Contact ID
- 格式:pdf
- 大小:39.30 KB
- 文档页数:4
Contact ID Format Library
Technical Assistance - Tel.:(800)503-5869 Fax :(416)665-1500 Page 1
Communication Protocol:18 SSSS QXYZ GG CCC K
18=Uniquely identifies this format to the receiver and
to an automation system, but not displayed on the
printer
SSSS =
4 digit Subscriber ID Q =Event qualifier, which gives specific event
information
E = 1New event or opening
R = 3New restore or closing
P = 6Previous event
YXZ =Event code (3 Hex digits)
GG =Group number (physical or logical, 2 Hex digits)
CCC =
Zone or sensor number(3Hex digits, event
reports) or user number (Open/close report)Note: The GG and CCC fields can contain 0 for a null (no information) field.
Contact ID Format Library
Technical Assistance - Tel.:(800)503-5869 Fax :(416)665-1500 Page 2
Contact ID Event Code Classification Medical Alarm - 100101 Pendant Transmitter 102Fail to report in Fire Alarms - 110111Smoke 112 Combustion 113Water Flow 114Heat 115Pull Station
116Duct 117Flame 118Near Alarm Panics Alarms - 120121Duress 122Silent 123Audible Burglar Alarms - 130131Perimeter 132Interior 13324 Hour 134Entry/Exit
135Day/Night 136 Outdoor 137Tamper 138Near Alarm General Alarms - 140141Polling Loop
Open
142Polling Loop
Short
143Expansion Module Failure 144Sensor Tamper 145Expansion Module Failure 24H Non-Burglary -150 and 160151Gas Detection
152Refrigeration
153Loss of Heat 154Water Leakage 155Foil Break 156Day Trouble
157Low bottled Gas
Level
158High Temp 159Low Temp
161Loss of Air Flow Fire Supervisory - 200and 210
201Low Water Pressure
202Low CO 2
203Gate Valve
Sensor
204 Low Water
Level
205Pump Activated
206Pump Failure
System Trouble - 300and 310301AC Loss 302 Low System Battery 303RAM Checksum Bad 304ROM Checksum Bad 305System Reset 306Panel Program Changed 307Self-Test Failure 308System Shutdown 309Battery Test Failure 310Ground Fault Sounder/Relay Troubles - 320321Bell 1322Bell 2323Alarm Relay 324Trouble Relay 325Reversing
Contact ID Format Library
Technical Assistance - Tel.:(800)503-5869 Fax :(416)665-1500 Page 3
System Peripheral Troubles - 330 and 340331 Polling Loop Open 332Polling Loop Short 333Expansion Module Failure 334Repeater Failure 335Local Printer Paper Out
336Local Printer Failure Communication Troubles - 350 and 360351Telco 1 fault 352Telco 2 fault 353Long Range Radio 354Fail to Communicate 355Loss of Radio Supervision 356Loss of Central Polling Protection Loop Trouble - 370
371Protection Loop
Open
372Protection Loop
Short
373Fire Trouble
Sensor Trouble - 380381 Loss of
Supervisory-
RF
382Loss of
Supervisory - RPM
383Sensor Tamper 384RF Transmitter Low Battery
Open/Close - 400
401Open/Close by
User
402Group Open/Close 403Automatic Open/Close 404Late to
Open/Close
405Deferred
Open/Close
406Cancel
407Remote Arm /Disarm
408Quick Arm
409Keyswitch Open
/Close Remote Access - 410411Call Request Made 412Success - Download Access 413Unsuccessful Access 414System Shutdown 415Dialer Shutdown Access Control - 420421Access Denied 422Access Report by User 441Stay Arming 451Early Opening /Closing 452Late Opening /Closing 453Late to Open 454Late to Close 455Auto-Arm Failure System Disable - 500 & 510
Contact ID Format Library
Technical Assistance - Tel.:(800)503-5869 Fax :(416)665-1500 Page 4Sounder/Relay Disable - 520521Bell 1 Disable 522Bell 2 Disable 523 Alarm Relay Disable 524Trouble Relay Disable 525Reversing Relay Disable System Peripheral Disable - 530 and 540Communication Disable - 550 and 560551Dialer Disable 552Radio Transmitter Disable Bypasses - 570570Zone Bypass 571Fire Zone Bypass 57224 Hour Zone Bypass 573Burglary Zone Bypass 574Group Bypass
Test/Misc. - 600601Manual Trigger Test
602Periodic Test Report
603Periodic RF Transmission
604Fire Test
605Status Report to
Follow
606Listen-in Follow
607Walk Test Mode 621Event Log Reset
622Event Log 50%
Full
623Event Log 90% Full
624 Event Log Overflow
625Time/Date Reset 626Time/Date
Inaccurate
627Program Mode Entry
628Program Mode Exit
631Exception
Schedule
Change。