当前位置:文档之家› 变电站各种母线接线方式的英文名称

变电站各种母线接线方式的英文名称

Gunnar Stranne
REB 670 Busbar Protection
Santiago de Chile Septiembre 5, 2006
?
ABB Power Technologies AB, 2005 2006-08-30 PTSX Gunnar Stranne 1

Application Areas for REB 670
Differential, CBF & Non-Dir OC Protection for: Busbars Meshed corners, T-protection
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 2

REB 670*1.0 … Available Versions
3-Phase Version
Two measuring zone CBF, OC, EnFP & AR 4 or 8 bays
1-Phase Version
Two measuring zones CBF, OC, EnFP & AR 12 or 24 bays One terminal per phase Summation
2006-04-20 PTSX Gunnar Stranne 3
?
ABB Power Technologies AB, 2005

REB 670*1.0 Variants
12I + 3*IO Cards
3Ph, 4 bays, 2 zone Used for small, fixed zones like T protection, meshed corner, ring bus etc. Not Applicable 3Ph, 8 bays, 2 zone
12I/24I + 11*IO Cards
Not Applicable
A20
Used for small substations with up to 8 CT inputs. Complete zone selection & CBF protection! A31
1Ph, 12 bays, 2 zone (three IEDs required)
ABB Power Technologies AB, 2005
Used for substation with up to 12 CT inputs. No zone selection possible due to limited No. of IO cards. No extension possibilities! Good for stations with fixed zones (i.e. 1? breaker). B20 Not Applicable
Used for substation with up to 12 CT inputs. Possible to use zone selection & CBF. Possible to extend to 24 CT inputs
B21
Used for substation with up to 24 CT inputs. Possible to use zone selection & CBF, but possible application problems due to binary IO limitations.
1Ph, 24 bays, 2 zone (three IEDs required)
?
2006-04-20 PTSX Gunnar Stranne 4
B31

Available I/O-modules ? 19” case
IOM (max 3st)
? of 19” Case 1 TRM 12I only! up to 3 I/O modules
BIM (max 3st)
BOM (max 3st)
10+2 binary outputs and 8 binary inputs
24 binary outputs (12*2contacts)
ABB Power Technologies AB, 2005
16 binary inputs
?
2006-04-20 PTSX Gunnar Stranne 5

Available I/O-modules 1/1 19” case
IOM (max 11st)
Full of 19” Case 1 or 2 TRM 12I only! up to 11 I/O modules
BIM (max 11st)
BOM (max 4st)
10+2 binary outputs and 8 binary inputs
24 binary outputs (12*2contacts)
ABB Power Technologies AB, 2005
16 binary inputs
?
2006-04-20 PTSX Gunnar Stranne 6

Three-Phase Terminal; 4/8 Bays- Double Zone Application Areas: Smaller Buses (up to 8 CTs per zone) Single Busbar Stations (with Transfer Bus) 1? Breaker Stations Double Busbar Stations (with Transfer Bus) Zone Interconnection included in the design
REB 670; 3Ph
2 Zones (A & B); 8 Bays
No switching in CT secondary circuits
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 7

REB 670*1.0 3-Ph; basic applications Diff & CBF
M/G
Auto-Transformer
Generator/Motor
Capacitor
Reactor
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 8

REB 670 3- Ph; BBP, BFP & EnFP for single buses
ZA ZA ZB
Single Busbar up to 4/8 feeder bays
Single Bus with bus tie CB up to 3/7 feeder bays on each side
ZA ZA ZB ZB
ABB Power Technologies AB, 2005
H type station with bus-section CB or sectionalizing disconnector
Alternative CT Location
T connections
?
2006-04-20 PTSX Gunnar Stranne 9

REB 670 3- Ph, BBP, BFP, EnFP for 1? CB stations
ZA
ZB
1? Breaker Stations up to 4 diameters
ZA
.. .
ZB
ABB Power Technologies AB, 2005
1? Breaker Stations up to 8 diameters
?
2006-04-20 PTSX Gunnar Stranne 10

REB 670 3- Ph; BBP, BFP & EnFP for Double CB stations
ZA
.. .
ZB
Double Breaker Station up to 8 feeders
Alternative CT Location
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 11

REB 670 1- Ph; BBP, BFP & EnFP for double buses
ZA ZB
.. .
Double Bus with bus-coupler CB and up to 6/7 feeder bays
ZA ZB
.. . .. . .. .
Transfer Bay
Transfer Bus
Isolator replica in REB 670*1.0 by CAP 531 Configuration
ABB Power Technologies AB, 2005
Double Busbars with bus coupler CB and Transfer Bus up to 6/7 feeder bays
2006-04-20 PTSX Gunnar Stranne 12
Optional Measuring Point
?

Scheme Layout for Double Busbar; 2 Zones/7 feeders
700 ABB
EQUIPMENT INCLUDED in the PANEL:
1 pcs 3 phase, Busbar protection terminal REB 670*1.0 - two differential zones - check zone - eight CB failure relays - eight OC feeder backup protection (EnFP) - internal disconnector replica logic - internal individual bay tripping logic - disconnector status supervision
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 13

Single-Phase Terminal; 12/24 Bays- Double Zone
REB 670; Ph-L1
2 Zones (A & B); 24 Bays
REB 670; Ph-L2
2 Zones (A & B); 24 Bays
Application Areas: Bigger Buses (up to 12/24 bays per zone) Single Busbar Stations (with Transfer Bus) 1? Breaker Stations Double Busbar Stations (with Transfer Bus) Load Transfer is included into the design 3 Terminals required for complete scheme LDCM available to share binary IO
REB 670; Ph-L3
2 Zones (A & B); 24 Bays
No switching in CT secondary circuits
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 14

REB 670 1- Ph; BBP, BFP & EnFP for single buses
ZA
.. .
Single Bus up to 12/24 feeder bays
ZA
.. .
.. .
ZB
Single Bus with bus-section disconnector up to 12/24 feeder bays (i.e. 12+12; 16+8 etc.)
ZA
.. .
.. .
ZB
ZA
.. .
.. .
ZB
?
ABB Power Technologies AB, 2005
Single Bus with bus-section CB, up to 11/23 feeder bays (i.e. 12+11; 10+13 etc.)
Single Bus with bus-section CB up to 11/23 feeder bays on each side
2006-04-20 PTSX Gunnar Stranne 15

REB 670 1- Ph; BBP applications for 1? CB stations
ZA
ZA
.. .
ZB
.. .
ZB
1? Breaker Stations up to 6 / 12 diameters
1? Breaker Stations up to 12 / 24 diameters
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 16

REB 670 1- Ph, Complete BBP, CBF & EnFP for 1? CB Stations!
ZA
.. .
ZB
Bus Diff, CB Fail & EnFP 1? Breaker Stations up to 4/8 diameters
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 17

REB 670 1- Ph; BBP, BFP & EnFP for Double CB stations
ZA
ZA
.. .
ZB ZB
.. .
Double Breaker Station up to 12 / 24 feeders
Double Breaker Station up to 6 / 12 feeders
Alternative CT Location
?
ABB Power Technologies AB, 2005 2006-04-20 PTSX Gunnar Stranne 18

REB 670 1- Ph; BBP, BFP & EnFP for double buses
ZA
.. .
ZB
Double Bus with bus-coupler CB up to 22/23 feeder bays
ABB Power Technologies AB, 2005
Isolator replica in REB 670*1.0 by CAP 531 Configuration
?
2006-04-20 PTSX Gunnar Stranne 19
Optional Measuring Point

REB 670 1- Ph; BBP, BFP & EnFP for double bus & transfer
ZA ZB
.. . .. . .. .
Combined Bus-Coupler & Transfer Bay
Transfer Bus
ZA ZB
.. . .. . .. .
Bus-Coupler Bay Transfer Bay
Transfer Bus
ABB Power Technologies AB, 2005
Isolator replica in REB 670*1.0 by CAP 531 Configuration
?
2006-04-20 PTSX Gunnar Stranne 20
Double Busbars with Transfer Bus up to 22/23 feeder bays