MODEL NUMBERS D53TP25D D53TP50D A53TP25D A53TP50D OUTPUT SPECIFICATIONS 1
Operating Voltage (47-63 Hz) [Vrms] 48-53048-53048-53048-530
Load Current Range 3 [Arms] .05-25.05-50.05-25.05-50
Transient Overvoltage [Vpk] 1200120012001200
Max. Surge Current, (16.6ms) [Apk] 250625250625
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.61.61.61.6
Thermal Resistance Junction to Case (R θJC ) [°C/W] 1.02.631.02.63
Maximum I 2 t for Fusing, (8.3 msec.) [A 2 sec] 26016202601620
Max. Off-State Leakage Current @ Rated Voltage [mArms] 10101010
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] 2 500500500500
Max. Turn-On Time 4 1/2 Cycle1/2 Cycle10.0 msec10.0 msec
Max. Turn-Off Time 1/2 Cycle1/2 Cycle40.0 msec40.0 msec
Power Factor (Min.) with Max. Load 0.50.50.50.5
INPUT SPECIFICATIONS 1 DC CONTROL AC CONTROL
Control Voltage Range 3-32 Vdc90-280 Vrms (60Hz)
Max. Turn-On Voltage 3.0 Vdc90 Vrms
Min. Turn-Off Voltage 1.0 Vdc10 Vrms
Nominal Input Impedance 450 Ohms 54.8k Ohms
Typical Input Current 10mA @ 5 Vdc2.2mA @ 120 Vrms, 4.4mA @ 240 Vrms
GENERAL NOTES 1 All parameters at 25ºC and per section unless otherwise specified.2 Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.13 Heat sinking required, for derating curves see page 2.4 Turn-on time for random turn-on versions is 0.02 msec (DC Control Models).• SCR Output
• LED Status Indicator
• Protective Cover Available (Part No. KS300)
SERIES 53TP.Rev. 100107PAGE 1 OF 3Three-phase solid state relays switch up to 530 Vrms directly to loads such as motors, transformers, heating elements, etc. Available with either AC or DC input (coil) control in zero-voltage or random turn-on switching versions. Manufactured in Crydom’s ISO 9001 Certified facility for optimum product performance and reliability.
© 2007 CRYDOM Inc., Specifications subject to change without notice. • Panel Mount
• Integrated Overvoltage Protection by Automatic Self Turn-On (Suffix P) Series 53TP
25-50Amp • 240/480 Vac - 3 PHASE
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540Crydom Inc., 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 606030 • FAX +44 (0)1202 606035 Crydom SSR Ltd., Arena Business Centre,Holyrood Close, Poole, Dorset BH17 7FJ, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506元器件交易网www.cecb2b.com80
4060
20
051020251520406080Load Current [Arms]Max Ambient Temp. [ºC]Power Dissipation
Base Plate Temp [ºC]0.5ºC/W1ºC/W
120
60
90
30
010204050
3020
4060
80Load Current [Arms]Max Ambient Temp. [ºC]Power Dis
s
i
p
a
t
i
on90
110
120Base Plate Temp [ºC]0.25ºC/W
10095
11510590
110
12010095
1151051ºC/W60
40
20
051020251520406080Load Current [Arms]Max Ambient Temp. [ºC]Power Dissipation100
Base Plate Temp [ºC]A53DP25D, D53DP25DA53TP25D, D53TP25D
A53TP50D, D53TP50D1ºC/W.5ºC/W
105110115120100
105
110
1151201.5ºC/W
102040503020406080Load Current [Arms]Max Ambient Temp. [ºC]Power Dissipation
Base Plate Temp [ºC].5ºC/W1.5ºC/W
1.5ºC/W0.5ºC/W
1ºC/W1.5ºC/W.25ºC/WCURRENT DERATING CURVESAVAILABLE OPTIONS
-10Non-Zero Cross,Instantaneous Turn-OnExample: D53TP50D-10
DP2 Controlled, 1 Linked (A1-A2)Example: D53DP50DGENERAL SPECIFICATIONSDielectric Strength 50/60Hz Input/Output/Base 4000 VrmsInsulation Resistance (Min.) @ 500 Vdc109OhmMax. Capacitance Input/Output 8 pFAmbient Operating Temperature Range-40 to 80ºCAmbient Storage Temperature Range-40 to 125ºC
MECHANICAL SPECIFICATIONSWeight: (typical)10.3 oz. (315g)Encapsulation: Thermally Conductive Epoxy
Terminals:Screws and Saddle Clamps Furnished
APPROVALSULE116950CSALR81689VDE5941 UG
Crydom Heat Sinksoffer excellentthermal management and are perfectly matched to the load currentratings of Crydom panel mountrelays. Request Crydom’s Heat Sinkspecification sheet for all the details.
SERIES 53TPRev. 100107PAGE 2 OF 3© 2007 CRYDOM Inc., Specifications subject to change without notice. 4.09
3.62(91.9).79(20.1).125(3.2)THICKNESS
.94(24.0)1.18(30.0)
A1B1C1
A2B2C2INPUTSTATUSLEDINPUT+
-1.875(47.6)2.125(54.0)10-32 TERMINAL(6 PLACES )(103.8)0.21(5.3)
0.79(20.1)2.89(73.4)
1.36(34.5).78(19.8)1.56(39.6)(10.0).39 REFTERMINAL(2 PLACES )6-32BASE PLATE
All dimensions are in inches (millimeters)Screw Torque Requirements:6-32 Screws - 10 in. lbs. (1.1Nm), 8-32 and 10-32 Screws - 20in. lbs. (2.2Nm) (Screws dry without grease.) PInternal Overvoltage Protection.Relay Will Self Trigger Between900-1200 Vpk. Not Suitable ForCapacitive Loads.Example: D53TP50DP
HHeat Trasfer Pad (Attached)Example: D53TP50DHSeries 53TP
25-50Amp • 240/480 Vac - 3 PHASE
A53DP50D, D53DP50D
90
30150180