11 01 12 06 01 01 4f 36 05 15 0f

03 12 01 12 06 01 01 4f 36 05 15 0f

03 13 01 12 06 01 01 4f 36 05 15 0f

03 14 01 12 06 01 01 4f 36 05 15 0f

03 15 01 12 06 01 01 4f 36 05 15 0f (上送组号为3的所有信息)

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb c4 00 00 00 90 eb 00 00 50 01 00 00 01 f0 12 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 17 0e

0a 01 01 12 06 01 02 4f 36 05 15 0f

0a 03 01 12 06 01 01 4f 36 05 15 0f

0a 04 01 12 06 01 01 4f 36 05 15 0f

0a 05 01 12 06 01 01 4f 36 05 15 0f

0a 06 01 12 06 01 01 4f 36 05 15 0f

0a 07 01 12 06 01 01 4f 36 05 15 0f

0a 08 01 12 06 01 01 4f 36 05 15 0f

0a 09 01 12 06 01 01 4f 36 05 15 0f

0a 0a 01 12 06 01 01 4f 36 05 15 0f

0a 0b 01 12 06 01 01 4f 36 05 15 0f

0a 0c 01 12 06 01 01 4f 36 05 15 0f

0a 0d 01 12 06 01 01 4f 36 05 15 0f

0a 0e 01 12 06 01 01 4f 36 05 15 0f (上送组号为10的所有信息)

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb f4 00 00 00 90 eb 00 00 50 01 00 00 01 f0 13 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 17 12

04 01 01 12 06 01 01 4f 36 05 15 0f

04 02 01 12 06 01 01 4f 36 05 15 0f

04 03 01 12 06 01 01 4f 36 05 15 0f

04 04 01 12 06 01 02 4f 36 05 15 0f

04 05 01 12 06 01 01 4f 36 05 15 0f

04 06 01 12 06 01 01 4f 36 05 15 0f

04 07 01 12 06 01 01 4f 36 05 15 0f

04 08 01 12 06 01 01 4f 36 05 15 0f

04 09 01 12 06 01 01 4f 36 05 15 0f

04 0a 01 12 06 01 01 4f 36 05 15 0f

04 0b 01 12 06 01 01 4f 36 05 15 0f

04 0c 01 12 06 01 01 4f 36 05 15 0f

04 0d 01 12 06 01 01 4f 36 05 15 0f

04 0e 01 12 06 01 01 4f 36 05 15 0f

04 0f 01 12 06 01 01 4f 36 05 15 0f

04 10 01 12 06 01 01 4f 36 05 15 0f

04 11 01 12 06 01 01 4f 36 05 15 0f

04 12 01 12 06 01 01 4f 36 05 15 0f (上送组号为4的所有信息)

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb 00 01 00 00 90 eb 00 00 50 01 00 00 01 f0 14 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 17 13

0b 01 01 12 06 01 02 4f 36 05 15 0f

0b 02 01 12 06 01 02 4f 36 05 15 0f

0b 04 01 12 06 01 02 4f 36 05 15 0f

0b 05 01 12 06 01 02 4f 36 05 15 0f

0b 06 01 12 06 01 02 4f 36 05 15 0f

0b 07 01 12 06 01 01 4f 36 05 15 0f

0b 08 01 12 06 01 02 4f 36 05 15 0f

0b 09 01 12 06 01 02 4f 36 05 15 0f

0b 0a 01 12 06 01 02 4f 36 05 15 0f

0b 0b 01 12 06 01 02 4f 36 05 15 0f

0b 0c 01 12 06 01 02 4f 36 05 15 0f

0b 0d 01 12 06 01 02 4f 36 05 15 0f

0b 0e 01 12 06 01 02 4f 36 05 15 0f

0b 0f 01 12 06 01 02 4f 36 05 15 0f

0b 10 01 12 06 01 02 4f 36 05 15 0f

0b 11 01 12 06 01 02 4f 36 05 15 0f

0b 12 01 12 06 01 02 4f 36 05 15 0f

0b 13 01 12 06 01 02 4f 36 05 15 0f (上送组号为11的所有信息)

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb 5c 01 00 00 90 eb 00 00 50 01 00 00 01 f0 15 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 09 00 fe f5 17 14

02 01 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 02 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 03 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 04 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 05 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 06 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 07 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 08 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 09 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 0a 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 0b 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 0c 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 0d 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 0e 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 0f 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 10 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 11 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 12 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 13 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f

02 14 01 13 0a 01 01 00 00 00 00 4f 36 05 15 0f (上送组号为2的所有信息)

2008-10-08 09:29:04 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1b 00 00 00 90 eb 00 00 50 01 00 00 01 f0 16 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 0a 00 fe f5 17 (总查询结束)

………………………………………………

2008-10-08 09:29:17 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1d 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:29:19 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1f 00 00 00 90 eb 00 00 01 f0 00 00 50 01 0c 00 01 00 50 00 00 00 00 00 ff ff 15 81 2a 50 fe f1 18 01 06 00 01 (召唤组值,组号06)

2008-10-08 09:29:23 装置:RCS9621C-2.02 地址:336 TCP

90 eb 4f 00 00 00 90 eb 00 00 50 01 00 00 01 f0 1e 00 2b 00 51 00 00 00 00 00 ff ff

0a 81 2a 00 fe f1 18 05

06 00 01 03 01 01 05

06 01 01 c9 05 01 00 00 00 00 1c

06 02 01 c9 05 01 00 00 00 00 1d

06 03 01 c9 05 01 00 00 00 00 1e

06 04 01 c9 05 01 00 00 00 00 1f

2008-10-08 09:29:24 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 1f 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 09:29:24 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 69 02 2b 00 51 00 00 00 00 00 ff ff

………………………………….

2008-10-08 16:24:20 装置:RCS9621C-2.02 地址:336 TCP

90 eb 26 00 00 00 90 eb 00 00 01 f0 00 00 50 01 19 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe f9 3a 01 01 01 01 07 04 01 00 00 a0 41 (修改定值选择)

2008-10-08 16:24:20 装置:RCS9621C-2.02 地址:336 TCP

90 eb 26 00 00 00 90 eb 00 00 50 01 00 00 01 f0 3d 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 2c 00 fe f9 3a 01 01 01 01 07 04 01 00 00 a0 41 (修改定值选择确认)

2008-10-08 16:24:20 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 01 f0 00 00 50 01 1a 00 01 00 50 00 00 00 00

00 ff ff 0a 81 28 50 fe fa 30 40 (修改定值执行)

2008-10-08 16:24:20 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 50 01 00 00 01 f0 3e 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 28 00 fe fa 30 40 (修改定值执行确认)

2008-10-08 16:24:20 装置:RCS9621C-2.02 地址:336 TCP

90 eb 34 00 00 00 90 eb 00 00 50 01 00 00 ff ff 3f 00 2b 00 51 00 00 00 00

00 ff ff 0a 81 01 00 fe f1 ff 02 03 0f 01 12 06 01 02 45 4c 18 10 08 03 10

01 12 06 01 02 45 4c 18 10 08

2008-10-08 16:24:22 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 40 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 16:24:22 装置:RCS9621C-2.02 地址:336 UDP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff f4 0b 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 16:24:23 装置:RCS9621C-2.02 地址:336 TCP

90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 41 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 20 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 16:24:28 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 01 f0 00 00 50 01 1c 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe f9 3b 01 01 32 01 03 01 01 00 (修改定值选择) 2008-10-08 16:24:28 装置:RCS9621C-2.02 地址:336 TCP

90 eb 23 00 00 00 90 eb 00 00 50 01 00 00 01 f0 42 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 2c 00 fe f9 3b 01 01 32 01 03 01 01 00 (修改定值选择确认) 2008-10-08 16:24:28 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 01 f0 00 00 50 01 1d 00 01 00 50 00 00 00 00 00 ff ff 0a 81 28 50 fe fa 30 40 (修改定值执行)

2008-10-08 16:24:28 装置:RCS9621C-2.02 地址:336 TCP

90 eb 1c 00 00 00 90 eb 00 00 50 01 00 00 01 f0 43 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 28 00 fe fa 30 40 (修改定值执行确认)

2008-10-08 16:24:28 装置:RCS9621C-2.02 地址:336 TCP

90 eb 34 00 00 00 90 eb 00 00 50 01 00 00 ff ff 44 00 2b 00 51 00 00 00 00

00 ff ff 0a 81 01 00 fe f1 ff 02 03 0f 01 12 06 01 02 35 69 18 10 08 03 10

01 12 06 01 02 35 69 18 10 08

2008-10-08 16:24:32 装置:RCS9621C-2.02 地址:336 TCP

90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 45 00 2b 00 51 00 00 00 00 00 ff ff

2008-10-08 16:24:33 装置:RCS9621C-2.02 地址:336 UDP

103报文详细解析

103规约转出软件实验报告(改进版) 1、初始化 ●主站发: 10 40 04 44 16 目的:给地址为04的装置发复位通信单元命令。 10 //固定帧长起始字符 04 // 44 16 子站回答:10 20 04 24 16 目的: ACD位置1,表明子站向主站请求1级数据上送。 ●主站发: 10 7a 04 7e 16 目的:向地址为04的装置发请求1级数据命令。 子站回答:68 15 15 68 28 04 05 81 04 04 b2 03 03 c4 cf c8 f0 bc cc b1 a3 01 00 01 00 9b 16 (ASDU5,CON=28,COT=4) 68 //启动字符 15 //报文长度 15 //报文长度 68 //启动字符 //控制域, 地址域, 类型标识, 可变结构限定词, 传送原因, 公共地址 28 04 05 81 04 04 //功能类型,信息序号, 兼容级别,8个ASCII b2 03 03 c4 cf c8 f0 bc cc b1 a3 //4个自由赋值 01 00 01 00 /////////////////////////////////////////////////// //连路用户数据 9b //校验和 16 //结束字符 (ASDU5,CON=28,COT=4) 80 00 目的:子站以ASDU5(复位通信单元)响应主站的召唤。并ACD位置1,表明子站继续向主站请求1级数据上送。 ●主站发:10 5a 04 5e 16 目的:向地址为04的装置发请求1级数据命令。 子站回答:68 15 15 68 08 04 05 81 05 04 b2 04 03 c4 cf c8 f0 bc cc b1 a3 01 00 01 00 7d 16 (ASDU5,CON = 08,COT=5) 目的:子站以ASDU5(启动/重新启动)响应主站的召唤。ACD 位置回0。 后面跟随时间同步和总查询。 结果分析:程序的行为完全正确。 2、对时 时间同步过程分两种情况: 1)ASDU6 可以发送无回答方式,其地址为255。

siemensT103规约使用指南参考解析

一、DL/T667-1999(IEC60870-5-103) 通信规约 1. 通信接口 1.1 接口标准:RS232、RS485、光纤。 1.2 通信格式:异步,1位起始位,8位数据位,1位偶校验位,1位停止位。字符和字节传输由低至高。线路 空闲状态为1。 1.3 通信速率:可变。默认9600 1.4 通信方式:主从一对多,Polling方式。 2. 报文格式 60870-5-103通信规约有固定帧长报文和可变帧长报文两种报文格式,前者主要用于传送“召唤、命令、确认、应答”等信息,后者主要用于传送“命令”和“数据”等信息。 2.1 固定帧长报文 10 H 启动字符 CODE 控制域 ADDR 地址域 C S 代码和 16 H 结束字符 注:代码和=控制域+地址域(不考虑溢出位,即256模和) 2.2 68 H ————启动字符1(1byte) Length ————长度(1byte) Length ————长度(重复)(1byte) 68 H ————启动字符2(重复)(1byte) CODE ————控制域(1byte) ADDR ————地址域(1byte) ASDU ————链路用户数据[(length-2)byte] C S————代码和(1byte) 16 H ————结束字符(1byte) 注:(1)代码和=控制域+地址域+ ASDU代码和(不考虑溢出位,即256模和) (2)ASDU为“链路用户数据”包,具体格式将在下文介绍 (3)Length=ASDU字节数+2 2.3 控制域 控制域分“主从”和“从主”两种情况。 (1)“主从”报文的控制域 D7 D6 D5 D4 D3 D2 D1 D0 备用PRM FCB FCV 功能码 0 1 1 (A)PRM(启动报文位)表明信息传输方向,PRM=1由主站至子站;PRM=0由子站至主站。 (B)FCB(桢记数位)。FCB = 0 / 1——主站每向从站发送新一轮的“发送/确认”或“请求/响应”传输服务时,将FCB取反。主站为每个从站保存一个FCB的拷贝,若超时未收到应答,则主站重发,重发报文的FCB 保持不变,重发次数最多不超过3次。若重发3次后仍未收到预期应答,则结束本轮传输服务。 (C)FCV (桢记数有效位),FCV= 0表明FCB的变化无效,FCV=1表明FCB的变化有效。发送/无回答服务、广播报文不考虑报文丢失和重复传输,无需改变FCB状态,这些桢FCV常为0

(示例)西门子103规约初始化过程

103规约-初始化过程(示例) 2007-06-2710:34 以下是我中心与某厂家装置通信过程初始化报文,对部分报文加以分析,与各位分享。 M->S1Phy1040014116 Dat PRM=1FCV=0Reset CU Address=01 App 注:主站复位通信单元,子站应删除缓冲区内的报文. S->M2Phy1020012116 Dat PRM=0ACD=1DFC=0ACK Address=01 App M->S3Phy107A017B16 Dat PRM=1FCB=1FCV=1Request user data class1Addre ss=01 App S->M4Phy6816166828010A810101FE F40001017B011206 010********C00E916 Dat L=22PRM=0ACD=1DFC=0User data Address=01 Link user data=0A81...0C00 App Generic data(=10) SQ=1Number of elements=1 Cause of transmission:Spontaneous(=1) Common address=01Function type=254(Generic function type)INF=244(Read value or attribute of a single entry) Return information identifier(RII)=0 Number of generic data sets(NGD):no=1,count=0,cont=0 Generic identification number(GIN):group=1,entry=123 (ENTRY identifier) Kind of description(KOD):Actual value Generic data description:(datatype=18,datasize=6,number=1,cont=0) General identification data:(DPI=ON Time:valid, standard,12:17:29.974Supplementary information(SIN)=0) 注:错误-采用通用分类服务上送的事件信息,在复位CU命令下仍然能够传输.按照规约,此时子站清空发送缓冲区,且应马上回复复位确认信息(ASDU5). M->S5Phy105A015B16 Dat PRM=1FCB=0FCV=1Request user data class1Addre ss=01

IEC103规约报文格式

IEC103规约报文格式

IEC103规约格式 1.基本报文格式 1.1固定帧长报文 启动字符 控制域 地址域 代码和 结束字符 注:代码和=控制域+地址域(不考虑溢出位,即256模和) 1.2可变帧长报文 注:(1)代码和=控制域+地址域+ ASDU 代码和(不考虑溢出位,即256模和) (2)ASDU 为“链路用户数据”包,具体格式将在下文介绍 (3)Length=ASDU 字节数+2 1.3控制域定义 控制域分“主∧ 从”和“从∧ 主”两种情况。 (1) “主∧ 从”报文的控制域 D7 D6 D5 D4 D3 D2 D1 D0 备用 PRM FCB FCV 功能码 1 每位的具体定义请参考详细103规约。 (2) “从∧ 主”报文的控制域 D7 D6 D5 D4 D3 D2 D1 D0 备用 PRM ACD DFC 功能码 0 0 每位的具体定义请参考详细103规约。 ———— 启动字符1(1byte ) ———— 长度(1byte ) ———— 长度(重复)(1byte ) ———— 启动字符2(重复)(1byte ) ———— 控制域(1byte ) ———— 地址域(1byte ) ———— 链路用户数据[(length-2)byte] ———— 代码和(1byte ) ———— 结束字符(1byte )

1.4地址域 地址域为主站与之通信的从站地址,0-254:设备地址,255:广播地址。 2.链路规约数据单元(LDPU) 控制方向:从控制系统到继电保护设备(或间隔单元)的传输方向。 监视方向:从继电保护设备(或间隔单元)到控制系统的传输方向。 2.1控制方向 ●复位帧计数位 ●复位通信单元 ●召唤1级数据 ●召唤2级用户数据 ●请求链路状态 2.2监视方向 ●确认帧:

完整word版104报文分析

1. 104规约框架分析 1.1 原始报文的组成 报文组成(1字节启动字符0x68,1字节报文长度,4字节控制域,不定长用户数据) 第1个字节是启动字符0x68; 第2个字节是报文长度; 第3~6共4个字节是控制域; 第7个字节是报文类型; 第8个字节是可变结构限定词; 第9~10共2个字节是传送原因; 第11~12共2个字节是应用服务数据单元公共地址; 第13~15共3个字节是信息对象地址; 。。。。。。 1.2 三种报文格式的控制域定义 (1)I帧 编号的信息传输格式(InFormation Transmit Format),简称I-格式I格式控制域标志,控制域:第一个八位位组的第一位比特= 0 第三个八位位组第一位比特= 0 (2)S帧 编号的监视功能格式(Numbered supervisory Functions),简称S-格式,控制域,第一个八位位组的第一位比特= 1 并且第二位比特= 0,第三个八位位组第一位比特= 0 (3)U帧 不编号的控制功能格式(Unnumbered control Function),简称U-格式,第一个八位位组的第一位比特= 1 并且第二位比特=1 且第三个八位位组第一位比特= 0 1.3 报文类型(第7个字节) 1.3.1 监视方向的应用功能类型 类型标识∶=UI8[1..8]<0..44> M_SP_NA_1(1) 无时标单点遥信 M_SP_TA_1(2) 带短时标的单点遥信 M_DP_NA_1(3) 无时标双点遥信 M_DP_TA_1(4) 带短时标双点遥信 M_ST_NA_1(5) 步位置信息 M_ST_TA_1(6) 带短时标的步位置信息 M_BO_NA_1(7) 32比特串 M_BO_TA_1(8) 带短时标的比特串

103报文示例及解析

103报文示例 10 40 04 44 16 // 复位通信单元 10 20 04 24 16 //确认 10 49 04 4D 16 //召唤链路状态 10 2B 04 2F 16 //从站以链路状态响应主站请求 68 0F 0F 68 73 04 06 81 08 04 FF 00 9E AB 0A 10 BB 04 07 32 16 //时间同步 10 20 04 24 16 //确认 68 09 09 68 53 04 07 81 09 04 FF 00 00 EB 16 //总查询(总召唤)的启动 10 20 04 24 16 //确认 10 7A 04 7E 16 //主站召唤一级数据 68 15 15 68 28 04 05 81 04 04 A0 03 02 53 49 45 4D 45 4E 53 20 34 2E 30 33 58 16 //厂家标识报文 10 5A 04 5E 16 //主站召唤一级数据 68 44 44 68 28 04 17 06 1F 04 A0 00 05 00 01 CE 8C 20 06 02 01 05 06 00 00 9A 9B 20 06 02 01 05 07 00 01 5C 67 19 02 03 01 05 08 00 01 47 9F 19 02 03 01 05 09 00 01 43 BB 21 05 03 01 05 0A 00 01 86 25 27 05 03 01 05 27 16 //被记录的扰动表 10 7A 04 7E 16 //主站召唤一级数据 68 0E 0E 68 28 04 01 81 09 04 28 01 01 22 2F 37 05 00 72 16 //遥信数据,下同 10 5A 04 5E 16 68 0E 0E 68 28 04 01 81 09 04 28 02 01 7C 2F 37 05 00 CD 16 10 7A 04 7E 16 68 0E 0E 68 28 04 01 81 09 04 28 03 01 D6 2F 37 05 00 28 16 10 5A 04 5E 16 68 12 12 68 28 04 02 81 09 04 28 0F 01 00 00 00 00 30 30 37 05 00 90 16 10 7A 04 7E 16 68 12 12 68 28 04 02 81 09 04 28 10 01 00 00 00 00 8B 30 37 05 00 EC 16 10 5A 04 5E 16 68 0E 0E 68 28 04 01 81 09 04 28 14 01 E4 30 37 05 00 48 16 10 7A 04 7E 16 68 0E 0E 68 28 04 01 81 09 04 28 51 01 3F 31 37 05 00 E1 16 10 5A 04 5E 16 68 0E 0E 68 28 04 01 81 09 04 3C 01 01 99 31 37 05 00 FF 16 10 7A 04 7E 16 68 0E 0E 68 28 04 01 81 09 04 3C 02 01 25 32 37 05 00 8D 16 10 5A 04 5E 16 68 0E 0E 68 28 04 01 81 09 04 3C 15 01 81 32 37 05 00 FC 16 10 7A 04 7E 16 68 0E 0E 68 28 04 01 81 09 04 3C 16 01 D9 32 37 05 00 55 16 10 5A 04 5E 16 68 0E 0E 68 28 04 01 81 09 04 3C 17 02 34 33 37 05 00 B3 16 10 7A 04 7E 16 68 12 12 68 28 04 02 81 09 04 3C 4B 01 00 00 00 00 8D 33 37 05 00 40 16 10 5A 04 5E 16 68 12 12 68 28 04 02 81 09 04 3C 4C 01 00 00 00 00 1A 34 37 05 00 CF 16 10 7A 04 7E 16

103报文详细解析

103规约转出软件实验报告(改进版) 1、初始化 主站发: 10 40 04 44 16 目的:给地址为04的装置发复位通信单元命令。 10 1999年11月8日1999年11月8日结果分析:程序行为正确。 主站发连续发送报文:68 0f 0f 68 44 ff 06 81 08 ff ff 00 d4 26 0f 09 28 0b 63 78 16目的:测试程序连续运行时的行为。 测试时间:一天 结果分析:连续运行结果正确。 主站发连续发送报文:68 0f 0f 68 44 ff 06 81 08 ff ff 00 d4 26 0f ff 28 0b 63 78 16目的:测试程序连续运行时的行为。 测试时间:一天。 结果分析:连续运行结果正确。 主站发:68 0f 0f 68 44 01 06 81 08 01 ff 00 d4 26 0f 09 28 0b 63 7c 16 68 0f 0f 68 44 01 06 81 08 01 ff 00 d4 26 0f 09 28 0b 63 7c 16 目的:给地址为01的装置发对时命令。 对时时间为:1999年11月8日9时15分秒 装置受(第一次):00 1f 00 09 ff 03 3d 09 0f 09 08 0b 63 对时令:对时时间:1999年11月8日9时15分9秒 装置受(第二次):00 1f 00 03 ff 03 3e 时钟同步令 子站回答:10 20 01 21 16 目的:ACD位置1,子站向主站请求上送1级数据。 主站发:10 7a 01 7b 16 目的:主站发向子站请求1级数据命令。 子站回答:68 0f 0f 68 08 01 06 81 08 01 ff 00 d4 26 0f 09 28 0b 63 40 16 目的:子站以ASDU6响应主站的召唤1级数据命令。

IEC103规约报文举例

IEC103规约报文举例 分类:电力系统2010-07-20 17:16 77人阅读评论(0) 收藏举报 遥控报文示例 主:68 11 11 68 53 32 0a(1) 81 28 32 fe(2) f9(3) 00(4) 01(5) 0b 01(6) 01(7) 03 01 01(8) 01(9) 75 16 通用分类带确认的写条目 子:10 20 32 52 16 确认帧 (1)类型标识(2)功能码,通用分类服务(3)信息序号,带确认写命令(4)返回信息标识符(5)通用分类个数(NOG)(6)通用分类标识序号(GIN)(7)描述类别,实际值(8)通用分类数据描述(GDD)(9)数据内容 主:10 7a 32 ac 16 召唤一级用户数据 子:68 11 11 68 08 32 0a(1) 81 2c(2) 32 fe f9 00 01 0b 01 01 03 01 01 01 2e 16 响应带确认的写条目 (1)类型标识(2)传送原因,通用分类写确认 主:68 0a 0a 68 53 32 0a(1) 81 28 32 fe(2) fa(3) 00(4) 00(5) 62 16 通用分类带执行的写条目 子:10 20 32 52 16 确认帧 (1)类型标识(2)功能码,通用分类服务(3)信息序号,带执行的写条目 (4)返回信息标识符(5)通用分类个数(NOG) 主:10 7a 32 ac 16 召唤一级用户数据 子:68 0a 0a 68 08 32 0a(1) 81 28 (2) 32 fe fa 00 00 17 16 响应带执行的写条目 (1)类型标识(2)传送原因,通用分类写命令肯定认可 遥测报文示例 说明:遥测数据可以通过通用分类服务总召唤、单组所有条目召唤、单组单条目召唤等方式获得。对于通用分类总召唤,在5.1.3中已经列出其报文实例。在本节中,只举一个单组所有条目召唤的实例。 主:68 0d 0d 68 73 32 15(1) 81 2a(2) 32 fe f1(3) 00(4) 01(5) 09 00(6) 01(7) 91 16 通用分类服务组召唤 子:10 20 32 52 16 确认帧 (1)类型标识(2)传送原因(3)信息序号,召唤单组所有条目(4)返回信息标识符(5)通用分类个数(NOG)(6)通用分类标识序号(GIN)(7)描述类别,实际值主:10 5a 32 8c 16 召唤一级数据 子:68 d2 d2 68 28 32 0a(1) 81 2a(2) 32 fe(3) f1(4) 00(5) 94(6) 09 01(7) 01(8) 07 04 01(9) 00 00 56 3b(10) 09 02 01 07 04 01 00 00 00 80 09 03 01 07 04 01 00 00 7e 3b 09 04 01 07 04 01 00 00 00 80 09 05 01 07 04 01 00 00 01 3b 09 06 01 07 04 01 00 00 00 80 09 07 01 07 04 01 00 00 e3 3b 09 08 01 07 04 01 00 00 00 80 09 09 01 07 04 01 00 00 3f 3b 09 0a 01 07 04 01 00 00 00 80 09 0b 01 07 04 01 00 00 4f 3b 09 0c 01 07 04 01 00 00 00 80 09 0d 01 07 04 01 00 00 b0 3a 09 0e 01 07 04 01 00 00 00 80 09 0f 01 07 04 01 00 00 8c 3b 09 10 01 07 04 01 00 00 00 80 09 11 01 07 04 01 00 00 15 3b 09 12 01 07 04 01 00 00 00 80 09 13 01 07 04 01 00 00 a6 3a 09 14 01 07 04 01 00 00 00 80 d7 16 通用分类服务

许继103规约详解

许继103规约报文详解

IEC60870-5-103(DL/T667-1999)报文详解 一、800系列装置串口IEC60870-5-103部分 一、引用标准 IEC60870-5-103:1997 继电保护设备信息接口配套标准,DL/T667-1999 远动设备及系统第5 部分传输规约第103 篇继电保护设备信息接口配套标准。 二、通信接口 1.接口标准:RS232 或RS485。 2.通信格式:异步,1 位启始位,8 位数据位,1 位偶校验,1 位停止位。 3.通信速率:9600 bit/s。 4.通信方式:主从式,装置为从站。 三、报文格式 IEC60870-5-103 通信规约有固定帧长和可变帧长两种报文格式。前者用于传送“复位、召唤、确认、无所要求、链路状态/响应、忙帧”等信息。后者主 要用于传送“命令、数据”等信息。 b.接受校验:每帧报文的启动位,停止位、偶校验位。接受校验的字符有启动字符、帧校验和、结束字符,若检出一个差错,舍弃此帧数据,若无差错,数据有效。 256的模和)。 b. ASDU 链路用户数据包的具体格式详见下文介绍 c. Length=ASDU 链路用户数据包的字节数+2(2为控制域、地址域的长度),长度为控制域、地址域、链路用户数据的8位位组的个数,即字节个数。 d. 接受校验:每帧报文的启动位,停止位、偶校验位。接受校验的字符有启动字符、两个长度字符Length应一致、接受字符总数为L+6(两个启动字符、两个长度字符、校验字符及结束字符16)、帧校验和、结束字符,若检出一个差错,舍弃此帧数据,若无差错,数据有效。 注:固定帧长报文主站和子站之间的确认;而可变帧长用于主站和子站之间传输数据。3、控制域

许继103报文解析

许继IEC-103规约报文实例详解

68 09 09 68 73 2B 07 81 09 01 FF 00 01 30 16 //总召唤第一扇区 10 20 2B 4B 16 10 5A 2B 85 16 68 0E 0E 68 28 2B 01 81 09 01 B2 B7 01 AB 55 28 0E 01 80 16 //asdu1 10 7A 2B A5 16 68 0E 0E 68 28 2B 01 81 09 01 B2 B1 02 44 56 28 0E 01 15 16 10 5A 2B 85 16 68 0E 0E 68 28 2B 01 81 09 01 B2 B8 01 DA 56 28 0E 01 B1 16 10 7A 2B A5 16 68 0E 0E 68 28 2B 01 81 09 01 B2 BD 01 65 57 28 0E 01 42 16 10 5A 2B 85 16 68 0E 0E 68 28 2B 01 81 09 01 B2 EE 02 F3 57 28 0E 01 02 16 10 7A 2B A5 16 68 0E 0E 68 28 2B 01 81 09 01 B2 B0 02 9E 58 28 0E 01 70 16 10 5A 2B 85 16 68 0E 0E 68 28 2B 01 81 09 01 B2 BC 02 25 59 28 0E 01 04 16 10 7A 2B A5 16 68 0E 0E 68 28 2B 01 81 09 01 B2 BB 02 B3 59 28 0E 01 91 16 10 5A 2B 85 16 68 0E 0E 68 28 2B 01 81 09 01 B2 BA 02 36 5A 28 0E 01 14 16 10 7A 2B A5 16 68 0E 0E 68 28 2B 01 81 09 01 B2 CB 02 CF 5A 28 0E 01 BE 16 10 5A 2B 85 16 68 0E 0E 68 28 2B 01 81 09 01 B2 DE 01 66 5B 28 0E 01 68 16 10 7A 2B A5 16 68 0E 0E 68 28 2B 01 81 09 01 B2 FC 01 FA 5B 28 0E 01 1A 16

104规约报文详解(解剖麻雀,最快速掌握,强力推荐)

--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- IEC-60870-5-104:应用模型是:物理层,链路层,网络层,传输层,应用层 物理层保证数据的正确送达,保证如何避免冲突。(物理层利用如 RS232上利用全双工) 链路层负责具体对那个slAvE的通讯,对于成功与否,是否重传由链路层控制(RS485 2线利用禁止链路层确认) 应用层负责具体的一些应用,如问全数据还是单点数据还是类数据等(网络利用CSMA/CD等保证避免冲突的发生) --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 基本定义:端口号2404,站端为SErvEr 控端为CliEnt,平衡式传输,2BytE站地址,2BytE传送原因,3BytE信息地址。 --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 注:APDU 应用规约数据单元(整个数据)= APCI 应用规约控制信息(固定6个字节)+ ASDU 应用服务数据单元(长度可变) --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- APDU长度(系统-特定参数,指定每个系统APDU的最大长度)APDU的最大长度域为253(缺省)。视具体系统最大长度可以压缩。 --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 【1个例子】 104报文分析 BuF序0 1 2 3 4 5 6 7 8 9 .10 11 12 13 14 15 16 17 18 19 20 21 22 M->R:68 1510 0002 001E 01 03 0001 0079 00 00 01 10 01 24 13 D2 0A 02分析的结果是I (主动上报SOE,主动上报是因为104是平衡式规约)报文头固定为0x68,即十进制104 长度15字节(不是6帧的,都是I帧) 发送序号=8【控制字节的解析10 00 02 00 ,发送序号:0010H/2=16/2=8】 接收序号=1 【控制字节的解析10 00 02 00 ,接收序号:0002H/2=2/2 =1】 0x1E=30 即M_SP_TB_1 带长时标的单点信息 01 -> SQ:0 信号个数:1 03 00 -> 传送原因:[ T=0 P/N=0 原因=3 | 突发] 01 00 -> 公共地址:1 79 00 00 -> 0x79=121 信息体地址: 121 01 -> 状态: 1 IV:0 NT:0 SB:0 BL:0 10 01 24 13 D2 0A 02 ->低位10 高位01,即0x0110=1*16*16+16=272 时标: 2002/10/18 19:36:00.272 --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 每个字节都为unsignED ChAr类型,如果是2个字节表示1个short型,则都是低位在前,高位在后。 --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 【字节0】0x68即十进制数104,68做为BuF第0个字节,下面的说明依次向后排 --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 【字节1】15即从字节2到最后的所有字节数(长度) --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 【字节2、3、4、5】这4个字节是4个控制域,对应不同类型的格式(I帧、U帧、S帧),意义和格式都不相同

许继103报文抓取与分析(整理版)

ASDU单元公共地址保护功能为01,测控功能为02 FUN的值,178(0XB2)为线路保护 时间同步报文:68 0F 0F 68 64 FF 06 81 08 FF FF 00 00 00 30 0F 18 0A 0A 5B 16 10 40 2C 6C 16 -----复位CU (31 ms) 10 20 2C 4C 16 -----有可召唤的一级数据 10 5A 2C 86 16 -----召唤一级数据 (31 ms) 68 15 15 68 28 2C 05 81 04 01 B2 03 02 57 58 48 2D 38 32 33 00 52 02 2E 0E E7 16 ------复位CU响应报文 10 7A 2C A6 16 ------继续召唤一级数据 (31 ms) 68 15 15 68 08 2C 05 81 05 01 B2 04 02 57 58 48 2D 38 32 33 00 52 02 2E 0E C9 16 ------启动重新启动报文 10 5A 2C 86 16 ------继续召唤一级数据,FCB=0 (31 ms) 10 09 2C 35 16 ------无召唤数据 68 0F 0F 68 64 FF 06 81 08 FF FF 00 00 00 26 0F 18 0A 0A 51 16 ------时间同步,FCB=1 68 09 09 68 73 2C 07 81 09 01 FF 00 00 30 16 ------总召唤启动,FCB=1,错误 (31 ms) 10 09 2C 35 16 68 09 09 68 53 2C 07 81 09 01 FF 00 00 10 16 ----总召唤启动,FCB=0 (47 ms) 10 20 2C 4C 16 ------有可召唤的一级数据 10 7A 2C A6 16 ------召唤一级数据,FCB=1 (31 ms) 68 0E 0E 68 28 2C 01 81 09 01 B2 B7 01 99 C2 27 0F 00 DB 16 ------ASDU_1,COMADD=01H,FUN=B2H(178),INF=B7H(183)低电压保护压 板,DPI=01H 10 5A 2C 86 16 ------继续召唤一级数据 (31 ms) 68 0E 0E 68 28 2C 01 81 09 01 B2 B1 02 B8 DA 27 0F 00 0D 16 ------INF=B1H(177)过负荷保护压板 10 7A 2C A6 16 (31 ms) 68 0E 0E 68 28 2C 01 81 09 01 B2 B8 01 AE E9 27 0F 00 18 16 ------INF=B8H(184)零序保护压板 10 5A 2C 86 16 (32 ms) 68 0E 0E 68 28 2C 01 81 09 01 B2 BD 01 BA 0C 28 0F 00 4D 16

及104规约报文解析方法

101、104规约报文解析方法 一、电力系统数据通信协议体系 IEC60870-5系列:远动通信协议体系 IEC60870-6系列:计算机数据通信协议体系 IEC61850-7系列:变电站数据通信协议体系 IEC60870-5系列; IEC TC57 WG03(远动规约) 配套标准 IEC60870-5-101:基本远动任务 IEC60870-5-102:电能累计量 IEC60870-5-103:继电保护 IEC60870-5-104:IEC60870-5-101的网络访问 其他规约类型;CDT、、MODBUS等。 二、远动传输规约IEC60870-5-104的解析方法 1)程序启动后,首先发送链路连接请求帧,68 04 07 00 00 00 起始字符:68H

应用规约数据单元长度(APDU):04H (4个字节,即07 00 00 00) 控制域第一个八位组:07H --> 0000 0111 由前两位11可知是U格式帧; 由第三四位01可知是链路连接请求帧2)随后,接到模拟从站发送来的连接请求确认帧, 68 04 0B 00 00 00 起始字符:68H 应用规约数据单元长度(APDU):04H (4个字节,即0B 00 00 00) 控制域第一个八位组:0BH --> 0000 1011 由前两位11可知是U格式帧; 由第三四位10可知是链路连接确认帧3)主站发送测试链路询问帧, 68 04 43 00 00 00 控制域第一个八位组:43H --> 0100 0011 由前两位11可知是U格式帧;

由第七八位01可知是链路测试请求帧4)从站发送链路测试确认帧; 68 04 83 00 00 00 控制域第一个八位组:43H --> 0100 0011 由前两位11可知是U格式帧; 由第七八位11可知是链路测试确认帧5)主站发送总召唤激活请求命令;

许继103通信规约

许继变电站自动化系统的103通信规约 1 前言 本文是许继电气公司的变电站自动化产品贯彻执行IEC60870-5-103和DL/T 667-1999标准的通信规约。 本通信规约完全执行IEC60870-5-103标准和DL/T 667-1999标准的全部规定,它描述了许继电气公司CBZ8000变电站自动化系统中的继电保护自动化产品的实际运用情况,以供产品的开发和使用参考。 2 引用标准 IEC60870-5-103:1997 继电保护设备信息接口配套标准, DL/T 667-1999 远动设备及系统第5部分传输规约第103篇继电保护设备信息接口配套标准。 3 规约 3.1 通信接口 1.接口标准:RS232或RS485。 2.通信格式:异步,1位启始位,8位数据位,1位偶校验,1位停止位。 3.通信速率:9600 bit/s。 4.通信方式:主从式,装置为从站。 3.2 报文格式 IEC60870-5-103通信规约有固定帧长和可变帧长两种报文格式。前者用于传送“复位、召唤、确认、无所要求、链路状态/响应、忙帧”等信息。后者主要用于传送“命令、数据”等信息。 3.2.1 固定帧长报文格式(见表一)

表一固定帧长报文格式 10H 启动字符 CODE 控制域 ADDR 地址域 CS 校验和 16H 结束字符 注:校验和=控制域+地址域 3.2.2可变帧长报文格式(见表二) 表二可变帧长报文格式 68H 启动字符 Length 长度 Length 长度(重复) 68H 启动字符 CODE 控制域 ADDR 地址域 ASDU 链路用户数据 CS 校验和 16H 结束字符 注: a. 校验和CS=控制域+地址域+链路用户数据代码和 b. ASDU链路用户数据包的具体格式详见下文介绍 c. Length=ASDU链路用户数据包的字节数+2 3.2.3控制域 控制域分“主->从”和“从->主”两种情况。 (1)“主->从”报文的控制域 D7 D6 D5 D4 D3 D2 D1 D0 备用 FUNCTION CODE PRM=1 FCB FCV 注:a. 当FCV=1时FCB有效,当FCV=0时FCB无效。 b. FCB=0/1:主站每向从站发送新一轮的“发送/确认”“请求/响应”传输服务时,将FCB取反。若超时未收到回答,主站重发报文,重发报文的FCB 保持不变,重发次数最多为3次,若3次未收到应答,结束本次传输服务。 c.功能码(FUNCTION CODE)(见表三) 表三主->从功能码 功能码帧类型功能描述 FCV状态 0 发送/确认帧 C_RCU_NA_3 复位通信单元 0 3 发送/确认帧传送数据 1 4 发送/无回答帧传送数据 0 7 复位帧计数位 C_RFB_NA_3 传送数据 0 9 请求/响应帧 C_RLK_NA_3 召唤链路状态 0 10 请求/响应帧 C_PL1_NA_3 召唤1级数据 1 11 请求/响应帧 C_PL2_NA_3 召唤2级数据 1

南瑞继保网络103报文实例_3375

103网络规约报文过程表(不够完善需要补充,召波形,动作信息没有) 2008-10-08 09:04:57 装置:RCS9621C-2.02 地址:336 TCP 90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff 02 00 2b 00 51 00 00 00 00 00 ff ff 装置心跳报文 2008-10-08 09:04:57 装置:RCS9621C-2.02 地址:336 UDP 90 eb 14 00 00 00 90 eb 00 00 50 01 00 00 ff ff d9 01 2b 00 51 00 00 00 00 00 ff ff 装置心跳报文 2008-10-08 09:05:01 装置:RCS9621C-2.02 地址:336 TCP 装置主动上送遥测 90 eb 8c 00 00 00 90 eb 00 00 50 01 00 00 ff ff 03 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 02 00 fe f1 ff 0e 05 01 01 0c 02 01 18 00 05 02 01 0c 02 01 10 00 05 03 01 0c 02 01 10 00 05 04 01 0c 02 01 08 00 05 05 01 0c 02 01 10 00 05 06 01 0c 02 01 10 00 05 07 01 0c 02 01 00 00 05 08 01 0c 02 01 00 00 05 09 01 0c 02 01 08 00 05 0a 01 0c 02 01 08 00 05 0b 01 0c 02 01 a0 6a 05 0c 01 0c 02 01 00 00 05 0d 01 0c 02 01 00 00 05 0e 01 0c 02 01 e8 ff 2008-10-08 09:05:06 装置:RCS9621C-2.02 地址:336 TCP 90 eb 1f 00 00 00 90 eb 00 00 01 f0 00 00 50 01 03 00 01 00 50 00 00 00 00 00 ff ff 15 81 2a 50 fe f1 40 01 09 00 01 召扰动数据表 2008-10-08 09:05:06 装置:RCS9621C-2.02 地址:336 TCP 90 eb f2 00 00 00 90 eb 00 00 50 01 00 00 01 f0 04 00 2b 00 51 00 00 00 00 00 ff ff 0a 81 2a 00 fe f1 40 9c