给水设计,净水厂工程设计计算书
- 格式:doc
- 大小:802.00 KB
- 文档页数:25
目录第一章总论 .......................................................................................................... - 2 -1.1设计任务及要求......................................................................................... - 2 -1.1.1设计题目.......................................................................................... - 2 -1.1.2设计背景.......................................................................................... - 2 -1.1.3设计任务.......................................................................................... - 2 -1.2原始资料与水质分析................................................................................. - 2 -1.2.1设计水量.......................................................................................... - 2 -1.2.2地质条件.......................................................................................... - 2 -1.2.3气象条件.......................................................................................... - 2 -1.2.4原水水质及分析.............................................................................. - 3 - 第二章设计原则与净水工艺选择 ........................................................................ - 4 -2.1设计原则..................................................................................................... - 4 -2.2厂址选择..................................................................................................... - 4 -2.3工艺选择..................................................................................................... - 5 -2.3.1选择依据.......................................................................................... - 5 -2.3.2常见处理工艺.................................................................................. - 6 -2.3.3工艺选择.......................................................................................... - 7 - 第三章净水构筑物及其计算 ................................................................................ - 7 -3.1配水井......................................................................................................... - 7 -3.2混凝剂类型及加药间................................................................................. - 7 -3.2.1混凝剂.............................................................................................. - 7 -3.2.2混凝剂的投加.................................................................................. - 9 -3.2.3溶解池、溶药池设计计算............................................................ - 10 -3.2.4加药间及药库布置........................................................................ - 11 -3.3混合设施................................................................................................... - 11 -3.3.1混合方式........................................................................................ - 11 -3.3.2机械混合池.................................................................................... - 13 -3.4隔板絮凝池............................................................................................... - 15 -3.4.1一般要求........................................................................................ - 15 -3.4.2设计计算........................................................................................ - 15 - 3.5平流沉淀池设计计算................................................................................ - 20 -3.6普通快滤池设计计算............................................................................... - 23 -3.6.1已知条件........................................................................................ - 24 -3.6.2 设计计算....................................................................................... - 24 -3.7加氯设备................................................................................................... - 30 -3.7.1 加氯量的确定....................................... - 30 -3.7.2 加氯设备........................................... - 30 -3.7.3 加氯间............................................. - 31 -3.8 清水池设计计算...................................................................................... - 31 -3.8.1 平面尺寸计算....................................... - 31 -3.8.2 管道系统........................................... - 32 -3.8.3清水池布置......................................... - 33 - 第四章净水厂总体布置设计计算 ...................................................................... - 34 -4.1工艺流程布置设计................................................................................... - 34 -4.2平面布置设计........................................................................................... - 34 -4.3高程布置设计........................................................................................... - 35 -4.3.1各构筑物间连接管中流速计算.................................................... - 35 -4.3.2各构筑物间水头损失计算................................. - 36 -小结............................................................................................ 错误!未定义书签。
净水厂设计计算书设计计算书:净水厂设计一、引言净水厂是为了提供清洁、安全、可靠的饮用水供应服务而建立的设施。
本设计计算书旨在对净水厂的设计进行全面的计算和说明,以确保其设计符合相关标准和要求。
二、设计流程1.确定供水规模和水质要求:根据用户需求确定净水厂的设计处理量,并确定水质要求,包括对悬浮物、有机物、微生物和化学成分的要求。
2.水源调查和选择:对供水水源进行调查和评估,确定其水质和水量,并选择最适合的水源。
3.工艺流程选择:选择适当的净水工艺流程,包括预处理、混凝、絮凝、过滤、消毒等环节,并根据水源水质和水量要求进行计算。
4.工艺设备选择:根据工艺流程选择适当的设备,并进行设备数量和尺寸的计算。
常用设备包括澄清池、絮凝池、滤池、曝气池、消毒装置等。
5.设备布置和管道设计:根据工艺设备的尺寸和数量,进行设备布置和管道设计,以确保净水效果和流程的顺畅。
6.水源保护措施:根据供水水源的特点,设计并实施相应的水源保护措施,确保供水水源的安全和可靠性。
7.操作和维护方案:制定净水厂的操作和维护方案,包括设备的日常操作、维护保养和定期检查等,以确保净水厂的正常运行。
三、设计计算1.净水流程计算:根据设计处理量和工艺流程,计算净水的流程和时间,并确定各个环节的处理效果。
2.设备尺寸计算:针对各种设备,进行尺寸计算,包括澄清池的容积、滤池的面积、消毒装置的处理量等,以确保设备能够满足设计要求。
3.管道设计计算:根据净水厂的布置和管道的长度、直径等参数,进行管道设计计算,并确定管道的材料和压力等级。
4.水力计算:针对净水流程、设备和管道,进行水力计算,包括管道的流速、压力损失、泵的扬程和功率等。
5.投资和运行成本计算:根据设备和材料的价格以及净水厂的运行成本,进行投资和运行成本的计算,并进行经济效益评估。
四、设计结果与讨论根据以上计算,得到净水厂的设计结果,并对其进行讨论,包括工艺流程的合理性、设备的选择和尺寸、管道的布局以及经济效益等方面。
某县净水厂给水处理设计计算书县净水厂给水处理设计计算书1.项目背景和目的县净水厂给水处理设计的目的是为了解决该县居民饮水问题。
该县面临着水资源短缺和水质污染的双重挑战。
通过建设一座净水厂,可以有效地提高水质,保障居民的健康饮水需求。
2.设计参数(1)城市规模:县人口约30万人,预测未来15年内增长10%。
(3)水质要求:根据国家标准,出水水质需要符合饮用水标准。
3.工艺流程根据给水处理的工艺要求,设计采用以下流程:原水进水池→格栅→调节池→自流式砂滤池→混凝沉淀池→滤水池→消毒池→供水。
其中,原水经过格栅、调节池预处理后,进入砂滤池进行过滤。
滤后水进入混凝沉淀池,经过混凝沉淀后再进入滤水池,最后经消毒处理后供水。
4.工艺参数计算(4)滤水池:滤水池的水层深度一般为1~2.5m,本设计采用1.5m。
(5)混凝剂投加量:根据原水悬浮物浓度和水质要求,确定混凝剂投加量。
一般情况下,混凝剂投加量为铝盐的0.8~1.0 mg/L。
本设计按照0.9 mg/L来计算。
5.工艺图纸根据上述设计参数和工艺流程,绘制出净水厂给水处理流程图纸。
6.总结和展望通过对县净水厂给水处理的设计计算,我们可以得出合理的设施规模和工艺参数。
通过提供高效的净水处理流程,该县居民可以获得更干净、更健康的饮用水。
然而,未来水资源短缺和水质污染问题仍然存在,需要进一步加强水资源保护和管理工作。
以上是县净水厂给水处理设计计算书,设计过程中考虑到了城市规模、水质要求等因素,为解决该县的饮水问题提供了有力的支持。
希望该设计能够对相关领域的学生和专业人士有所帮助。
二 设计计算内容一、 水厂规模及水量确定综合生活用水量:Q 1=270000×250×96%=64800000L/d=64800m 3/d 生产用水量:Q 2=12000+12000+12000+8000=44000m 3/d 工业企业用水量:Q 3=[(25×1600×3+35×400×3+60×400×3)+(25×1600×3+35×400×3+40×400×3)+(25×1000×3)+(25×1600×3)]/1000=639m 3/d 浇洒绿地用水量:Q 4=(Q 1 +Q 2 +Q 3 )×10%=(64800+44000+639) ×10%=10944m 3/d 未预见用水及管网漏水量: Q 5=20%×(Q 1+Q 2+Q 3+Q 4)=24077 m 3/d 设计水量:Q d =Q 1+Q 2+Q 3+Q 4+Q 5=144460 m 3/d=6019 m 3/h=1.67 m 3/s 水厂自用水量取5% Q I =1.05×TQd=6320.125 m 3/h 消防水量:Qx=55×2=110L/s=9504 m 3/d二. 给水工艺流程的确定及构筑物的选择 2.1工艺流程的确定水厂以地表水作为水源,工艺流程如图1所示。
原水混 合絮凝沉淀池滤 池混凝剂消毒剂清水池二级泵房用户图1 水处理工艺流程2.2构筑物形式的选择根据已选工艺流程,在设计中混合设施选用机械混合池,反应池选用折板絮凝池,沉淀池选用平流式沉淀池,滤池选用V 型滤池,采用加氯消毒。
三、 给水单体构筑物设计计算 (一) 混凝剂配制和投加 1. 设计参数根据原水水质及水温,参考有关净水厂的运行经验,选聚合氯化铝为混凝剂。
一、用水量计算用水定额取3L/人.d,总用水人数3000人,取时变化系数Kh=2.5,用水时间T=10小时。
最大日用水量为:Qdmax=3×3000=9000L/d=9m3/d最大时用水量为:Qhmax=2.5×9/10=2.25m3/h二、设备选型计算1、制水量Qh净水站设计制水能力按最高日平均时流量考虑。
因Qh=9/10 m3/h=0.9 m3/h,净水站制水能力按1.0 m3/h设计。
2、水处理流程自来水→原水箱→原水泵→砂滤罐→炭滤罐→软水器→精滤器→↑回水高压泵→一级反渗透→高压泵→二级反渗透→臭氧混合塔→成品水箱→供水泵→稳压罐→用户。
3、设备选型计算假设反渗透装置的水回收率为50%,则前处理阶段净水设备设计净水能力应为2.0 m3/h。
(1)原水箱取调节时间T=1.5h,则水箱容积V=2×1.5=3.0 m选用不锈钢水箱一个,水箱尺寸为φ1400×H2000mm。
(2)原水泵水量Q2.0 m3/h,扬程H按砂滤罐所需进水压力及管路水损考虑,选择丹麦格兰富不锈钢立式多级离心泵CR2-30型一台,流量Q2.0 m3/h,扬程H30m,功率P0.37KW。
(3)砂滤器处理水量2.0 m3/h,滤速设为7m/h,则过滤面积F为:F=Q/v=2.0/7=0.286m2 过滤器直径D=(4F/π)1/2=600mm。
砂滤层厚度1.5m,选择美国OSMONICS型砂滤器一台(带多路阀),外形尺寸为φ600×H1800mm。
(4)炭滤器处理水量2.0 m3/h,滤速设为7m/h,则过滤面积F为:F=Q/v=2.0/7=0.286m2 过滤器直径D=(4F/π)1/2=600mm。
炭滤层厚度1.5m,选择美国OSMONICS型砂滤器一台(带多路阀),外形尺寸为φ600×H1800mm。
(5)软水器由于没有详细的水质资料,无法进行计算,根据经验选择OSMONICS型软水器一台(带多路阀),外形尺寸为φ350×H1650mm。
净水工程设计计算书一、双阀滤池1) 设计数据(1)设计规模:10万吨/日,分两期实施,水厂的用水系数1.05;(2)设计流量:Q =1.05×5×104m 3/d =2187.5 m 3/h =0.6076m 3/s ;(3)设计滤速:按规模要求,单层石英砂滤料的滤速V =8~10m/h ,这里取8.1 m/h ;(4)冲洗强度:12~15L /s·m 2,取13 L /s·m 2;(5)冲洗时间:t =6min ; 2) 主要计算(1)滤池面积及尺寸滤池工作时间为24h ,冲洗周期按12h 计;滤池实际工作时间T =24-(0.1×1224)=23.8(h );(注:式中只考虑反冲洗时间,未考虑初滤水的排放时间);滤池面积:2433.2728.231.805.1100.5m VT Q F ===;采用滤池格数:N =8,布置成对称双行;则单格滤池面积:204.34833.2728m F f ===;采用滤池长宽比3.1=BL,规范要求:1.25:1~1.5:1;每格滤池尺寸:L=6.6m ,B =5.1m ;复核:因此,每格滤池实际过滤面积f =B ×L =6.6×5.1=33.66m 2;滤池实际的正常滤速h m F Q V h /12.866.3385.2187=?==校核强制滤速h m N NV V /28.912.81881=?-=-=' (2)滤池高度支承层高度 H 1采用0.58m (d10~d32的支承层顶面应高于配水系统孔眼100mm );滤料层高度 H 2采用0.7m ;砂面以上水深 H 3采用1.90m ;超高(干管) H 4采用0.27m ;故滤料总高度 H =H 1+H 2+H 3+H 4=3.45m ;(3)配水系统(每格滤池)Ⅰ、干管干管流量 =?=q f q g 13.5 L /s·m 2×33.66 m 2=0.454m 3/s; 采用管径 d g =700mm (干管应埋入池底,顶部开孔接配水支管,详大样水施1-5-5);因此,干管起端流速V g =1.18m/s ;(注:若采用d g =800mm ,则V g =0.91m/s <1.0 m/s =;Ⅱ、支管支管中心间距采用 a j =0.25m ;每格滤池支管数 n j =5225.06.622=?=?j a L 根;每根支管入口流量 s L n q q jg j /73.852454===;采用管径 d j =80mm (公称外径90mm ,查《塑料给水管水力计算表》P86);支管始端流速 V j =1.56m/s ;Ⅲ、孔眼布置支管孔眼总面积与滤池面积之比K 采用0.25%;则孔眼总面积 F k =K f =0.25%×33.66=0.08415m 2=84150mm 2;采用孔眼直径 d k =9mm ;每个孔眼面积 f k =2225.639785.041mm d k =?=π;孔眼总数 13255.6384150===k k k f F N 个;每根支管孔眼数 26521325===j k k n N n 个;支管孔眼布置:设两排,与垂线成45°夹角,向下交错排列;每根支管长度 L j =0.5B =2.55m (注:两端除去间隙,L j =2.31m );每排孔眼中心距:m n L a k j k 178.0262131.221=?==Ⅳ、孔眼水头损失支管壁厚δ=5mm ;孔眼直径与壁厚之比8.159==δkd ,查《流量系数μ值表》得流量系数μ=0.68;水头损失 m g k q g h k 2.325.068.0105.1321102122=??=???? ??=μ;Ⅴ、复核配水系统支管长度与直径之比不大于60,60875.28080.031.2<==jj d L ;孔眼总面积与支管总横截面积之比小于0.5,()5.0322.008.0785.05208415.02<=??=j j k f n F ;干管横截面积与支管横截面积之比为1.75~2.0,()()47.108.0785.0527.0785.022==j j gf n f ;孔眼中心距应小于0.2m ,a k =0.178m<0.2m ;(4)洗砂排水槽洗砂排水槽中心距采用a 0=1.70m ;排水槽根数n 0=7.11.5=3根;排水槽长度m L l 6.60==;每根排水槽排水量s L a ql q /47.1517.16.65.13000=??==;采用三角形标准断面槽中流速采用V 0=0.6m/s ;横断面尺寸m V q x 251.06.0100047.1512110002100=?==,取0.25m ;排水槽槽底厚度采用δ=0.005m ;砂层最大膨胀率e =45%;砂层厚度H 2=0.70m ;洗砂、排水槽顶距砂面厚度H e =eH 2+2.5x +δ+0.075 =0.45×0.70+2.5×0.25+0.08 =1.02m ;洗砂、排水槽总平面面积00002n l x F ==2×0.25×6.6×3=9.9m 2;复核:排水槽总平面面积与滤池面积之比,一般小于25%,%25%4.29%10066.339.90≈=?=f F ;排水槽底高出集水槽底的高度2.0100081.03 2+??=b fg H=0.56+0.2=0.76m ;槽底距集水槽起端水面的高度不小于0.05~0.20m ;(5)滤池各种管渠计算Ⅰ 进水进水总流量 Q 1=52500m 3/d =0.6076m 3/s ;采用进水渠断面:渠宽B 1=0.8m ,水深为0.6m (两根进水管);渠中流速V 1=0.66m/s ,水力坡降2.7‰;进水总管管径(每5万吨设两根进水管)Q 2=h m /75.109324205.1100.534=,则进水管采用DN700,管中流速V 2=0.79m/s ;Ⅱ 冲洗水冲洗水流量Q 3=qf =13.5×33.66=0.454m 3/s ;采用管径D 3=500mm ;管中流速V 3=2.26m/s ;Ⅲ 清水清水总流量Q 4=Q 1=0.6076m 3/s ;清水总管管径采用D 4=800mm ,则V 4=1.21m/s ;每格滤池清水管流量Q 5=Q 2=86076.0=0.076m 3/s ;采用管径D 5=300mm ,则V 5=1.04m/s ;强制滤速下,5V '=1.19m/s ;Ⅳ 排水排水流量Q 6=Q 3=0.454m 3/s ;排水渠断面:渠宽B 6=0.8m ,水深为0.6m ;渠中流速V1=0.66m/s ;(6)进水虹吸管虹吸管进水量()s m Q /0868.01824360005.1100.534=-=进;事故冲洗进水量()s m Q /101.028********.1100.534=-=事;断面面积20.217m0.40.0868===进进进V Q ω;取用断面尺寸进ω=B ×L =0.4×0.5=0.2m 2;进水虹吸管局部水头损失∑?1.22gV 2进事局=ξf h0.505m/s 0.21.01Q V ===进事进事ω ∑?=++=出口弯头进口ξξξξ290 0.5+0.8×2+1.0=3.10.048m 1.29.8120.5053.12==局f h进水虹吸管的沿程水头损失L RC V 22?进事沿=f hm 111.0)5.04.0(22.0R =+?==进χω 32.63)111.0(012.0116161===R n CL 取2m0.00115m20.11163.322=??=沿f h 则局沿+f f f h h h ==0.048+0.00115=0.049m 取f h =0.1m;(7)进水槽及配水槽进水虹吸管出口至槽底h 1取0.25m ;进水虹吸管淹没水深h 2取0.25m ;配水槽出水堰宽b 1取1.2m ;配水堰堰顶水头0.128m 1.21.840.101)b 1.84(32323=)=(进事??=Q h ;进水堰超高C 取0.35m ;则H 进=h 1+h 2+h 3+h f +C =0.25+0.25+0.128+0.1+0.35 =1.078m ,取1.05m ;(8)排水虹吸管冲洗排水量Q 排=qf =13.5×33.66=0.454m 3/s ;排水虹吸管滤速V 排=1.4~1.6m/s ,取V 排=1.5m/s ;则220.303m1.50.454===排V qf ω;采用矩形断面,其尺寸为B 2×L 2=0.45×0.675=0.3015m 2;排水虹吸管管长L=10m ;∑2g V 2排局=ξf h 0.36m 9.8121.513.12==?? L RC V 22排沿=f hm 134.0)675.054.0(23015.0R 2=+?==χω 61.59)134.0(012.0116161===R n C0.05m 100.13459.612=??=沿f h则局沿+f f f h h h ==0.36+0.05=0.41m (9)反冲洗水泵计算水泵所需的供水量Q =qf =13.5×33.66=0.454m 3/s =1634.4m 3/h ;水泵所需扬程H=H 0+h 1+h 2+h 3+h 4+h 5H 0—排水槽顶与清水池最低水位之差;(5.45m )1h —从清水池至滤池间冲洗管道中的总水头损失,计算可得h 1=1.82m ;2h —滤池配水系统的水头损失;(3.2m )3h —承托层的水头损失;(0.13m ) 4h —滤料层膨胀时水头损失m h 68.07.0)41.01)(1165.2(4=?--=; 5h —富裕水头损失;(1.5m )则H=5.45+1.82+3.2+0.13+0.68+1.5=12.78m ;选冲洗水泵两台,一用一备。
福州市西区水厂一期扩建工程设计阐明书1自然条件1.1地形、地质福州市地处闽江下游福州盆地,盆地总面积约200Km2,四周有鼓山、旗山、五虎山莲花峰等群山环抱。
地貌类型以平原为主,地势由西北向东南倾斜,市中心散落有乌山、于山和屏山等小山,南台岛上有仓山、盖山和城门山。
市区高程普通为5~15m(黄海高程系),闽江横贯市区,由于地势较低,易受洪涝灾害,需沿江、河筑堤。
市区重要有两类地质:一是靠山丘陵地区,重要在于于山、乌山、屏山一带以及市区四周群山余脉高地和仓山区丘陵地带,容许承载力约0.25Mpa;二是淤积、冲积地区为高压缩性土,范畴较广,淤泥埋藏浅,容积承载力为0.05~0.08MPa,地下水位高,普通在地面下0.5~2.0m。
1.2气象条件福州市属于亚热带海洋性季风气候,夏季炎热多雨,冬季温暖少雨。
(1)气温年平均:19.6摄氏度极端最高:41.1摄氏度(1950年7月19日)极端最低:-2.5摄氏度(1940年1月25日)(2)水量年平均:1355.8mm年平均降水天数:151.2天24小时最大降水量:167.4mm暴雨重要浮现月份:5~9月(3)霜冻年无霜期326天(4)风常年主导风向为西北风和东南风,冬季多西北风,夏季盛行东南风。
平均风速:2.8m/s极大风速:40.7m/s基本风压:0.6KN/m2台风影响我市始于5月,结束于11月中旬,以7月中旬至9月中旬次数最多。
(5)湿度年平均相对湿度77%最大相对湿度84%最小相对湿度5%(6)蒸发量年平均蒸发量 1451.1mm1.3水文条件闽江是福建省最大河流,水量充沛。
闽江在淮安如下分为两支,北支为北港,穿越市区至马尾,将中心城区别为江北平原和南台岛两某些,长为30.5km,平均水面坡降0.15‰,枯水季水面宽150~200m。
南支为南港,又名乌龙江,经洪塘、湾边、纳入大漳溪河后来,出峡兜于马尾、长乐营前与北港又合二为一,南港长34.4km,进入河口段经亭江、倌口、琅歧流入东海。
1、供水规模与原水水质
设计规模:1万m3/d
自用水量:6%
净水厂设计水量:10600m3/d,441.67m3/h,122.7L/s
原水浊度2.41NTU,色度12度,PH=6.83,耗氧量:1.44mg/L,铁含量0.641mg/L,锰含量0.779mg/L
2、曝气池计算
设计采用1级跌水曝气
跌水高度,宜为0.5-1.0m(规范P57),设计选取0.8m。
单宽流量,宜为20-50m3/(m*h)(规范P57),设计选取30 m3/(m*h)。
池子个数为2个。
则曝气池边长φ=441.67/2/30=7.36m,半径r=1.17m,设计半径为1.20m。
外池与内池距离选取1.4m,两曝气池距离选取1.6m,则外池长L=9.0m。
3、普通快滤池计算
滤料选取锰砂滤料d=1mm,厚度宜为0.8-1.2m(规范P58),设计1.4m。
承托层650mm(手册P814)
滤上水深,宜为1.5-2.0m(手册P617),设计选取2.0m。
滤池超高,一般采用0.3m(手册P617),设计选取0.3m。
滤池深度=0.65+1.4+2.0+0.3=4.35m。
普通快滤池,滤速宜为5-8m/h(手册P814),选取V=5.5m/h。
每日工作时间23h,日反冲洗一次。
滤池面积F=Q/VT,(手册P616),F=10600/5.5/23=83.8m2。
设计4座滤池(手册P616),单池面积20.95m2,设计平面尺寸4.5x4.5m,校核滤速=5.69m/h。
强制滤速5.69*4/3=7.58m/h。
课程设计计算说明书课题名称《水质工程学》—净水厂课程设计学院(系)建筑工程学院管理与市政工程系专业给水排水工程学号学生姓名2010 年7 月 3 日至2009 年7 月17 日共 2 周一、设计目的及任务1.目的城市给水处理设计室给水工程课程教学环节之一,其目的在于加深理解所学的知识,培养学生运用所学的理论和技术知识分析和解决实际工程设计问题的初步能力,使学生在设计、运算、绘图、查阅资料设计手册及使用设计规范等基本技能上得到初步训练和提高,初步树立技术经济意识。
2.任务根据所给的资料和设计要求进行系统设计,并对主要构筑物或设备的工艺尺寸进行计算,确定平面布置和高程布置,最后绘制出系统图、平面布置图和高程图,并简要写出一份设计说明书和工艺计算书,给出设备清单和材料清单。
二、水厂总体设计水厂厂址的选择,应符合城镇总体规划和相关专项规划,并根据下列要求综合确定:1.给水系统布局合理;2.不受洪水威胁;3.有较好的废水排除条件;4.有良好的工程地质条件;5.有便于远期发展控制用地的条件;6.有良好的卫生环境,并便于设立防护地带;7.少拆迁,不占或少占良田;8.施工、运行和维护方便。
水厂总体布置应结合工程目标和建设条件,在确定的工艺组成和处理构筑物形式的基础上进行。
平面布置和竖向设计应满足各构筑物的功能和流程要求;水厂附属建筑和附属设施应根据水厂规模、生产和管理体制,结合当地实际情况确定。
三、给水处理厂的设计规模及流程选择1.根据《室外给水设计规范》(GB50013-2006)可知:水处理构筑物的设计水量,应按最高日供水量加水厂自用水量确定。
水厂自用水率应根据原水水质、所采用的处理工艺和构筑物类型等因素通过计算确定,一般可采用设计水量的5%-10%。
当滤池反冲洗水采取回用时,自用水率可适当减小。
本设计水厂最高日供水量为Q=20×104m3/d,滤池反冲洗水采取回用,水厂自用水系数1取5%。
水厂自用水量Q2=20×104×5%=1.0×104 m3/d则给水处理厂处理规模为Q=Q1+Q2=21.0×104 m3/d2.给水处理厂的主要构筑物拟分为2组,2组平行设置,同时运行,每组处理规模为10.5×104 m3/d。
目录第一章设计原始资料第二章设计水量与工艺流程的确定第一节设计水量计算第二节给水处理流程确定第三章给水处理构筑物与设备型式选择第一节加药间第二节配水井第三节混合设备第四节絮凝池第五节沉淀池第六节滤池第七节消毒方法第四章净水厂工艺计算第一节加药间设计计算第二节配水井设计计算第三节混合设备设计计算第四节往复式隔板絮凝池设计计算第五节平流式沉淀池设计计算第六节普通快滤池设计计算:第七节消毒和清水池设计计算第八节取水水泵选配及一级泵房设计计算第九节二级泵站第五章水厂平面布置和高程布置计算第一节水厂平面布置第二节水厂高程布置计算第三节净水管道水力计算第四节附属建筑物第四节净水厂绿化与道路第六章净水工艺自动化设计第一章 设计原始资料一、地理条件:地形平坦,稍向西倾斜,地势平均标高22m (河岸边建有防洪大堤)。
二、水厂位置占地面积:水厂位置距离河岸200m ,占地面积充分。
三、水文资料:河流年径流量3.76-14.82亿立方米,河流主流量靠近西岸。
取水点附近水位:五十年一遇洪水位:21.84m ; 百年一遇洪水位:23.50m ; 河流平常水位:15.80m ; 河底标高:10m 。
四、气象资料及厂区地址条件:全年盛行风向:西北;全年雨量:平均63mm ;冰冻最大深度1m 。
厂区地基:上层为中、轻砂质粘土,其下为粉细沙,再下为中砂。
地基允许承载力:10-12t/m 2。
厂区地下水位埋深:3-4m 。
地震烈度位8度。
五、水质资料:浊度:年平均68NTU ,最高达3000NTU ;PH 值:7.4-6.8;水温:4.5-21.5℃;色度:年平均为11-13度;臭味:土腥味;总硬度:123.35mg/L CaCO 3;溶解氧:年平均10.81 mg/L ;Fe :年平均0.435 mg/L ,最大为0.68 mg/L ;大肠菌群:最大723800个/mL ,最小为24600个/ mL ;细菌总数:最大2800个/ mL ,最小140个/ mL 。
六、水质、水量及其水压的要求:设计水量:根据资料统计,目前在原地下水源继续供水的情况下,每天还需7万立方米。
水质:满足现行生活饮用水水质标准。
水压:二级泵站扬程按50米考虑。
第二章 设计水量与工艺流程的确定第一节 设计水量计算水处理构筑物的生产能力,应以最高日供水量加水厂自用水量进行设计,并以水质最不利情况进行校核。
水厂自用水量主要用于滤池冲洗和澄清池排泥等方面。
城镇水厂自用水量一般采用供水量的5%~10%,本设计取10%,则设计处理量为:44333(1)(110%)7107.710/3208/0.89/d Q a Q m d m h m s =+=+⨯⨯=⨯==式中: Q ——水厂日处理量;a ——水厂自用水量系数,一般采用供水量的5%~10%,本设计取10%;Q d ——设计供水量(m 3/d ),为7万m 3/d 。
第二节 给水处理流程确定给水处理工艺流程的选择与原水水质和处理后的水质要求有关。
本设计以地表水为水源,为满足现行生活饮用水水质标准,通常采用混合、絮凝、沉淀、过滤、消毒的处理工艺。
第三章给水处理构筑物与设备型式选择第一节加药间一、药剂溶解池设计药剂溶解池时,为便于投置药剂,溶解池的设计高度一般以在地平面以下或半地下为宜,池顶宜高出地面0.20m左右,以减轻劳动强度,改善操作条件。
溶解池的底坡不小于0.02,池底应有直径不小于100mm的排渣管,池壁需设超高,防止搅拌溶液时溢出。
由于药液一般都具有腐蚀性,所以盛放药液的池子和管道及配件都应采取防腐措施。
溶解池一般采用钢筋混凝土池体,若其容量较小,可用耐酸陶土缸作溶解池。
二、混凝剂的选用与投加1、混凝剂的选用混凝剂选用:精制硫酸铝,每袋质量是40Kg,每袋体积为0.5*0.4*0.2(m3),最大投药量为30mg/L。
2、混凝剂的投加本设计采用计量加药泵,泵型号JZ-800/10,选用3台,两用一备。
三、加氯间设计加氯间时,须按以下要求进行设计:(1)加氯间靠近滤池和清水池,以缩短加氯管线的长度。
水和氯应充分混合,接触时间不少于30min。
为管理方便,和氯库合建。
(2)加氯间和氯库应布置在水厂的下风向。
该水厂所在地主导风向为西北风,加氯间应设在水厂的东南部。
(3)加氯间的氯水管线应敷设在地沟内,直通加氯点,地沟应有排水设施以防积水。
输送氯气的管使用无缝钢管,输送配制成一定浓度的氯水管使用橡胶管,给水管使用镀锌管。
(4)加氯间和其他工作间隔开,加氯间应有直接通向外部、且向外开的门,加氯间和值班室之间应有观察窗,以便在加氯间外观察工作情况。
(5)加氯机的间距约0.7m,一般高于地面1.5m左右,以便于操作,加氯机(包括管道)不少于两套,以保证连续工作。
称量氯瓶重量的地磅秤,放在磅秤坑内,磅秤面和地面齐平,使氯瓶上下搬运方便。
有每小时换气8-12次的通风设备。
加氯间的给水管应保证不断水,并且保持水压稳定。
加氯间外应有防毒面具、抢救材料和工具箱。
防毒面具应防止失效,照明和通风设备应有室外开关。
第二节配水井配水井体积为213.6m3,平面尺寸为11m×4m=44m2,水力停留时间T=4min,有效水深5m。
第三节混合设备为提高混合效果,采用管式静态混合器,加药点设在混和器进口处,并增加药液扩散器,使混凝剂在管道内很好的扩散,形成均匀混合。
管式静态混合器具有投资较低,无需额外提供能源,易于安装,无需经常维修,混合效果好的显著优点。
第四节絮凝池絮凝过程就是在外力作用下,使具有絮凝性能的微絮粒相互接触碰撞,而形成更大具有良好沉淀性能的大的絮凝体。
目前国内使用较多的是各种形式的水力絮凝及其各种组合形式,主要有隔板絮凝、折板絮凝、栅条(网格)絮凝、和穿孔旋流絮凝等。
根据各种絮凝池的特点以及实际情况进行比较,本设计选择往复式隔板絮凝池。
第五节 沉淀池本设计采用平流沉淀池。
相比之下,平流式沉淀池具有适应性强、处理效果稳定和排泥效果好等特点,且占地面积大。
第六节 滤池从实际运行状况来看,普通快滤池主要有以下优点: 1、有成熟的运转经验,运行稳妥可靠。
2、采用砂滤料,材料易得,价格便宜。
3、采用大阻力配水系统,单池面积可做的较大,池深较浅。
4、可采用降速过滤,水质较好。
根据设计资料,综合比较选用目前较广泛使用的普通快滤池。
第七节 消毒方法水的消毒处理是生活饮用水处理工艺中的最后一道工序,其目的在于杀灭水中的有害病原微生物,防止水致传染病的危害。
其方法分化学法与物理法两大类,前者往水中投加药剂,如氯、臭氧、重金属、其他氧化剂等;后者在水中不加药剂,而进行加热消毒、紫外线消毒等。
经比较,本设计采用液氯作为消毒剂,滤后消毒。
氯是目前国内外应用最广的消毒剂,除消毒外还起氧化作用。
加氯操作简单,价格较低,且在管网中有持续消毒杀菌作用。
虽然二氧化氯消毒能力较氯强而且能在管网中保持很长时间,但是由于二氧化氯价格昂贵,且其主要原料亚氯酸钠易爆炸,国内目前在净水处理方面应用尚不多。
第四章 净水厂工艺计算第一节 加药间设计计算一、设计参数根据原水水质及水温,参考有关净水厂的运行经验,选精制硫酸铝为混凝剂,混凝剂的最大投药量a=30mg/L ,药的容积的浓度按b=10%考虑,混凝剂每日配制次数n=3次。
二、设计计算1、溶液池容积:31113032087.69417417103W Q m bn μ==⨯⨯=⨯⨯,取8m 3式中:a —混凝剂(精制硫酸铝)的最大投加量(mg/L ),本设计取30mg/L ;Q —设计处理的水量,3208m 3/h ; b —溶液浓度(按商品固体重量计),一般采用5%-20%,本设计取10%; n —每日调制次数,一般不超过3次,本设计取3次。
溶液池采用矩形钢筋混凝土结构,设置2个,。
有效高采用1.0m, 则单池尺寸为 2.0 2.0 1.3L B H m m m ⨯⨯=⨯⨯, 高度中包括超高0.3m ,置于室内地面上。
溶液池实际有效容积:32.0 2.0 1.3 5.2W m '=⨯⨯=,满足要求。
2、溶药池容积:3210.30.34 1.2W W m ==⨯=式中:W 2 ——溶解池容积(m 3 ),一般采用(0.2-0.3)W 1;本设计取0.3 W 1。
溶解池池体尺寸为:B ×L ×H=2.0m ×1.0m ×(0.6+0.3)m 。
溶解池的放水时间采用t=10min ,则放水流量:s L t W q /0.2106010002.16020=⨯⨯==查水力计算表得放水管管径d0=50mm ,相应流速v0=1.02m/s 。
溶解池底部设管径d=100mm 排渣管一根。
3.投药管投药管流量:s L W q /278.0606024100038606024100031=⨯⨯⨯⨯=⨯⨯⨯⨯=查表得投药管管径d=25mm ,相应流速为0.57m/s 。
溶解池底部设管径d=100mm 的排渣管一根。
4.投药计量设备采用计量加药泵,泵型号JZ —800/10,选用三台,两用一备。
加药间的平面尺寸取为B ×L=12m ×25m 。
5.药剂仓库的计算 (1)已知条件混凝剂为精制硫酸铝,每袋质量是40kg ,每袋体积为0.5×0.4×0.2(m3)。
投药量为40mg/L ,水厂设计水量为3208m 3/h 。
药剂堆放高度为1.5m ,药剂储存期为30d 。
(2)设计计算 硫酸铝的袋数:(袋)23104030403208024.0024.0100024=⨯⨯==⨯=W Qut W ut Q N有效堆放面积:2772.015.12.04.05.02310)1(m e H NV A =-⨯⨯⨯⨯=-=)(仓库平面尺寸B ×L=7m ×11m 。
第二节 配水井设计计算一、设计参数设计流量:43337.710/0.89/53.4/min Q m d m s m =⨯== 水力停留时间: 4.0min T =; 二、设计计算配水井体积: 353.44213.6V QT m ==⨯=; 配水井平面尺寸:211444m m m ⨯=; 有效水深:213.64.8544H m ==。
取5m ,超高取0.5m ,则井深为5.5m 。
配水井出水处设溢流堰,采用渠道与絮凝池连接,渠道宽b=1.0m ,流速取v=1.0m/s ,则有效水深为0.890.89,1.01Q h m bv ===⨯ 取0.9米超高取0.3m ,渠道深'(0.90.3) 1.2H m m =+=。
配水井设DN=1000mm 的溢流管,溢流水位0.60m ,放空管直径DN=700mm 。
第三节 混合设备设计计算一、设计参数设计总进水量为Q=77000m 3/d ,水厂进水管投药口靠近水流方向的第一个混合单元,投药管插入管径的1/3处,且投药管上多处开孔,使药液均匀分布,进水管采用2条,流速v=1.0m/s 。