摘要

本毕业设计主要介绍的是根据国家相关标准和规范对小区供配电系统进行电气设计。其主要内容包括以下几个方面:首先,按单位面积法、单位指标法进行负荷计算。其次,选择降压箱式变电站的形式及位置。最后,根据电压和计算电流选择低压电缆型号和低压配电设备。简要介绍了箱式变电站的防雷与接地,并绘制出相关的电气图纸。

关键词:负荷计算;箱式变电站;电缆;防雷接地;

Abstract

The main graduation presented is based on national standards and norms forresidential electric power supply system design. Its main contents include the following aspects: First, per unit area method, unit load calculation method indicators. Next, choose the form of step-down box and the location of substation. Finally, the selectionvoltage and low voltage cable models calculate current and low voltage power distribution equipment. Outlined box substation lightning protection and grounding, and draw out the relevant electrical drawings.

Keywords: load calculation; box-type substation; cable; lightning protection and grounding;

目录

第一章绪论 (1)

1.1研究目的和意义 (1)

1.2国内外高层住宅建筑设计及发展研究现状 (1)

1.3本文的工作 (2)

第二章设计说明 (4)

2.1.住宅小区基本情况 (4)

2.2.设计范围 (4)

2.3.设计原则 (4)

2.4.环境条件 (5)

第三章住宅小区负荷计算 (6)

3.1.供配电系统概述 (6)

3.2.负荷分级及供电要求 (6)

3.3.电源及高压供配电系统 (7)

3.4.负荷计算 (8)

第四章住宅楼层供配电措施 (13)

4.1.箱式变的台数与容量、类型的选择 (13)

4.2.高、低压分线设备选择 (16)

4.3.高、低压电缆类型及截面型号选择 (17)

第五章照明系统设计 (21)

5.1住宅各部分照明对设计的要求 (21)

5.2灯具的选择 (22)

5.3照明开关的选择 (22)

5.4以往插座系统设计的现状及其存在的问题 (22)

5.5本设计的设计方案 (23)

5.6照明设计的计算 (24)

第六章弱电系统设计 (27)

6.1电话通讯系统设计 (27)

6.2有线电视系统设计 (28)

6.3信息网络系统设计 (28)

第七章消防系统的设计 (29)

7.1消防系统的概述 (29)

7.2火灾报警系统 (29)

7.3消防控制室的设置 (29)

7.4火灾探测器的计算 (30)

7.5应急照明 (32)

第八章防雷接地 (34)

8.1电力设备防雷 (34)

8.2低压配电系统的接地型式和基本要求 (34)

8.3接地种类 (35)

8.4接地装置 (35)

参考文献 (37)

致谢 (38)

第一章绪论

1.1 研究目的和意义

众所周知,电能是现代工业生产的主要能源和动力。电能既易于由其它形式的能量转换而来,又易于转换为其它形式的能量以供应用;电能的输送的分配既简单经济,又便于控制、调节和测量,有利于实现生产过程自动化。因此,电能在现代工业生产及整个国民经济生活中应用极为广泛。

电能在工业生产中的重要性,并不在于它在产品成本中或投资总额中所占的比重多少,而在于工业生产实现电气化以后可以大大增加产量,提高产品质量,提高劳动生产率,降低生产成本,减轻工人的劳动强度,改善工人的劳动条件,有利于实现生产过程自动化。从另一方面来说,如果工厂的电能供应突然中断,则对工业生产可能造成严重的后果。因此,一个稳定可靠的供配电系统对于发展工业生产,实现工业现代化,具有十分重要的意义。由于能源节约是工厂供电工作的一个重要方面,而能源节约对于国家经济建设具有十分重要的战略意义。因此在当今全球资源紧张的局势下,一个好的供配电系统设计,对于节约能源、保护环境、支援国家经济建设,也具有重大的作用。

1.2 国内外高层住宅建筑设计及发展研究现状

1.1 课题背景及意义

供配电技术,就是研究电力的供应及分配的问题。电力,是现代工业生产、民用住宅、及企事业单位的主要能源和动力,是现代文明的物质技术基础。没有电力,就没有国民经济的现代化。现代社会的信息化和网络化,都是建立在电气化的基础之上的。因此,电力供应如果突然中断,则将对这些用电部门造成严重的和深远的影响。故,作好供配电工作,对于保证正常的工作、学习、生活将有十分重要的意义。

供配电工作要很好的为用电部门及整个国民经济服务,必须达到以下的基本要求:(1)安全——在电力的供应、分配及使用中,不发生人身事故和设备事故。

(2)可靠——应满足电力用户对供电可靠性和连续性的要求。

(3)优质——应满足电力用户对电压质量和频率质量的要求。

(4)经济——应使供配电系统投资少,运行费用低,并尽可能的节约电能和减少有色金属消耗量。

另外,在供配电工作中,还应合理的处理局部和全局,当前与长远的关系,即要照顾局部和当前利益,又要有全局观点,能照顾大局,适应发展。

1.2 国内外研究现状

20世纪三相交流电发明之后,供配电技术就朝着大机组、大电网、超高压、自动

化的方向不断发展。我国目前用电结构趋于重型化,为满足经济增长对电力的需求,国家加大电力建设投资。中国电力跨越式发展使得发电装机容量和发电量先后超过法国、加拿大、德国、英国、俄罗斯跃升世界第二,西电东送、南北互供、全国联网的发展战略为我国电力系统的发展带来了极大的空间。

世界范围内,电力工业正在进行以打破垄断、引进竞争为特征的电力体制改革,2008世界电力工业概况显示:日本首次量产发电效率全球最高的燃料电池,正在开发高效家用燃料电池热电联产系统;德国靠“秘密技术“让太阳和地热水发电;英国拟建水上太阳能板;俄罗斯研制出新一代核电厂挑战通用电气抢占国际电力市场。

1.3 本文的工作

配电网处于电力系统末端,将大量通过输电网传输过来的电能经逐级降压后

通过配电网络“分配’’给各个用户,近年配电网供电可靠性受到电力企业的重视,把供电可靠性作为企业达标评优的一个具体考核指标,促进供电企业积极开展配电网供电可靠性管理工作,用可靠性研究的结果指导生产建设。

改革开放30年来,随着我国经济的高速发展,城镇化水平不断提高,人民生活水平得到极大的改善,全社会用电量增长迅猛,在受到年初冰雪灾害和金融危机的等诸多不利因素的影响下08年全国发电量仍然达34334亿千瓦时实现5%的增长,同比78年2566亿千瓦时增长了1 3.35倍。尽管如此我国人均用电水平仍然较低2006年人均用电量约2149千瓦时,约为美国的1 5%,日本的25%,韩国的33%;人均生活用电更是仅为246千瓦时,约为美国的5%,同本的lO%,存在巨大的发展空间。但是我国长期以来配电工程的资金投入落后于发电、输电工程,造成配电网供电能力远低于发电能力和输电能力的增长。配电网普遍存在技术落后、设备陈旧、网架结构薄弱、转供互供能力差,供电可靠性低,在内需成为拉动国民经济增长主要力量,如何不断提高人民生活水平提振内需成保持国民经济持续快速健康发展主要动力的今天。我国落后的配电网建设、管理水平不能满足R益增长的电力供应需求。

所幸这个问题得到了各方面的重视,国家的电力投资将向配电网倾斜投入巨资大规模建设和改造城乡配电网络,电力企业也将目光转向如何提高配电网供电可靠性增供扩销提高效益上来。但如何投放资金和高效的利用资源,有效的改善配电网供电可靠性成为电力企业面临一个现实问题。一方面用户对电能质量和连续性要求不断提高,系统规模不断扩大,运行控制复杂,事故后果严重;另一方面资金资源有限。通过对现有配电网络进行可靠性评估,了解整个系统配电系统的可靠性水平,指出配电网薄弱环节和改进方向,找到可行的改进措施为配电网

的规划、建设、管理提供依据是提高配电网供电可靠性保证,对实现电力工业现代化,提高电力企业经济效益和社会效益都有着重要意义。

第二章设计说明

2.1.住宅小区基本情况

本工程位于四川(省市),乐山市长风置业有限公司,电梯公寓。地下一层,层高3.0米,主要为汽车和自行车库;地上十五层,一层层高4.20米、二三层层3.9米,四~十五层层高3.0米,一~三层为商业,四~十五层均为住宅;屋顶设有电梯机房及水箱间;建筑主体高度48米,总建筑面积为12000平方米。结构形式为框架剪力墙结构,现浇混凝土楼板。

2.2.设计范围

按照市区供电部10kV及以下配电网络设计的规定,对于商住配电工程,设计范围为:

高压侧从市区公用10kV配电线路起,在接引10kV电源处设置明显断开点,低压侧至小区内各建筑低压用电计量装置上表位。

2.3.设计原则

进入新世纪后,我国正在进入人口城市化的社会新时期。各地的开发小区悄然兴起,以满足城市人口急剧膨胀的需要。开发小区的特点是占地面积大、人口集中、楼房之间有较大的空间。加之绿地、曲径、花园、水泵、以及灯饰等,丰富了小区的内涵,体现环境、建筑及人居的和谐统一。根据以上特点它的供电特点与一般的乡村、工厂不同,必须采取新的配电思路和方式来满足其功能的需要。在供配电设计中,力求做到小区特点及环境的要求。设计必须根据小区实际,符合其特点,采用多种供配电形式和方法,满足使用功能的要求,不但做到整体布局合理,在宏观上保持三相负荷分配基本平衡,而且在微观上要做到细致,给每个用户提供一个良好的用电环境。在实现安全可靠配电的同时,还要做到环境的美化,使整个小区的配电合理、适用、经济。

总之,供配电设施要坚持服务和服从于文明城、文明小区创建活动的要求,坚持美化城镇、小区形象,合理布局,科学规范的原则,要有超前意识和适应不断发展变化的新形势。否则,将有可能造成重复建设,不仅造成资金、资源的浪费,还要影响居民用电。在建设上主要是符合如下条件:

(1)符合城镇建设的总体规划;

(2)节约居民小区宝贵的土地资源;

(3)保持居民小区的形象整体美观;

(4)配变置于居民小区中心位置;

(5)有较高的供电质量和供电可靠性。

住宅小区的供电方案主要有:柱上变压器配电、独立配电室配电、箱式变电站配电三种。其中,柱上变压器配电方案虽然投资小,但对小区环境影响较大,因为高压需架空线路引入而不容易深入负荷中心,不能保证较高的供电质量也将造成较高的低压线损,对居民也增加了事故隐患。独立配电室配电方案需要一定面积的土建占地,增大了建设投资,对于本设计所选择的小区来说并不适宜,本小区多为多层建筑,用电负荷分散,供电半径大,降低了供电质量、提高了低压线损。箱式变电站配电方案的特点是,体积小、占地小、外形美观,高压侧采用电缆引入,箱变位置可以随意选择,使得低压配电部分更加合理,提高了供电可靠性,也有利于安装电量采集装置实现自动化管理。

因此,本设计考虑将住宅小区的主要供电模式定位为箱式变电站配电工程。

本市的高压供电等级模式为110kV→35kV→10kV,城区主要配电线路电压等级为10kV,住宅小区一级配电电压选用10kV,低压配电电压应采用220/380V。

2.4.环境条件

当地年最高温度+40 C°,年最低温度-30 C°,年平均温度+10 C°。

覆冰-5mm,最大风速30m/S。

当地海拔高度800米。

第三章住宅小区负荷计算

3.1. 供配电系统概述

随着国民生活水平的提高和房地产业的蓬勃发展,各地新建中高档住宅小区越来越多。准确计算出住宅小区的用电负荷,合理选择配变电设施,才能既满足小区居民现在及将来的用电需要,又能合理降低工程造价、节省投资。

供配电系统设计要彻彻执行国家的技术经济政策,做到保障人身安全,供电可靠,技术先进和经济合理。另外,供配电系统的还必须做到统筹兼顾,按照负荷性质、用电容量、工程特点和地区供电条件,合理确定设计方案。

供配电系统的设计为减小电压偏差,应符合下列要求:

一、正确选择变压器的变压比和电压分接头。

二、降低系统阻抗。

三、采取补偿无功功率措施。

四、宜使三相负荷平衡。

3.2. 负荷分级及供电要求

3.2.1.负荷分级的相关规范:

电力负荷应根据对供电可靠性的要求及中断供电在政治、经济上所造成损失或影响的程度进行分级,并应符合下列规定:

1.符合下列情况之一时,应为一级负荷:

(1).中断供电将造成人身伤亡时。

(2).中断供电将在政治、经济上造成重大损失时。例如:重大设备损坏、重大产品报废、用重要原料生产的产品大量报废,国民经济中重点企业的连续生产过程被打乱需要长时间才能恢复等。

(3).中断供电将影响有重大政治、经济意义的用电单位的正常工作。例如:

重要交通枢纽、重要通信枢纽、重要宾馆、大型体育场馆、经常用于国际活动的大量人员集中的公共场所等用电单位中的重要电力。在一级负荷中,当中断供电将发生中毒、爆炸和火灾等情况的负荷,以及特别重要场所的不允许中断供电的负荷,应视为特别重要的负荷。

2.符合下列情况之一时,应为二级负荷:

(1).中断供电将在政治、经济上造成较大损失时。例如:主要设备损坏、大量产品报废、连续生产过程被打乱需较长时间才能恢复、重点企业大量减产等。

(2).中断供电将影响重要用电单位的正常工作。例如:交通枢纽、通信枢纽等

现代建筑电气设计

对现代建筑电气设计问题的探讨 【摘要】随着社会经济的发展,现代建筑的功能越来越强,建筑电气的重要性也日益明显。在市场竞争日益激烈的前提下,建筑设计的理念也不断变化,适应市场,满足客户需求是每一位设计工作者不断提升自己的原动力,这需要我们每一位建筑电气设计人员随时去关注市场、了解市场,才能掌握市场动态,把握主动权。 一、建筑电气设计的概念和内容 关于设计的概念问题,所谓设计它是一个把构思进行表达,然后再构思再表达,持续发展与评价的过程,可以分为以下几个阶段,包括博览与创意,构思与表达。设计的每一个阶段无论从深度还是广度都不一样,而且,表达的工具与方式也是多式多样的,表达的工具与方式要与思维的速度相适应,它对思维发展的成熟起着重要的推动作用。 建筑电气设计内容从狭义上仅指民用建筑中的电气设计,从广义上讲应该包括工业建筑、构筑物和道路、广场等户外工程。传统建筑电气设计只包括供电和照明,而今天一般将其设计的内容形容为强电和弱电。将供电、照明、防雷归类在强电,而其余部分,如电话、电视、消防和楼宇自控等内容统统归于弱电。 二、建筑电气设计的原则 建筑电气设计严格遵守相关的设计规范。设计规范是国家或地方制定的设计准则,它体现了国家的政策和对建筑的质量要求,是建筑电气设计者设计的标准。建筑电气设计应满足建筑的功能需求,保证

建筑的各项功能稳定连续运行,给居民的日常生活带来方便、快捷。建筑电气设计是建筑的一部分,在设计过程中也要考虑综合经济因素,既要考虑初投资也要兼顾以后的运行费用,以求得建筑生命周期内费用最低的目标。 三、目前我国建筑电气设计中存在的问题 1、关于配电回路方面的问题 每一户的住宅室里都不能有太少的配电回路,因为配电回路太少的话,就会导致回路的负荷加大,也就相当于导线截面的减少。像空调电源插座、照明、电源插座、卫生间电源插座以及厨房电源插座都是从配电箱出来的分支回路,现在的住宅中,卧室与客厅基本都安有空调,空调器负荷有大有小,也就决定了空调的回路数量,一般情况下都在五个以上。除此之外,还有电话线路、有线电视,最少也有7路的管线进入居室,并且在这7路的管线中只有照明的辐射是在顶板,其它的管线都在地面的垫层里面,而且肯定会有交叉现象。而住宅的垫层又非常薄,线路管线错乱交叉处理起来非常困难,而住户在铺地板的时候,通常会打断地坪里的管线,这样就会导致电气使用起来非常的不安全,也非常的不方便。如果把暗敷线路在进行敷设时与地面保持平行或者与墙缝保持垂直的话,那么,以上所说的问题就不会发生,管线交叉的问题完全能在墙缝中解决好,关于照明的线路完全可以在墙的拐弯处通过接线盒对其进行分线,住户要想了解分支回路的位置与方向,就可以通过配电平面图进行了解,这样,也很好的避免了在铺设地板的时候打断管线的问题。

建筑电气设计手册[1].

建筑电气设计手册(含材料表及工程概算)

§表达线路敷设方式、部位、照明灯具安装方式的文字代号§ 表达内容 标注代号对照 表达内容 标注代号对照 表达内容 标注代号对照 英文代号汉语拼音代号英文代号汉语拼音代号英文 代号 汉语拼音代号 用轨形护套线敷设GBV 沿钢索敷设SR S 线吊式CP 用塑制线槽敷设PR XC/VXC 沿屋架或层架下弦敷设BE LM 自在器线吊 式 CP X 用硬质塑制管敷设PC VG 沿柱敷设CLE ZM 固定线吊式CP1 X1 用半硬塑制管敷设FEC ZVG/BYG 沿墙敷设WE QM 防水线吊式CP2 X2 用可挠型塑制管敷设KRG 沿天棚敷设CE PM 吊线器式CP3 X3 用薄电线管敷设TC DG 在能进入的吊顶内敷设ACE PNM 链吊式CH L 用厚电线管敷设G 暗敷在梁内BC LA 管吊式P G 用水煤气钢管敷设SC G/GG 暗敷在柱内CLC ZA 吸顶式或直 附式 S D 用金属线槽敷设SR GC/GXC 暗敷在屋面内或顶板内CC PA 嵌入式R R 用电缆桥架(或托盘)敷设CT 暗敷在地面内或地板内FC DA 顶棚内安装CR DR 用瓷夹敷设PL CJ 暗敷在不能进入的吊顶内AC PNA 墙壁内安装WR BR 用塑制夹敷设PCL VT 暗敷在墙内WC QA 台上安装T T 用蛇皮管敷设CP 柱上安装(灯具)CL Z 支架上安装SP J 用瓷瓶式或瓷柱式绝缘子敷设K CP 座装(灯具)HM ZH 壁装式W B 2

3 §室内电气管线、配电设备与其它管道、设备之间的最小距离表§ 注:1、表内无括号数字为电气管线在管道上面时的数据,有括号数字为电气管线在管道下面时的数据。 2、在不能满足表中所列距离情况下,应采取下列措施: (1) 电气管线与蒸气管线不能保持表中距离时,应在蒸气管或电气管外包以绝热层,此时平行净距可减减至200毫米,交叉处仅 须考虑施工操作和便于维护的距离。 (2) 电气管线与暖水管不能保持表中距离时,可在暖水管外包绝热层。 (3) 裸母线与其它管道交叉不能保持表中距离时,应在交叉处的裸母线外加装保护网或罩。 3、当上水管与电气管线平行敷设且在同一垂直面时,应将电气管线敷设于水管之上。 线路布线 方式 各种布线与其它用途的管道间最小距离 煤气管 乙炔管 氧气管 蒸气管 暖热水管 通风管 上水、下水管 压缩空气管 工艺设备 平行 交叉 平行 交 叉 平行 交 叉 平行 交叉 平行 交叉 平行 交 叉 平行 交叉 平行 交 叉 平行 交叉 导线穿金属管 100 100 100 100 100 100 1000 (500) 300 300 (200) 100 电缆 500 300 1000 500 500 300 1000 (500) 300 500 100 200 100 200 100 200 100 明敷绝缘导线 1000 300 1000 500 500 300 1000 (500) 300 300 (200) 100 200 100 200 100 200 100 裸母线 1000 300 2000 500 1000 500 1000 500 1000 500 1000 500 1000 500 1000 500 1500 1500 吊车滑触线 1500 500 3000 500 1500 500 1000 500 1000 500 1000 500 1000 500 1000 500 1500 1500 配电设备 1500 3000 1500 500 100 100 100 100

现代建筑电气设计的特点及发展

一、现代化建筑电气的概念及其发展 现代化建筑电气是当今的一门独立的学科,主要是借助建筑物的平台,充分发挥现代电气技术的优势。在建筑有限的空间内,最大限度的创作人性化的生活环境。在现代化建筑物飞速发展的今天,建筑物的电气化设计也起到越来越重要的作用。建筑电气的发展是伴随着建筑水平的发展而发展的,经过不断的实践,已经形成比较完整的理论体系,其已经发展到建筑供电技术、电气控制技术、电气安全及自动化技术。鉴于建筑物设计的不断进步,电气化设计也发生了变化,体现出了相应的设计特点,电气化设计实现了跨越式的发展。随着改革开放的不断深入,大量新的产品技术不断的引进,我国的建筑电气化设计得到了不断的进步和发展。 二、现代建筑电气设计的特点 现代建筑电气设计的特点是根据现代电气设计的原则而表现出来的相应的特点,一般的建筑物电气设计中都遵循相关的原则。 (1)要最大程度的满足建筑物的使用功能,其中包括建筑物内部的照明功能。保障建筑物内部的风量及其温度,还要满足建筑物其外在的建筑物的工艺要求。 (2)建筑物电气设计要充分考虑其经济效益。在技术设计上要充分考虑其电气设计的成本核算和提高电气设备的利用效率,把握好工艺节能成本等。 (3)充分考虑节能成本,利用新技术新设备降低电气设备的消耗。从细节出发,研究具体的节能途径。 现代建筑电气设计在其遵循的基本原则下,其设计特点有如下几点。 (1)系统相比较来说比较复杂 现代建筑工程总的建筑面积相对较大,相应的用电需求也比较大。整体来说,电气设计系统比较复杂。 (2)电气设计的功能比较繁多 现代建筑是电气设备使用的综合性建筑,以其功能的多样化和设备的电气要求决定了电气设计的复杂性。 (3)建筑设计的难度比较大 由于项目的不同需要,在电气设计的时候通常要多方协调。应兼顾多方需求,分清主次,统筹协调。 三、建筑电气设计发展趋势

民用建筑电气设计规范完整版

民用建筑电气设计规范 HEN system office room 【HEN16H-HENS2AHENS8Q8-HENH1688】

民用建筑电气设计规范 25 住宅(小区)电气设计 一般规定 本章适用于城镇普通及康居住宅的电气设计,住宅电气设计除应符合本规范外,尚应符合国家现行的有关强制性标准的规定。 普通住宅套型按居住空间个数和使用面积分为一、二、三、四类。 康居住宅分为:基本型(1A)、提高型(2A)、先进型(3A)。 住宅电气设计应与国家同期经济发展水平相适应。 住宅电气设计一般包括:供配电系统;电力、照明系统;火灾自动报警及联动控制系统;安全防范系统;通信网络系统;信息网络系统;建筑设备监控与管理系统;家庭智能控制器;线路敷设及防雷、接地等。 负荷等级 住宅楼的负荷等级应遵守本规范第3 章表3.2.2 常用用电负荷分级表的规定,消防电梯、应急照明等消防用电设备的负荷等级应符合消防电源的供电要求。 建筑装修标准高和设有空调系统的高级住宅、19 层及以上普通住宅的消防供电系统应按一级负荷要求设计。 10层至18层的普通住宅的消防供电系统应按二级负荷要求设计。 供配电系统 供配电系统设计应符合下列要求:

1 住宅小区的10kV供电系统宜采用环网方式。 2 住宅小区的220/380V配电系统,宜采用放射式、树干式、或是二者相结合的方式。 3 住宅小区供电系统宜留有发展的备用回路。 4 住宅小区内重要的集中负荷宜由变电所设专线供电。 5 住宅供电系统的设计,应采用TT、TN-S、TN-C-S接地方式,并进行总等电位联结。 6 每幢住宅的总电源进线断路器,应能同时断开相线和中性线,应具有剩余电流动作保护功能。 剩余电流动作值的选择应符合下列要求: 1)当住宅的电源总进线断路器整定值不大于250A 时,断路器的剩余电流动作值宜为300mA。 2)当住宅的电源总进线断路器整定值为250~400A 时,断路器的剩余电流动作值宜为500mA。 3)当住宅的电源总进线断路器整定值大于400A 时,宜在总配电柜的出线回路上分别装设若干组具有剩余电流动作保护功能的断路器,其剩余电流动作值按本款1)、2)项设定。 4)消防设备供电回路的剩余电流动作保护装置不应作用于切断电源,只应作用于报警。 5)电源总进线处的剩余电流动作保护装置的报警除在配电柜上有显示外,还宜在小区值班室设声光报警。 7 住宅小区路灯的供电电源,宜由专用变压器或专用回路供电。 8 供配电系统应考虑三相用电负荷平衡。 9 单元(层)应设电源检修断路器一个。 10 只有单相用电设备的用户,其计算负荷电流小于等于40A 时应单相供电;计算负荷电流大于40A 时应三相供电。

建筑电气课程设计---M户型住宅楼电气设计

建筑电气课程设计 工程名称:M户型住宅楼电气设计 目录 第一章建筑电气课程设计任务书 (3) 第二章照明系统 (5) 第三章建筑物防雷系统及做法 (9) 参考文献…………………………………………………

第一章建筑电气课程设计任务书 1设计题目:多层住宅楼电气设计 1.1本设计为一栋六层住宅楼的电气设计,一梯两户,层高为3.3m,包含 供配电、照明系统、防雷接地系统三部分。 2设计目的 2.1通过课程设计的实践环节,明确电气设计的流程和步骤,了解相关规 范要求,掌握建筑电气工程设计方法,熟悉电气制图及图形符号国家 标准的应用和电气工程图纸的绘制方法。训练学生的专业设计思维, 培养综合应用理论知识进行实际电气工程设计的能力。 3设计内容 3.1 计算部分 3.1.1电力负荷计算; 3.1.2照度计算及照明线路布置; 3.1.3配电线路截面积的选择计算; 3.1.4防雷、接地计算; 3.2 主要完成图纸 3.2.1干线系统图; 3.2.2配电箱系统图; 3.2.3住宅楼防雷与接地平面; 3.2.4住宅楼电气照明平面图; 3.2.5其他形成整套图纸的必须文件。 3.3 编制、编号的主要表格,文字资料 3.3.1编制设备材料表; 3.3.2编制施工图设计说明书。 4设计要求 4.1 设计原则 4.1.1设计应贯彻实用、经济、运行安全可靠、维护方便等原则,供电照 明灯具的布置、选型、色彩的配合要适当。

4.1.2设计中,在降低工程造价的前提下,应尽量采用新工艺、新技术、 新设备和新产品,达到实用、经济、美观的要求。 4.1.3设计规程、参考资料、设计手册、标准图集由设计者到图书馆查阅。 设计时从规程、手册上取用的数据、定额、计算公式应注明出处。 4.2 设计要求 4.2.1设计应遵守各项规范、定额和规定,综合运用所学理论知识和技能 独立完成工程设计,充分发挥主观能动性,严格要求,一丝不苟, 做到计算准确、说明清楚,图纸清晰美观,要能经受实践的检验; 4.2.2设计成果格式:设计说明书按照封面,任务书,摘要,目录,正文, 参考文献,封底的顺序装订。图纸需遵循绘图规范绘制,图纸幅面 不得小于A3。 4.2.3设计时间:1周,计算1天,选择方案1天,绘图2天,整理设计 说明书1天。 5设计所需原始数据资料 5.1 电源资料 5.2电源为从变电所引来一回380V/220V线路。 5.3 气象资料 5.4设计地点自定,要求同组人员选择地点不得相同。 5.5 水文、地质资料 5.6地面表层为砂质粘地、中性,地下0.5~1.0米以下为砂岩,地耐压力 不低于8T/m2;土壤电阻率雨后数天实测30欧/米;地下水位在5米以 下,含钙镁盐较多。 参考资料 6JGJ16-2008,民用建筑电气设计规范[S]. 7GB 50057-94(2000版),建筑物防雷设计规范[S]. 8GB 50034—2004,建筑照明设计标准[S]. 9段春丽,黄仕元.建筑电气[M].北京:机械工业出版社,2006. 10戴瑜兴.民用建筑电气设计手册[M].北京:中国建筑工业出版社,2000.11《建筑电气设计手册》编写组.建筑电气设计手册[M].北京:中国建筑工业出版社,1991. 12吕大光.建筑电气安装工程图集[M].北京:中国电力出版社,1997. 13戴瑜兴.民用建筑电气设备手册[M].北京:中国建筑工业出版社,1998.

高层住宅楼供配电

毕业设计 高层住宅楼供配电系统的设计 姓名: 学号: 班级: 11电气1 专业:电气工程及其自动化 所在系:自动化工程系 指导教师:

高层住宅楼供配电系统的设计 摘要 我国的城市建设过程中,住宅向着高层化趋势发展。高层住宅楼,因其为住户提供的安全、舒适、高效、节能的居住环境,受到了越来越多人的青睐,也成为现代人主要的居住方式。与此同时,高质量的高层住宅楼供配电系统的设计就显得尤为重要。在电气设计时既要考虑用电负荷日益增长的需要,又要满足供电的可靠性及安全性的要求。 本课题以高层建筑的供配电系统为研究对象。为了达到用户能够安全、可靠、高效用电的目的,我们对高层建筑的供配电系统整体进行设计。其中包括对建筑负荷的计算,选择恰当地供电方式;进行短路电流的计算,选择合适的导线及低压电器产品;对室内照明进行设计;对防雷接地的设计等。同时为了提高设计质量及缩短设计周期,本课题采用功能强大的建筑电气软件CAD来设计供配电系统的电路图。 关键词:电气设计;安全性;负荷计算;防雷接地;软件AutoCAD

The Design of High-rise Residential Building Power Supply and Distribution System ABSTRACT In the process of urban construction in our country, the housing development trend towards upwards. High-rise residential buildings, because of its for residents to provide safe, comfortable, efficient and energy saving living environment, got the favour of more and more people, modern has become the main way of living. At the same time, the high quality of high-rise residential building design of power supply and distribution system is particularly important. In the electrical design should not only consider the increasing needs of the power load, and to meet the requirements of the reliability and security of the power supply. This topic in power supply system of high-rise building as the research object. In order to achieve the user to the purpose of safe, reliable and efficient utilization, our power supply system of high-rise building the overall design. Including the building load calculation, choose proper power supply way; For the calculation of short-circuit current, select the appropriate conductor and low-voltage electrical products; For indoor lighting design; The design of lightning protection grounding, etc. At the same time in order to improve the design quality and shorten the design cycle, this subject adopts powerful building electrical software AutoCAD to design the circuit diagram of power supply and distribution system. Key Words: Electrical Design ;security;Load calculation;Lightning protection and grounding;Software AutoCAD

高层住宅建筑电气设计

摘要 本毕业设计主要介绍的是根据国家相关标准和规范对小区供配电系统进行电气设计。其主要内容包括以下几个方面:首先,按单位面积法、单位指标法进行负荷计算。其次,选择降压箱式变电站的形式及位置。最后,根据电压和计算电流选择低压电缆型号和低压配电设备。简要介绍了箱式变电站的防雷与接地,并绘制出相关的电气图纸。 关键词:负荷计算;箱式变电站;电缆;防雷接地;

Abstract The main graduation presented is based on national standards and norms forresidential electric power supply system design. Its main contents include the following aspects: First, per unit area method, unit load calculation method indicators. Next, choose the form of step-down box and the location of substation. Finally, the selectionvoltage and low voltage cable models calculate current and low voltage power distribution equipment. Outlined box substation lightning protection and grounding, and draw out the relevant electrical drawings. Keywords: load calculation; box-type substation; cable; lightning protection and grounding;

民用建筑电气设计手册(学习笔记)

民用建筑电气设计手册 ——学习笔记 一、民用建筑电气工程设计的内容 1、变配电所设计 (1)根据变配电所供电的负荷性质及其对供电可靠性的要求,进行负荷分级,从而确定所需的独立供电电源个数与供电电压等级,并确定是否设置应急备用发电机组。 (2)进行变配电所负荷计算与无功功率补偿计算,确定无功补偿容量。 (3)确定变压器形式、台数、容量。进行主接线方案选择。 (4)变配电所选址。为了节约电能与减少有色金属耗量,通常应尽可能使高压深入负荷中心。但在建筑高度甚高和大容量负荷相当分散的情况下,也可分散设置多处变电所,其布置方案应经过技术经济进行比较确定。 (5)短路电流计算与开关设备选择。 (6)二次回路方案的确定,继电保护的选择和整定计。操作电源的选择。计量与测量。(7)防雷保护与接地装置设计。 (8)变配电所电气照明设计。 高压与低压配电所的设计、除不需进行变压器选择之外,其余部分的设计内容与变电所设计基本相同。 2、高低压供配电系统设计 (1)输电线路设计 包括:线路路径及线路结构型式(架空线路还是电缆线路)的确定,导线截面选择,架空线路杆位确定及标准电杆绝缘子、金具的选择,弧垂的确定与荷载的校验,电缆敷设方式的确定,线路的导线或电缆及配电设备和保护设备选择,架空线路的防雷保护及接地装置的设计等。 (2)高压配电系统设计 高压配电多采用放射式系统,以增强其供电可靠性与控制的灵活性。对于有多处变压器分散设置的高层建筑,高压配电网络也可以采用环网结构。 主要任务:确定配电电压与网络结构;进行配电线负荷计算;选择开关设备并进行短路校验;拟定二次回路方案并进行继电保护整定计算;选择高压电缆截面、形式,确定配电干线路径与敷设方式。 还应做好防雷击与电气防火设计,以确保安全。 (3)、低压配电系统设计 主要任务:确定低压配电方式与配电网络的结构,其主要内是竖直配电干线与水平配电干线的个数,位置与走向。进行分干线与干线的负荷计算,选择开关设备及导线、电缆、封闭式母线的截面与形式。选择保护装置,进行保护整定计算并保证其级间的选择性配合,以防止穿越性跳闸。确定线路敷设方式,进行电气竖井与配电小间的设计。低压无功补偿容量计算,补偿方式与调节方式的选择。按需配置电气测量与电能计量装置。保护接地、重复接地系统的设计。 3、电力设计 电力设计通常指动力负荷的供电设计。 主要内容:在建筑平面图上确认各动力负荷的位置、容量;按各动力负荷的性质及其对供电可靠性的要求,进行负荷分级,并采取相应的供电保证措施(如双电源互投的供电方式);确定动力负荷的配电网络形式,通常多采用放射式供电。确定配电装置的位置、选择

浅析住宅照明电气插座及其回路设计

浅析住宅照明电气插座及其回路设计探讨 摘要:现代住宅中插座的选型、布置位置、数量和安装高度都直接关系到住户今后的使用效果,是现代住宅电气设计中十分重要的内容。如果电气插座设计还按照以前的做法,墨守成规的话,已经跟不上时代的步伐。现代建筑电气设计人员十分有必要对插座这个小小的电气装置元件引起足够重视。 关键词:电气插座回路设计住宅 电气插座布置 插座这个小小的电气装置元件,往往容易被人忽视,但在现代住宅中却随处可见,不管是在客厅、卧室、书房,还是在厨房、餐厅、卫生间,人们都要使用它,甚至阳台都忘不了装一个插座,以备它用。 现代生活水平不断的提高,人们对住宅电气装置的要求也越来越高,人们不再满足于照明、风扇、洗衣机、电冰箱、彩电等电气设备带来的方便,而更加热衷追求音响、空调、大屏幕彩电、电脑、电话带来的享受。随着当今知识经济、信息时代的到来,可视电话、电子购物、家庭办公等智能化住宅建筑将不断涌现。这些电能、信息的传递除通过电线、电缆外,还必须通过插座这个小小电气装置元件输送给用电设备或信息终端。可见,插座的种类和数量在现代住宅中呈日益增长的趋势。所以,现代住宅中插座的选型、布置位置、数量和安装高度都直接关系到住户今后的使用效果,是现代住宅电气设计中十分重要的内容。如果电气插座设计还按照以前的做法,墨守成规的话,已经跟不上时代的步伐。现代建筑电气设计人员十分有必要对插座这个小小的电气装置元件引起足够重视。 然而,在现实的住宅电气中,往往看到住宅建成后,住户搬进来之前,都要对原设计的电气线路进行很大的改造,这里增加一个灯,那里增加一个多用插座和电话插座,那里还要增加一个空调插座和电视插座,增加最多的就是插座,到处凿墙打洞,对整个建筑物的结构造成很大破坏,有的甚至留下安全隐患。进行线路改造者大部分又不是电气专业安装人员,时常造成烧坏家电、短路、断路、等现象,对整个建筑物的配电系统造成损害。出现上述现象的原因是多方面的,但设计不尽人意, 也是一个重要方面。

最 新《住宅建筑电气设计规范》(总结版)

《住宅建筑电气设计规范》总结版 JGJ 242 - 2011 术语 住宅建筑常用的术语有:住宅、酒店式公寓、别墅、老年人住宅、商住楼、低层住宅、多层住宅、中高层住宅、高层住宅、单元式住宅、塔式住宅、通廊式住宅、联排式住宅、跃层式住宅等。 一、供配电系统 1.应急电源与正常电源之间必须采取防止并列运行的措施。 2.住宅建筑中主要用电负荷的分级表(未列出为级宜为三级) 3.照明、航空障碍照明、生活水泵宜设自备电源供电。 4.每套住宅用电负荷和电能表的选择 注: A.S≧150 超出的建筑面积可按 40W/~50W/ 计算用电负荷 B.每套住宅用电负荷不超过 12kW用单相进户供电,超过用则三相进户 5.电能表的安装位置:安装在户外 A.低层:1~3;多层:4~6 ;按住宅单元集中安装

B.中高层:7~9;高层:10层及以上 ; 宜按楼层集中安装; C.电能表箱安装在公共场所时,暗装箱底距地宜为1.5m,明装箱底 距地宜为1.8m; 安装在电气竖井内的电能表箱宜明装,箱的上沿 距地不宜高于 2.0m。 6.方案设计阶段可采用单位指标法和单位面积负荷密度法;初步设计及 施工图设计阶段,宜采用单位指标法与需要系数法相结合的算法。 注: 当单相负荷的总计算容量小于计算范围内三相对称负荷总计算容量的 15% 时,应全部按三相对称负荷计算;当大于等于 15%时,应将单相负 荷换算为等效三相负荷,再与三相负荷相加。 二、配变电所 1.单栋住宅建筑用电设备总容量为 250kW 以下时,宜多栋住宅建筑集中 设置配变电所;单栋住宅建筑用电设备总容量在250kW 及以上时,宜 每栋住宅建筑设置配变电所。 2.当配变电所设在住宅建筑内时,配变电所不应设在住户的正上方、正 下方、贴邻和住宅建筑疏散出口的两侧,不宜设在住宅建筑地下的最 底层。 3.住宅建筑应选用节能型变压器。变压器的结线宜采用 D,yn11 ,变压 器的负载率不宜大于 85% 4.当变压器低压侧电压为 O.4kV 时,配变电所中单台变压器容量不宜大 于 1250kVA ,预装式变电站中单台变压器容量不宜大于 800kVA。 三、自备电源 1.建筑高度为 100m 或 35 层及以上的住宅建筑宜设柴油发 2.应急电源装置 (EPS) 可作为住宅建筑应急照明系统的备用电源 四、低压配电 1.住宅建筑单相用电设备由三相电源供配电时,应考虑三相负荷平衡。 2.住宅建筑每个单元或楼层宜设一个带隔离功能的开关电器,且该开关 电器可独立设置,也可设置在电能表箱里。 3.采用三相电源供电的住宅,套内每层或每间房的单相用电设备、电源 插座宜采用同相电源供电。 4.每栋住宅建筑的照明、电力、消防及其他防灾用电负荷,应分别配电。 5.住宅建筑电源进线电缆宜地下敷设,进线处应设置电源进线箱,箱内 应设置总保护开关电器。电源进线箱宜设在室内,当电源进线箱设在 室外时,箱体防护等级不宜低于 IP54。 6. 6 层及以下的住宅单元宜采用三相电摞供配电,当住宅单元数为 3 及 3 的整数倍时,住宅单元可采用单相电源供配电;7 层及以上的住宅 单元应采用三相电源供配电,当同层住户数小于 9 时,同层住户可采 用单相电源供配电。 7.每套住宅应设置自恢复式过、欠电压保护电器。 8.线缆选择 A.高层住宅建筑中明敷的线缆应选用低烟、低毒的阻燃类线缆。

探究现代建筑电气设计的特点及发展_0

探究现代建筑电气设计的特点及发展 如今我国的建筑工程电气领域发展得越来越好,但仍存在很多的问题,研究解决问题也是对未来信息化时代建筑工程电气领域的发展有一定实际的意义。利用电气工程能够促使建筑工程完成得更加全面。本文主要对现代建筑电气设计的特点及发展进行了分析研究。 标签:建筑工程;电气设计;技术问题;未来发展 引言 我国的科技水平和社会经济发展都在飞速前进,进而对现代建筑电气设计也提出了新的要求,需要将人性化、智能化和实用性结合起来,需要不断创新和完善设计水平才能满足现代建筑对电气设计的要求。电气设计需要以安全性、经济性和实用性为基本原则,还要充分考虑现代科技和信息技术的发展,将新型技术融合到电气设计中,也是必然的发展趋势,设计中需要充分将以上特点和发展趋势结合起来,才能不断提升我国现代建筑电气设计的整体水平。 1现代建筑中电气设计的必备特点 1.1人性化 现代建筑必须要迈向人性化,首先就需要电气设计趋于人性化,将这个理念始终贯穿于电气设计中,才能满足现代建筑的需求。电气设计要满足建筑的使用需要,包含照明和防盗等,还要满足人们对空间的需求,并要保持空间内的空气流通,便于温度的传递等。还要考虑外部设计,内外都需要符合设计理念并满足人性化要求。 1.2经济化 现代建筑电气化设计需要充分考虑经济化,不可做无谓的浪费,充分考虑造价和成本,结合考虑使用效率等因素,以节约成本和提升使用效率为设计的重要参考标准,以节约环保为原则。 1.3难度大 现代建筑电气设计面临着越来越多的挑战,随着现代建筑的发展和人们越来越高的要求,电气设计需要充分考虑各个方面的因素,还要对建筑的运行进行整体筹划,确保使用中能够协调运作,同时还要确保利益最大化。现代建筑需要多样化和人性化,这不但需要设计创新,还增加了复杂度,这些都是电气设计需要克服的新困难。 2电气设计技术性问题

中华人民共和国行业标准民用建筑电气设计规范Codeforelectrical

中华人民共和国行业标准 民用建筑电气设计规范 Code for electrical design of civil buildings JGJ 16-2008 J 778-2008 批准部门:中华人民共和国建设部 施行日期:2008年8月1日 中华人民共和国建设部 公告 第800号 现批准《民用建筑电气设计规范》为行业标准,编号为JGJ16-2008,自2008年8月1日起实施。其中,第3.2.8、3.3.2、4.3.5、4.7.3、4.9.1、4.9.2、7.4.2、7.4.6、7.5.2、7.6.2、7.6.4、7.7.5、11.1.7、11.2.3、11.2.4、11.6.1、11.8.9、11.9.5、12.2.3、12.2.6、12.3.4、12.5.2、12.5.4、12.6.2、14.9.4条为强制性条文,必须严格执行。原行业标准《民用建筑电气设计规范》JGJ/T16-92同时废止。 本规范由建设部标准定额研究所组织中国建筑工业出版社出版发行。 1 总则

1.0.1 为在民用建筑电气设计中贯彻执行国家的技术经济政策,做到安全可靠、经济合理、技术先进、整体美观、维护管理方便,制定本规范。 1. 0. 2 本规范用于城镇新建、改建和扩建的民用建筑的电气设计,不适用于人防工程、燃气加压站、汽车加油站的电气设计。 1. 0.3 民用建筑电气设计应体现以人为本,对电磁污染、声污染及光污染采取综合治理,达到环境保护相关标准的要求,确保人居环境安全。 1.0.4 民用建筑电气设计的装备水平,应与工程的功能要求和使用性质相适应。 1.0.5 民用建筑电气设计应采用成熟、有效的节能措施,降低电能消耗。 1.0.6 应选择符合国家现行标准的产品。严禁使用已被国家淘汰的产品。1.0.7 民用建筑电气设计,应采取经实践证明行之有效的新技术,提高经济效益、社会效益。 1.0.8 民用建筑电气设计除应符合本规范外,尚应符合国家现行有关标准的规定。 2 术语、代号 2.1 术语

建筑电气课程设计参考.

目录 第1章概述 (3) 1.1工程概述........................................................................ .. (3) 1.2 设计要求 (3) 第2章供配电系统设计 (4) 2.1动力系统的负荷计算 (4) 2.2插座的选择与布置 (5) 2.3 动力系统导线型号及截面的选择 (5) 第3章照明系统设计 (12) 3.1 光源的选择 (12) 3.2灯具的选择 (13) 3.3照明负荷计算 (17) 第4章电气设备的选择 (19) 4.1低压断路器的选择 (19) 4.2低压开关柜的选择 (21) 4.3 系统原理图 (22) 参考资料 (23) 课程设计总结 (23)

一、概述 1.1工程概述: 设计对象为某部队综合楼第二层,假设其高为3.5m,窗高1.8m,卫生间,开关,楼梯间的工作面高度为地面,其余工作面高度均为0.75米。电源采用三相四相制AC380v/220v供电。设计内容包括照明灯具设计、开关、插座、配电箱布置,电气管线选用,以及总配电箱、分配电箱内部线路、电气设备选用。 1.2设计要求: (1)总的要求: 室内布线应在基建施工时布置在墙内,墙上应留有足够的插座,保证居民住进去后不需要布置明线而各种家电都可以使用。由于单相用电设备的使用是经常变化的,不可能做到两相平衡,因此一般情况下不要两个单相支路共用一根中性线。 (2)配线: 室内配线不仅要使电能的输送可靠,而且要使线路布置合理、整齐、安装牢固,符合技术规范的要求。内线工程不能降低建筑物的强度和影响建筑物的美观。在施工前要考虑好与给排水管道、热力管道、风管道以及通讯线路布线等的位置关系。室内配线技术要求如下: ①室内布线根据绝缘皮的颜色分清火线、中性线和地线。 ②选用的绝缘导线其额定电压应大于线路工作电压,导线的绝缘应符合线路的安装方式和敷设的环境条件。导线的截面应满足供电能力和供电质量的要求。还应满足防火的要求。 ③配线时应尽量避免导线有接头。因为往往接头由于工艺不良等原因而使接触电阻太大,发热量较大而引起事故。必须有接头时,可采用压接和焊接,务必使其接触良好,不应松动,接头处不应受到机械力的作用。 ④当导线穿过楼板时,应装设钢管或PVC管加以保护,管子的长度应从高楼板面2m处到楼板下出口处为止。 ⑤当导线互相交叉时,为避免碰线,在每根导线上应套上塑料管或绝缘管,并需将套管固定。 (3)穿管: 若导线所穿的管为钢管时,钢管应接地。当几个回路的导线穿同一根管时,管内的绝缘导线数不得多于8根。穿管敷设的绝缘导线的绝缘电压等级不应小于500V,穿管导线的总截面积(包括外护套)应不大于管内净面积的40%。 (4)开关: 住宅室内的总开关、支路总开关和所带负荷较大的开关(如电炉、取暖器等)应优先选用具有过流保护功能、维护操作简单且能同时断开火线和中性线的负荷开关,如HK-2系列闸刀等。表箱内每户出线的火线上安置1个单极自动开关,用户住宅门口的接线盒内安装1个漏电开关,室内总开关和分支总开关用闸刀。所有灯具的开关必须接火线(相线),否则会影响到用电安全及经济用电。 1)有利于对人的活动安全、舒适和正确识别周围环境,防止人与环境之间失去协调;

浅探住宅照明电气插座及其回路设计

浅探住宅照明电气插座及其回路设计关键字:住宅照明;电气插座;回路设计 摘要:插座这个小小的电气装置元件,往往容易被人忽视,但在现代住宅中却随处可见,不管是在客厅、卧室、书房,还是在厨房、餐厅、卫生间,人们都要使用它,甚至阳台都忘不了装一个插座,以备它用。 keyword: residential lighting; electrical socket; circuit design abstract: the socket this small electrical devices components, often ignored, but in the modern house but is everywhere, whether in the sitting room, bedroom, study, or in the kitchen, restaurant, toilet, people have to use it, and even the balcony all unforgettable pack a socket, ready to use it. 中图分类号:s611文献标识码:a 文章编号: 现代生活水平不断的提高,人们对住宅电气装置的要求也越来越高,人们不再满足于照明、风扇、洗衣机、电冰箱、彩电等电气设备带来的方便,而更加热衷追求音响、空调、大屏幕彩电、电脑、电话带来的享受。随着当今知识经济、信息时代的到来,可视电话、电子购物、家庭办公等智能化住宅建筑将不断涌现。这些电能、信息的传递除通过电线、电缆外,还必须通过插座这个小小电气装置元件输送给用电设备或信息终端。可见,插座的种类和数量在现

高层建筑电气设计要点浅析(标准版)

高层建筑电气设计要点浅析 (标准版) Safety work has only a starting point and no end. Only the leadership can really pay attention to it, measures are implemented, and assessments are in place. ( 安全管理 ) 单位:______________________ 姓名:______________________ 日期:______________________ 编号:AQ-SN-0761

高层建筑电气设计要点浅析(标准版) - 摘要:随着我国经济建设的飞速发展,我国房地产市场也有了很大进步,住宅建设高速增长尤其是以成片开发的住宅小区为主,以多层、小高层住宅组团分布并配以会所、广场、健身场所、超市、幼儿园、学校等完善的配套设施。 关键词:住宅建筑;电气设计;配电设计 引言 随着建筑智能化水平的不断提高,高层建筑电气设计增加了很多弱电部分系统,包括数字电视系统、综合布线系统、背景音乐系统,保安监控系统,电脑的管理系统等。弱电设备占基建投资比率越来越高,所以设计好弱电各个系统,对于节约投资、提高智能化水平都有非常重要的意义。

一﹑高层建筑电气设计的特点 与高层建筑电气关联的用电设备品种繁多。室内、楼梯过道、安全照明等电器照明设备;货梯、客梯等电梯设备;生活水泵和消防泵等给排水设备;冷却塔风机以及水机组等制冷设备;引风机和鼓风机等锅炉房设备;排风机、电冰箱等厨房设备;包括送风机、回风机、风机管盘在内的空调系统送电设备;包括正压风机、排烟风机等在内的消防设备;另外,不同用处的高层建筑在用电量上也存在差别,不过总的来说耗电量比较大。再加上高层建筑的消防用电、客梯电力、应急照明等还要有分别独立的电源。 二﹑高层建筑电气设计的主要内容 (一)用电负荷的计算 高层建筑供电设计的重要参数依据就是电力负荷,其计算的准确程度对选择合理设备并确保电力安全可靠的运行,都能起到重要作用,并发挥节能功效。一般用电负荷的计算方式主要采取负荷密度法与需要系数法。 (二)高低压配电系统的设计

建筑电气设计规范手册

§表达线路敷设方式、部位、照明灯具安装方式的文字代号§ 表达内容 标注代号对照 表达内容 标注代号对照 表达内容 标注代号对照 英文代号汉语拼音代号英文代号汉语拼音代号英文 代号 汉语拼音代号 用轨形护套线敷设GBV 沿钢索敷设SR S 线吊式CP 用塑制线槽敷设PR XC/VXC 沿屋架或层架下弦敷设BE LM 自在器线吊 式 CP X 用硬质塑制管敷设PC VG 沿柱敷设CLE ZM 固定线吊式CP1 X1 用半硬塑制管敷设FEC ZVG/BYG 沿墙敷设WE QM 防水线吊式CP2 X2 用可挠型塑制管敷设KRG 沿天棚敷设CE PM 吊线器式CP3 X3 用薄电线管敷设TC DG 在能进入的吊顶内敷设ACE PNM 链吊式CH L 用厚电线管敷设G 暗敷在梁内BC LA 管吊式P G 用水煤气钢管敷设SC G/GG 暗敷在柱内CLC ZA 吸顶式或直 附式 S D 用金属线槽敷设SR GC/GXC 暗敷在屋面内或顶板内CC PA 嵌入式R R 用电缆桥架(或托盘)敷设CT 暗敷在地面内或地板内FC DA 顶棚内安装CR DR 用瓷夹敷设PL CJ 暗敷在不能进入的吊顶内AC PNA 墙壁内安装WR BR 用塑制夹敷设PCL VT 暗敷在墙内WC QA 台上安装T T 用蛇皮管敷设CP 柱上安装(灯具)CL Z 支架上安装SP J 用瓷瓶式或瓷柱式绝缘子敷设K CP 座装(灯具)HM ZH 壁装式W B 2

3 §室内电气管线、配电设备与其它管道、设备之间的最小距离表§ 注:1、表内无括号数字为电气管线在管道上面时的数据,有括号数字为电气管线在管道下面时的数据。 2、在不能满足表中所列距离情况下,应采取下列措施: (1) 电气管线与蒸气管线不能保持表中距离时,应在蒸气管或电气管外包以绝热层,此时平行净距可减减至200毫米,交叉处仅 须考虑施工操作和便于维护的距离。 (2) 电气管线与暖水管不能保持表中距离时,可在暖水管外包绝热层。 (3) 裸母线与其它管道交叉不能保持表中距离时,应在交叉处的裸母线外加装保护网或罩。 3、当上水管与电气管线平行敷设且在同一垂直面时,应将电气管线敷设于水管之上。 §钢材重量换算表§ 线路布线 方式 各种布线与其它用途的管道间最小距离 煤气管 乙炔管 氧气管 蒸气管 暖热水管 通风管 上水、下水管 压缩空气管 工艺设备 平行 交叉 平行 交 叉 平行 交 叉 平行 交叉 平行 交叉 平行 交 叉 平行 交叉 平行 交 叉 平行 交叉 导线穿金属管 100 100 100 100 100 100 1000 (500) 300 300 (200) 100 电缆 500 300 1000 500 500 300 1000 (500) 300 500 100 200 100 200 100 200 100 明敷绝缘导线 1000 300 1000 500 500 300 1000 (500) 300 300 (200) 100 200 100 200 100 200 100 裸母线 1000 300 2000 500 1000 500 1000 500 1000 500 1000 500 1000 500 1000 500 1500 1500 吊车滑触线 1500 500 3000 500 1500 500 1000 500 1000 500 1000 500 1000 500 1000 500 1500 1500 配电设备 1500 3000 1500 500 100 100 100 100

相关主题
文本预览
相关文档 最新文档