110kV串抗型式试验报告_test11
- 格式:doc
- 大小:354.50 KB
- 文档页数:2
1.试验项目及结论Order Test Type Testing Date Test Results 1 Conducted Emission Test 11.29 PASS2 Immunity to Continuous ConductedInterference Test11.29 PASS3 Radiated Emission Test(30MHz ~ 1000MHz)11.29 PASS4 Immunity To Radiated Electric Fields Test 11.29 PASS5 Electrical Fast Transient/Burst Immunity Test11.29 PASS6 Surge Immunity Test 11.29 PASS7 Voltage Dips, Short Interruptions and VoltageVariations Immunity Test11.30 PASS8 Voltage fluctuation and Flicker Test 11.30 PASS9 Harmonic Current Emissions Test 11.30 PASS10 Electrostatic Discharge Immunity Test 11.30 PASS 2. Mode of operation during the testConducted Emission Test:Mode1:Norma l Operation(DC 48V)Mode2: Norma l Operation(AC 220V/50Hz)Immunity to Continuous Conducted Interference Test:Mode1:Norma l Operatio nRadiated Emission Test(30MHz ~ 1000MHz):Mode1: Normal OperationImmunity To Radiated Electric Fields Test:Mode1:Norma l Operation(DC 48V)Mode2: Norma l Operation(AC 220V/50Hz)Electrical Fast Transient/Burst Immunity Test:Mode1:Normal Operation(DC 48V)Mode2: Normal Operation(AC 220V/50Hz)Mode2: Normal Operation(AC 220V/50Hz)Voltage Dips, Short Interruptions and Voltage Variations Immunity Test: Mode1:Normal Operation(DC 48V)Mode2: Normal Operation(AC 220V/50Hz)Voltage fluctuation and Flicker Test:Mode1:Normal Operation(DC 48V)Mode2: Normal Operation(AC 220V/50Hz)Harmonic Current Emissions Test:Mode1:Normal Operation(DC 48V)Mode2: Normal Operation(AC 220V/50Hz)Electrostatic Discharge Immunity Test:Mode1:Normal Operation1. Conducted Emission Test1.1. Conducted Emission Test Data and ResultsTes t Mod e : Mod e 1: Norma l Operation(D C 48V)DC Power : DC 48V Phase : LINE Temperature : 23°C Humidity : 52% Pressure(mbar) : 1002 Date: 2014/11/29No. Frequenc y(MHz) Facto r(dB)Readin g(dBuV)Leve l(dBuV)Limi t(dBuV)Margi n (dB)Detector1 0.1580 10.19 31.79 41.98 65.56 -23.58 QP2 0.1580 10.19 13.69 23.88 55.56 -31.68 AVG3 0.4460 10.27 29.01 39.28 56.95 -17.67 QP4 0.4460 10.27 22.69 32.96 46.95 -13.99 AVG5 1.0820 10.33 21.25 31.58 56.00 -24.42 QP6 1.0820 10.33 14.59 24.92 46.00 -21.08 AVG7 7.9860 10.54 20.34 30.88 60.00 -29.12 QP8 7.9860 10.54 19.57 30.11 50.00 -19.89 AVG9 15.9740 10.67 17.82 28.49 60.00 -31.51 QP10 15.9740 10.67 14.68 25.35 50.00 -24.65 AVG11 29.9300 10.84 17.79 28.63 60.00 -31.37 QP12 29.9300 10.84 16.09 26.93 50.00 -23.07 AVG Note: Measuremen t Leve l = Readin g Leve l + Correc t Facto rTes t Mod e : Mod e 1: Norma l Operation(D C 48V)DC Power : DC 48V Phase : NEUTRALTemperature : 23°C Humidity : 52%Pressure(mbar) : 1002 Date: 2014/11/29No. Frequenc y(MHz) Facto r(dB)Readin g(dBuV)Leve l(dBuV)Limi t(dBuV)Margi n(dB)Detector1 0.1539 9.86 31.22 41.08 65.78 -24.70 QP2 0.1539 9.86 13.69 23.55 55.78 -32.23 AVG3 0.4420 9.87 28.05 37.92 57.02 -19.10 QP4 0.4420 9.87 21.34 31.21 47.02 -15.81 AVG5 1.0980 9.90 21.36 31.26 56.00 -24.74 QP6 1.0980 9.90 13.40 23.30 46.00 -22.70 AVG7 7.9860 10.09 20.59 30.68 60.00 -29.32 QP8 7.9860 10.09 19.79 29.88 50.00 -20.12 AVG9 15.9780 10.18 12.82 23.00 60.00 -37.00 QP10 15.9780 10.18 7.32 17.50 50.00 -32.50 AVG11 29.4580 10.31 20.36 30.67 60.00 -29.33 QP12 29.4580 10.31 18.16 28.47 50.00 -21.53 AVG Note: Measuremen t Leve l = Readin g Leve l + Correc t Facto rTes t Mod e : Mod e 2: Norma l Operation(A C 220V/50Hz)DC Power : AC 220V/50Hz Phase : LINETemperature : 23°C Humidity : 52% Pressure(mbar) : 1002 Date: 2014/11/29No. Frequenc y(MHz) Facto r(dB)Readin g(dBuV)Leve l(dBuV)Limi t(dBuV)Margi n (dB)Detector1 0.1500 10.13 33.31 43.44 65.99 -22.55 QP2 0.1500 10.13 20.60 30.73 55.99 -25.26 AVG3 1.1180 10.16 23.34 33.50 56.00 -22.50 QP4 1.1180 10.16 16.56 26.72 46.00 -19.28 AVG5 1.5220 10.17 21.37 31.54 56.00 -24.46 QP6 1.5220 10.17 14.94 25.11 46.00 -20.89 AVG7 7.9900 10.25 15.67 25.92 60.00 -34.08 QP8 7.9900 10.25 12.28 22.53 50.00 -27.47 AVG9 15.9780 10.49 14.42 24.91 60.00 -35.09 QP10 15.9780 10.49 8.36 18.85 50.00 -31.15 AVG11 23.9580 10.41 22.71 33.12 60.00 -26.88 QP12 23.9580 10.41 21.01 31.42 50.00 -18.58 AVG Note: Measuremen t Leve l = Readin g Leve l + Correc t Facto rTes t Mod e : Mod e 2: Norma l Operation(A C 220V/50Hz)DC Power : AC 220V/50Hz Phase : NEUTRAL Temperature : 23°C Humidity : 52% Pressure(mbar) : 1002 Date: 2014/11/29No. Frequenc y(MHz) Facto r(dB)Readin g(dBuV)Leve l(dBuV)Limi t(dBuV)Margi n(dB)Detector1 0.1500 10.13 32.58 42.71 65.99 -23.28 QP2 0.1500 10.13 19.63 29.76 55.99 -26.23 AVG3 1.1420 10.18 24.80 34.98 56.00 -21.02 QP4 1.1420 10.18 17.43 27.61 46.00 -18.39 AVG5 7.9860 10.26 17.78 28.04 60.00 -31.96 QP6 7.9860 10.26 15.55 25.81 50.00 -24.19 AVG7 15.9780 10.51 16.77 27.28 60.00 -32.72 QP8 15.9780 10.51 13.07 23.58 50.00 -26.42 AVG9 23.9660 10.36 21.20 31.56 60.00 -28.44 QP10 23.9660 10.36 14.52 24.88 50.00 -25.12 AVG11 28.4940 10.29 17.12 27.41 60.00 -32.59 QP12 28.4940 10.29 14.45 24.74 50.00 -25.26 AVG13 0.1500 10.13 32.58 42.71 65.99 -23.28 QP14 0.1500 10.13 19.63 29.76 55.99 -26.23 AVG Note: Measuremen t Leve l = Readin g Leve l + Correc t Facto rTes t engineer:1.2. Conducted Emission Test Set-upDC 48VAC220V/50Hz2. Immunity to Continuous Conducted Interference Test2.1 Immunity to Continuous Conducted Interference Test Data and ResultsBasic Standard : GB/T 17626.5-2008Product Standard : EN 61000-6-2Final Test Result : PASSCoupling mode : CDN-(M2+M3) for DC power portsTemperature : 21°CRelative Humidity : 51%Atmospheric Pressure : 100 kPaTest Date : 2014.11.29Test Mode 1Frequency : 0.15~80MHz, Modulation : AM 80%,1KHz sine wave, Dwell time: 3sFrequency Step Size : 1 % of preceding frequency valuemode Voltage(V) Result Frequency Test0.15 ~ 80MHz Power(M2) 10 ATes t engineer:2.2.Immunity to Continuous Conducted Interference Test Set-up3. Radiated Emission Test(30MH z ~ 1000MHz)3.1.Radiated Emission Test Data and ResultsTes t Mod e : Mod e 1: Norma l Operatio nDC Power : DC 48V Ant. Polarization: Horizontal Temp : 23℃ Humidity : 52%Pressure(mbar) : 1002 Date : 2014/11/29No. Frequenc y(MHz) Facto r(dB/m)Readin g(dBuV)Leve l(dBuV/m)Limi t(dBuV/m)Margi n(dB)Det. Heigh t(cm)Azimut h(deg)1 189.0800 -18.19 46.32 28.13 40.00 -11.87 peak 200 1312 298.6899 -16.73 40.94 24.21 47.00 -22.79 peak 100 2043 364.6499 -15.10 38.09 22.99 47.00 -24.01 peak 200 24 445.1600 -13.53 38.68 25.15 47.00 -21.85 peak 100 2885 583.8700 -11.69 40.08 28.39 47.00 -18.61 peak 100 556 668.2599 -10.16 34.41 24.25 47.00 -22.75 peak 200 216 Note: Measuremen t Leve l = Readin g Leve l + Correc t Facto rTes t Mod e : Mod e 1: Norma l Operatio nDC Power : DC 48V Ant. Polarization: Vertical Temp : 23℃ Humidity : 52% Pressure(mbar) : 1002 Date : 2014/11/29No. Frequenc y(MHz) Facto r(dB/m)Readin g(dBuV)Leve l(dBuV/m)Limi t(dBuV/m)Margi n(dB)Det. Heigh t(cm)Azimut h(deg)1 47.4600 -18.33 45.98 27.65 40.00 -12.35 peak 100 3442 72.6800 -26.39 52.58 26.19 40.00 -13.81 peak 100 173 189.0800 -18.04 51.62 33.58 40.00 -6.42 peak 100 1344 302.5700 -16.47 39.53 23.06 47.00 -23.94 peak 100 1345 366.5900 -15.02 40.04 25.02 47.00 -21.98 peak 200 2896 584.8400 -11.76 41.09 29.33 47.00 -17.67 peak 100 148 Note: Measuremen t Leve l = Readin g Leve l + Correc t Facto rTes t engineer:3.2. Radiated Emission Test Set-upAC220V/50Hz4.Immunity To Radiated Electric Fields TestStandar d Fina l Tes t Resul t: EN61000-4-3: 2006 Fina l Tes t Resul t: PAS STest Voltage:80M~2GHz,10 V/m Temperatur e: 23°CRelativ e Humidit y: 55%Atmospheri c Pressur e: 100 kP aTes t Dat e: 2014.11.29Frequency (MHz)AntennaPolarizationTest fieldstrengthResult Remark80 MHz to 1 GHz Vertical 10 V/m PASS Criterion A 80 MHz to 1 GHz Horizontal 10 V/m PASS Criterion A 1.4 GHz to 2 GHz Vertical 10 V/m PASS Criterion A 1.4 GHz to 2 GHz Horizontal 10 V/m PASS Criterion ATes t engineer:5. Electrical Fast Transient/Burst Immunity TestBasi c Standar d : GB/T 17626.42008Fina l Tes t Resul t : PAS S O n D C Por t ±2.0 KvTes t Voltag e :Temperatur e : 21°CRelativ e Humidit y : 51 %Atmospheri c Pressur e : 100 kP aTes t Dat e : 2014.11.29Mode1:Puls e : 5/50 n sRepetitio n Rate: 5 kHz Burst 15m/300msTest time 1 min/each conditionVoltage/ Mode/ Polarity/ Result/ Phas e 1.0 kV 2.0 kV+ -+ -D C Powe r Lin eL(+)-- -- A A N (-)‐‐‐‐ A A L(+)-N (-)‐‐‐‐ A A P E ‐‐‐‐ A A L(+)-P E ‐‐‐‐ A A N (-)-P E‐‐‐‐ A A O n D C Por t ±2.0 K vO n A C Por t ±4.0 K vL(+)-N (-)-P E‐‐‐‐ A A Note: + fo r anode, fo r cathod eMode 2Puls e : 5/50 n sRepetitio n Rate: 5 kH zBurst : 15m/300msTest time : 1 min/each conditionVoltage/ Mode/ Polarity/ Result/ Phas e2.0 kV 4.0 kV + +A C Powe r Lin eL - A A-N A A LN A A PE A A LPE A A N PE A A L NPE A ACerpas s Technolog y (Suzhou) Co., Lt d Issue d Dat e : No v 30.2014Tes t engineer:6.Surg e Immunit y Tes t6.1 Surge Immunity Tes t Data and ResultsBasi c Standar d Produc t: GB/T 17626.5.2008 Standar d Fina l Tes t Resul t: EN6100062Fina l Tes t Resul t: PAS STes t Voltag e: Input DC Power Port -- ±2.0kV for Line to Line, ±4.0Kvfor Line to GNDInput AC Power Port -- ±4.0kV for Line to Line, ±6.0Kvfor Line to GNDTemperatur e: 21°C Relativ e Humidit y: 51 % Atmospheri c Pressur e: 100 kP a Tes t Dat e: 2014.11.29Mode 1: Normal Operation(DC 48V)Waveform : 1.2/50μs(8/20μs) Repetition rate : 60 sec Time : 20 time/each condition/Phase Voltage / Mode / Polarity Result2.0 kV L(+)-N(-)+ A- A4.0 kV L(+)-PE+ B- BN(-)-PE+ B- BMode 2: Normal Operation(AC 220V/50Hz)Waveform : 1.2/50μs(8/20μs) Repetition rate : 60 sec Time : 20 time/each condition/Phase Voltage / Mode / Polarity Result4.0 kV L-N+ A- A6.0 kV L-PE+ B- B+ BN-PE- BTes t enginee r6.2 Surge Immunity Tes t Set-up7.Voltage Dips, Short Interruptions and Voltage Variations Immunity TestStandar d Fina l Tes t Resul t: EN61000-4-11:2004Fina l Tes t Resul t: PAS STest Port:AC Power PortsTemperatur e: 20°C Relativ e Humidit y: 50% Atmospheri c Pressur e: 100 kP a Tes t Dat e: 2014.11.30Voltage Dips Test level (%residual voltage) Duration(ms)Minimumrequirement Result100 10 Criterion A Criterion A Pass 100 50 Criterion A Criterion A Pass30 500 Criterion B Criterion A PassVoltage InterruptionTest level (%residual voltage) Duration(s)Minimumrequirement Result0 5 Criterion C Criterion C PassTes t engineer:8. Voltage fluctuation and Flicker TestStandar d Fina l Tes t Resul t: GB 17625.2Fina l Tes t Resul t: PAS STemperatur e: 24°CRelativ e Humidit y: 53%Atmospheri c Pressur e: 101kP aTes t Dat e: 2014.11.30Uncertainty of FlickerExpanded uncertainty (k=2) of flicker measurement is ± 0.030 %Tes t engineer:9. Harmonic Current Emissions TestStandar d Fina l Tes t Resul t: GB 17625.1 Fina l Tes t Resul t: PAS S Temperatur e: 20°CRelativ e Humidit y: 50% Atmospheri c Pressur e: 100 kP a Tes t Dat e: 2014.11.30Order Av. Current[A] Frame:2.5min Limit In/I1 (%) Result1 0.0978 1.0800 0.738% PASS2 0.1878 2.3000 1.417% PASS3 0.0293 0.4300 0.221% PASS4 0.0409 1.1400 0.308% PASS5 0.0302 0.3000 0.228% PASS6 0.0348 0.7700 0.262% PASS7 0.0299 0.2300 0.226% PASS8 0.0363 0.4000 0.274% PASS9 0.0259 0.1840 0.195% PASS10 0.0382 0.3300 0.288% PASS11 0.0206 0.1533 0.155% PASS12 0.0388 0.2100 0.293% PASS13 0.0164 0.1314 0.124% PASS14 0.0415 0.1500 0.313% PASS15 0.0128 0.1150 0.097% PASS16 0.0426 0.1324 0.321% PASS17 0.0104 0.1022 0.078% PASS18 0.0389 0.1184 0.293% PASS19 0.0078 0.0920 0.059% PASSOrder Av. Current[A] Frame:2.5minLimit In/I1 (%) Result21 0.0401 0.1071 0.302% PASS22 0.0059 0.0836 0.045% PASS23 0.0333 0.0978 0.251% PASS24 0.0057 0.0767 0.043% PASS25 0.0346 0.0900 0.261% PASS26 0.0051 0.0708 0.038% PASS27 0.0328 0.0833 0.247% PASS28 0.0053 0.0657 0.040% PASS29 0.0277 0.0776 0.209% PASS30 0.0041 0.0613 0.031% PASS31 0.0255 0.0726 0.192% PASS32 0.0046 0.0575 0.035% PASS33 0.0226 0.0682 0.170% PASS34 0.004 0.0542 0.030% PASS35 0.0203 0.0643 0.153% PASS36 0.0036 0.0511 0.027% PASS37 0.0158 0.0608 0.119% PASS38 0.0036 0.0484 0.027% PASS39 0.0138 0.0577 0.104% PASS40 0.004 0.0460 0.030% PASSTes t engineer:10.Electrostatic Discharge Immunity Test10.1. Electrostatic Discharge Immunity Test Data and ResultsStandar d Fina l Tes t Resul t: GB/T 17626.2-2006Fina l Tes t Resul t: PAS STes t Voltag e: ±8kV Contact±15kV AirTemperatur e: 25°CRelativ e Humidit y: 50%Atmospheri c Pressur e: 100 kP aTes t Dat e: 2014.11.30Contact Discharge Air Discharge25 times / each 10 times / eachVoltage 2 kV 4 kV 6 kV 8 kV 2 kV 4 kV 8 kV 15 kV-+ -+ -+-+-+-+ -+ -Point\Polarity +------------A A---------------------------HCP ------------------A A---------------------VCP ------------------------------A A------------ 1,3,4,5,6 ---------------B B------------ --- --- ---------2,7,8,9,10,11,12 ------------------------A A---------------------14 ---13,15,16,17,18,22,23,24 --- --- --- ---------B B------------ --- --- ------------------A A--------------------- 19,20,21 ---------25,26,27,28,29,30,31,32 --- --- --- ---------B B------------ --- --- ------33,34,35,36,37,38 ------ --- ---------B B------------ --- --- ------39,40,41,42,43 B B49 ------ A A44,45,46 B B47,48 A A50,51,52,53 B B54,55 A A56,57 A B58,59,60 A A61,62,63 A ATes t engineer:10.2. Electrostatic Discharge Immunity Test Set-up。
152康青线保护屏一、铭牌:二、通电前检查:1、屏体上的标签与图纸相一致。
2、接线与实际图纸相符。
3、拔出所有插件,检查各插件上的元件无松动、脱落现象,无机械损伤及连线无被扯断等现象。
4、绝缘电阻测试合格(2000V),接地符合要求,屏蔽措施符合规程要求,接线与反措细则一致。
5、通过测CT极性,检查保护、测量、计量电流二次回路均正确。
三、装置通电检查:将插件按顺序全部插入,分别给上直流电源后各装置面板上的工作指示灯点亮,面板上其它指示灯不亮。
四、回路检查:1)手合、手跳装置及回路反映情况正确,红绿灯指示正确。
2)当地监控系统跳合闸操作反映情况正确,报文正确。
3)开出、开入传动核对正确。
(具体详见大纲)4)保护压板核对正确。
五、装置调试1、零漂检验:装置通电两小时后各通道零漂检验结果如下(要求零漂范围-0.3----+0.3)2、采样值精度校验:误差范围在-3%—+3%之间。
3、保护功能测试:将测试电源IA、IB、IC、IN加在CT的对应相上;UA、UB、UC、UN加在PT对应的端子上。
1)、相间距离的测试:(1) 定值的测定(2)整组测试模拟瞬时故障模拟永久故障2)、零序电流的测试:(1) 定值的测定(2)整组测试模拟瞬时故障模拟永久故障:3)过流保护功能测试:(1)、保护定值的测定:将测试电源IA、IC、IN加在CT的对应相上;在各相上分别加电流,使保护动作并重合。
(2)通入模拟量传动的整组试验:模拟瞬时性故障:装置A、C相分别通入1.05倍的定值和0.95倍的定值,动作情况如下:模拟永久性故障:装置A、C相分别通入1.05倍的电流保护定值和0.95倍的电流保护定值,动作情况如下:4)结论:合格5)试验仪器:S40型深圳凯旋保护校验仪。
1#主变保护试验报告装置名称:PST671U一、外观及接线检查:检查结果:良好二、绝缘测试:直流地:90M 交流电流地:100M交流电流直流:120M三、CT校验:一次侧CT变比:500/1二比侧CT变比:5000/1四、装置菜单功能及功能检查:检查结果:正确五、开关量输入回路检查:检查结果:正确六、输出接点及信号检查:检查结果:正确七、交流回路相序及相角检查:检查结果:正确八、主保护试验:(1)测量值(2)速差保护定值测试:整定值:5.0A 时间:0s(3)比差保护定值测试:(4) 谐波制动特性测试定值:二次谐波15%整定值:0.44A 时间:6s(2)闭锁有载调压定值测试:整定值:0.86A 时间:7s九、主变高后备保护(2)复压过流保护定值Ⅰ段2时限测试:整定值:动作电流:1.07A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.9s 切1101断路器投高压侧定时限过流保护压板(3)复压过流保护定值Ⅰ段3时限测试:整定值:动作电流:1.07A ; 动作电压:65V; 负序动作电压:7V; 动作时限:2.2s 切1101断路器、101断路器投高压侧定时限过流保护压板(4)复压过流保护定值Ⅱ段2时限测试:整定值:动作电流:1.07A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.9s 切1101断路器投高压侧定时限过流保护压板(5)复压过流保护定值Ⅱ段3时限测试:整定值:动作电流:1.07A ; 动作电压:65V; 负序动作电压:7V; 动作时限:2.2s 切1101断路器、101断路器投高压侧定时限过流保护压板(6)复压过流保护定值Ⅲ段2时限测试:整定值:动作电流:1.07A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.9s 切1101断路器投高压侧定时限过流保护压板整定值:动作电流:1.07A ; 动作电压:65V; 负序动作电压:7V; 动作时限:2.2s 切1101断路器、101断路器投高压侧定时限过流保护压板(8)高压侧过负荷保护定值测试:(9)间隙零序保护定值测试:整定值:动作电流:1A;动作电压:180V;动作时限:0.3S十、主变低后备保护(1)测量值:(2)复压过流保护定值Ⅰ段1时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.0s 切100断路器投低压侧定时限过流保护压板(3)复压过流保护定值Ⅰ段2时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.3s 切100断路器、切101断路器投低压侧定时限过流保护压板(4)复压过流保护定值Ⅰ段3时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.6s 切100断路器/101断路器、1101断路器投低压侧定时限过流保护压板(5)复压过流保护定值Ⅱ段1时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.0s 切100断路器投低压侧定时限过流保护压板(6)复压过流保护定值Ⅱ段2时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.3s 切100断路器、切101断路器投低压侧定时限过流保护压板(7)复压过流保护定值Ⅱ段3时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.6s 切100断路器/101断路器、1101断路器投低压侧定时限过流保护压板(8)复压过流保护定值Ⅲ段1时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.0s 切100断路器投低压侧定时限过流保护压板(9)复压过流保护定值Ⅲ段2时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.3s 切100断路器、切101断路器投低压侧定时限过流保护压板(10)复压过流保护定值Ⅲ段3时限测试:整定值:动作电流:0.98A ; 动作电压:65V; 负序动作电压:7V; 动作时限:1.6s 切100断路器/101断路器、1101断路器投低压侧定时限过流保护压板(11)低压侧过负荷保护定值测试:整定值:0.86A 时间:9s十一、整组传动1、手动分合开关良好,后台遥控正确。
电气安装工程高压调试报告变电站名称:110kV尖峰变电站一、110kV断路器 (3)二、110kV#1 主变设备间隔 (21)三、IIOkGlS交流耐压试验 (42)四、110kV尖#1主变10kV侧进线003断路器间隔 (44)五、10kV站用变 (56)六、110kV变电站10kV电站电源一008断路器间隔 (59)七、110kV 变电站10kV电站电源二009断路器间隔 (67)八、110kV变电站10kV配电电站004断路器间隔 (75)九、110kV变电站10kV备用一005断路器间隔 (83)十、110kV变电站10kV备用二006断路器间隔 (91)十^一、110kV变电站10kV配电站电源一001断路器间隔 (98)十二、110kV变电站10kV配电站电源二006断路器间隔 (106)十三、110kV 变电站10kV零序CT (114)十四、110kV变电站10kV母线电压互感器013设备间隔 (117)十五、110kV变电站10kV三相过电压保护器 (122)十六、110kV变电站10kV#1电容器组011断路器间隔 (123)十七、110kV变电站10kV#2电容器组012断路器间隔 (140)十八、110kV变电站10kV余热发电并网柜007断路器间隔 (170)十九、110kV变电站10kV电容补偿柜一011断路器间隔 (181)二十、110kV变电站10kV电容补偿柜二012断路器间隔 (189)1^一、110kV变电站接地网电气完整性测试试验 (197)一、110kV变电站151断路器间隔六氟化硫断路器试验报告安装间隔:110kVGIS进线151断路器设备间隔试验人员:GIS主回路试验报告安装间隔:110kVGIS进线151断路器间隔. 断路器气体检漏试验金属氧化物避雷器试验报告安装间隔:110IWGIS进线151断路器间隔铭牌主要技术参数电压互感器试验报告安装间隔:IIOkVGIS进线151断路器间隔铭牌主要技术参数试验人员:电流互感器试验报告安装间隔:110kV151断路器间隔进线侧CT铭牌主要技术参数试验人员:电流互感器试验报告安装间隔:110kV151断路器间隔主变侧CT试验人员:、110kV 变电站110kV#1主变设备间隔油浸式电力变压器试验报告安装间隔:110kV #1主变设备间隔4.绕组连同套管一起的直流泄漏电流试验试验人员:金属氧化物避雷器试验报告安装间隔:110kV # 1主变(110kV侧中性点避雷器)3.计数器表计刻度及动作情况检查试验人员:隔离开关试验报告安装间隔:110kV #1主变高压侧中性点1010接地开关试验人员:变压器升高座电流互感器试验报告安装间隔:110kV #1主变4.绕组直流电阻试验试验人员:专业专注放电间隙试验报告安装间隔:110kV #1主变110kV侧中性点放电间隙试验人员:电流互感器试验报告安装间隔:110kV # 1主变(110kV中性点间隙CT)2.绕组直流电阻试验试验人员:、110kV变电站IIOkVGIS交流耐压试验110kV GIS整组交流耐压试验记录110kV户内设备及母线整组交流工频耐压试验试验人员:四、110kV 变电站110kV #1 主变10kV侧进线003断路器间隔户内高压真空断路器试验报告安装间隔:110kV#1主变10kV侧进线设备间隔4 •模拟操动试验试验人员:专业专注电流互感器试验报告安装间隔110kV #1主变10kV侧进线003断路器间隔铭牌主要技术参数。
110KV线路保护装置试验报告
电站名称:中卫第二十八光伏电站设备名称:仁光Ⅰ线111 试验人员:试验性质:新安装
试验日期:2016.12.14 审核人员:
试验单位:青海蒙汉电气技术有限公司
仁光Ⅰ线111保护试验报告
一、微机保护的基本信息
二、外观检查
三、装置通电检查
四、开入量检查
根据装置原理接线图给各开入量输入端子分别加正电源。
此时应有对应开入量变化的显示输出。
测试结果:
五、零漂检查
交流电流电压回路不加入交流量,观察装置刻度的检查值。
每回路零漂应在-0.1~+0.1范围内。
检查结果:(误差在允许范围内)
六、电压电流采样检验
1、通入三相交流电流电压,查看装置各通道的采样值与试验仪加入量是否一致。
七、开出传动试验
1.差动保护功能校验:
(1)分相电流差动校验
(2)零序电流差动检验
2.距离保护校验仅投距离保护压板
3.零序过流保护
断线过流保护
九、操作箱校验
1.操作箱功能测试
十、二次回路反措执行情况检查
十一、保护整租试验(投重合闸,带开关传动)
十二、保护联调
1.两侧采样检查
2、光差保护联调试验
十三、信号回路检查
十四、极性、变比试验
1.以母线指向线路为正,A/B/C三相各绕组极性、变比如下。
实验目的1. 了解110kv变压器的结构和原理。
2. 掌握110kv变压器的试验方法。
3. 分析110kv变压器的试验结果。
实验设备1. 110kv变压器一台。
2. 交流电源一台。
3. 电压表一台。
4. 电流表一台。
5. 功率表一台。
6. 示波器一台。
7. 万用表一台。
实验步骤1. 检查110kv变压器的外观,确保其完好无损。
2. 将110kv变压器连接到交流电源上。
3. 打开交流电源,调整电压表和电流表的量程。
4. 记录110kv变压器的输入电压和电流。
5. 调整功率表的量程,记录110kv变压器的输入功率。
6. 使用示波器观察110kv变压器的输入电压和电流波形。
7. 使用万用表测量110kv变压器的绝缘电阻。
实验结果1. 110kv变压器的输入电压为110kV,输入电流为100A,输入功率为11kW。
2. 110kv变压器的输入电压和电流波形为正弦波。
3. 110kv变压器的绝缘电阻大于100MΩ。
实验分析1. 110kv变压器的输入电压和电流符合正弦波的特征,说明110kv变压器的工作状态良好。
2. 110kv变压器的输入功率为11kW,说明110kv变压器具有较高的效率。
3. 110kv变压器的绝缘电阻大于100MΩ,说明110kv变压器的绝缘性能良好。
实验结论1. 110kv变压器的结构和原理正确。
2. 110kv变压器的试验方法正确。
3. 110kv变压器的试验结果表明,110kv变压器的工作状态良好,效率高,绝缘性能良好。