当前位置:文档之家› 110kV变电站电气主接线设计_毕业设计(论文)说明书

110kV变电站电气主接线设计_毕业设计(论文)说明书

110kV变电站电气主接线设计_毕业设计(论文)说明书
110kV变电站电气主接线设计_毕业设计(论文)说明书

毕业设计(论文)说明书

110kV变电站电气主接线设计

摘要

随着城市化的发展,城郊已经纳入城市的发展规划,供电方面要求越来越高,特别是供电的安全性、可靠性和持续性。电网的安全性、可靠性和持续性往往取决于变电站的合理设计和配置。一个典型的变电站要求变电设备运行可靠、操作灵活、经济合理、扩建方便。

本论文设计了一个降压变电站,此变电站有三个电压等级:高压侧电压为110kV。中压侧电压为35kV,有八回出线。低压侧电压为10kV,有十四回出线。同时对于变电站内的主要设备进行合理的选型。本设计选择选择两台SFSZ11-63000/110主变压器,其他设备如断路器、隔离开关、电流互感器、高压熔断器、电压互感器和继电保护装置等等也按照具体要求进行选型、设计和配置,力求做到运行可靠,操作简单、方便,经济合理,具有扩建的可能性和改变运行方式时的灵活性,使其更加贴合实际,更具现实意义。

关键字:降压变电站;电气主接线;变压器;设备选型。

Abstract

With the development of citilization, The planning of city expanding has included the skirts of a town , The requirement of power supply is higher and higher , especially to the security、reliability and endurance .But the security、reliability and endurance of the electrical network often rely on the transformer substation’s rationality an d disposition. One typical transformer substation requests the equipments in it work reliably, operate nimbly, being carried on reasonably and easy to expend .

Refer to these several reasons, in this article we devise a transformer substation for abasing voltage, which has three voltage rates: the high voltage rate is 110kV; the middle voltage rate is 35kv, which has eight routes; the low voltage rate is 10kV, which has fourteen routes. In the same time ,we select the main equipments for the transformer substation .This article select two main transformer (SFSZ11-63000/110) and other equipments, for example : breaker , isolator ,current transformer, voltage transformer, high voltage fuse , idle work compensator ,the protecting equipments and so on are also selected ,devised and disposed according to the actual fact. What’s more, we try our best to mange to make the substation work reliably, operate nimbly, be carried on reasonably and easy to be expended. So that it can close the fact more.

Keywords: transformer substation; electrical main wiring; transformer; equipment type selection.

目录

摘要............................................................................................................................................. I Abstract ..................................................................................................................................... II 目录.......................................................................................................................................... III 1 概述. (1)

1.1 概述 (1)

1.2 设计任务 (1)

1.2.1 待设计变电站基本情况 (1)

1.2.2 设计任务 (2)

2 电气主接线设计 (4)

2.1 主接线设计的要求 (4)

2.2 主接线设计 (4)

2.2.1 110kv主接线设计 (4)

2.2.2 35kV主接线设计 (5)

2.2.3 10kV主接线设计 (6)

3 主变压器的选择 (9)

3.1 变压器容量和台数的确定 (9)

3.2 变压器型号的确定 (9)

4 短路电流的计算 (11)

4.1 短路计算的原因与目的 (11)

4.2 短路计算的条件 (11)

4.2.1短路计算原则 (11)

4.2.2短路计算的一般规定 (12)

4.3 最大最小运行方式分析 (12)

4.3.1最大运行方式 (12)

4.3.2最小运行方式 (13)

4.3.3基本假定 (13)

4.3.4基准值的选择 (13)

4.3.5各元件参数标幺值的计算 (14)

4.4 短路电流的计算 (15)

4.4.1短路计算的目的 (15)

4.4.2短路计算 (16)

5 电气设备的选择 (18)

5.1 电气设备选择要求 (18)

5.1.1电气设备选择技术条件 (18)

5.2 高压断路器的选择 (19)

5.3 隔离开关的选择 (20)

5.4 各级电压母线的选择 (20)

5.4.1 110kV侧母线的选择 (21)

5.4.2 35kV侧母线的选择 (21)

5.4.3 10kV侧母线的选择 (21)

5.5 绝缘子和穿墙套管的选择 (22)

5.6 电流互感器的配置和选择 (22)

5.6.1参数选择 (22)

5.6.2型式选择 (23)

5.7 电压互感器的配置和选择 (23)

5.7.1参数选择 (23)

5.7.2型式选择 (24)

5.7.3 110kV侧PT的选择 (24)

5.7.4 35kV母线PT选择 (24)

5.8 各主要电气设备选择结果一览表 (25)

6 过压保护及接地 (26)

6.1 过电压保护 (26)

6.2 接地装置 (27)

7 消防通风通信及监控 (28)

7.1 消防 (28)

7.2 通风 (28)

7.3 通讯 (28)

7.4 监控 (28)

7.4.1、闭路监控系统 (29)

7.4.2、防盗、防火报警系统 (29)

毕业设计总结 (30)

致谢 (32)

参考文献 (33)

附录1 (34)

附录2 (35)

附录3 (36)

1 概述

1.1 概述

随着国民经济的发展和人民生活水平的提高,对供电质量的要求日益提高。国家提出了加快城网和农网建设和改造、拉动内需的发展计划,110kV变电站的建设迅猛发展。供电可靠性是城网建设改造的一个重要目标,110kV变电站设计是成网建设分中较为关键的技术环节,如何设计110kV变电站,是城网建设和改造中需要研究和解决的一个重要课题。

1.2 设计任务

1.2.1 待设计变电站基本情况

该变电站位于湖北省沙洋县后港镇,该地区地势平坦,交通便利,空气污染轻微。所处自然条件:

年最高气温:45℃

年最底气温:-5℃

年平均气温:18℃

最热月平均最高温度:30℃

土壤温度:25℃

土壤电阻率:7000Ω.cm

该变电站建成后主要作为供给城郊的工厂以及一部分城郊居民生活用电。该变电站的电压等级为110kV/35kV/10kV,110kV是电源电压,35kV和10kV是二次电压。供电源由50公里外的兴隆港110kV变电站供给,备用电源为相距50km的110kV沙洋变电站经沙后线受电。该变电站带负荷情况见表1-1、表1-2。

表1-1 35kV母线侧所带负荷

负荷名称有功功率(MW)功率因数

拾桥镇变 5 0.9

十里铺镇变 1.3 0.9

蛟镇变 4.8 0.9

管珰镇变 6.5 0.9

古泵镇变 5 0.9

毛李镇变 4.8 0.9

系统

35kV 中压35kV 侧计划送出线8回,其中2回备用。

表1-2 10kV 母线侧所带负荷

负荷名称

有功功率(MW ) 功率因数 纺织厂1

1 0.9 纺织厂2

2.3 0.9 纺织厂3

2.3 0.9 塑料厂

2.2 0.9 加工厂

2 0.9 材料厂

1.2 0.9 食品厂

0.8 0.9 化工厂 0.8 0.9

低压10kV 侧计划送出线14回,其中4回备用,2回接站用变压器。

待设计变电站与电力系统的连接关系如下图1-3所示

图1-1 关系图 1.2.2 设计任务

(1)选择本变电所主变的台数、容量和类型;

(2)变电所电气主接线设计,选出几个电气主接线方案进行技术经济比较,确定一个较佳方案;

(3)短路电流计算;

(4)选择和校验所需电气设备(主变压器、断路器、隔离开关、母线、10kV 电缆、

电流互感器和电压互感器等等);

(5)防雷保护规划设计;

(6)画出变电站主接线和站用电图纸;

注:设计图纸应符合国家有关规程、规范。

本章小结:

本章主要对设计任务和原始资料进行收集。其中包括设计背景,环境资料,以及变电站近期所供给的对象以及负荷容量进行资料收集整理,并且提出待设计变电站的一次部分设计的任务和要求。

2 电气主接线设计

2.1 主接线设计的要求

变电站电气主接线的选择是根据变电站在系统中的地位和作用、地理位置、电压等级、变压器台数及容量和进出线等各种条件综合优化决定的。城市电网的安全可靠性固然重要,但是城市人口密度大,用地紧张,因此城网变电站接线除了满足安全可靠性外,还必须尽量简单化。因此变电站设计应该满足一下基本要求:

1、运行可靠

断路器检修时是否影响供电;设备和线路故障检修时,停电数目的多少和停电时间的长短,以及能否保证对重要用户的供电。

2、具有一定的灵活性

主接线正常运行时可以根据调度的要求灵活的改变运行方式,达到调度的目的,而且在各种事故或设备检修时,能尽快地退出设备。切除故障停电时间最短、影响范围最小,并且再检修在检修时可以保证检修人员的安全。

3、操作应尽可能简单、方便

主接线应简单清晰、操作方便,尽可能使操作步骤简单,便于运行人员掌握。复杂的接线不仅不便于操作,还往往会造成运行人员的误操作而发生事故。但接线过于简单,可能又不能满足运行方式的需要,而且也会给运行造成不便或造成不必要的停电。

4、经济上合理

主接线在保证安全可靠、操作灵活方便的基础上,还应使投资和年运行费用小,占地面积最少,使其尽地发挥经济效益。

5、应具有扩建的可能性

由于我国工农业的高速发展,电力负荷增加很快。因此,在选择主接线时还要考虑到具有扩建的可能性。

变电站电气主接线的选择,主要决定于变电站在电力系统中的地位、环境、负荷的性质、出线数目的多少、电网的结构等。

2.2 主接线设计

2.2.1 110kv主接线设计

方案I:采用单母线分段接线

优点:1、用断路器把母线分段后,对重要用户可以从不同段引出两个回路,有两

个电源供电。

2、当一段母线发生故障,分段断路器自动将故障段切除,保证正常段母线不间断供电和不致使重要用户停电。

缺点:1、当一段母线或母线隔离开关故或检修时,该段母线的回路都要在检修期间内停电。

2、扩建时需向两个方向均衡扩建。

适用范围:适用于35-63kV配电装置的出线回路数为4-8回时。

方案II:采用双母线接线

优点:供电可靠,调度灵活,扩建方便。

适用范围:一般适用于出线回路多,容量较大的配电装置中,35-60kV出线数超过8回,或连接电源较大,负荷较大时。

经过对比,决定采用单母分段接线方式。

2.2.2 35kV主接线设计

该变电站中压35kV侧有8回出线,其中2回是备用。其负荷情况如下表2-1所示:

表2-1 35kV母线侧所带负荷

负荷名称有功功率(MW)功率因数

拾桥镇变 5 0.9

十里铺镇变 1.3 0.9

蛟镇变 4.8 0.9

管珰镇变 6.5 0.9

古泵镇变 5 0.9

毛李镇变 4.8 0.9

参考35kV负荷情况,考虑以下两种优化方案:

方案I:采用单母线分段接线

优点:(1)用断路器把母线分段后,对重要用户可以从不同段引出两个回路,有两个电源供电。

(2)当一段母线发生故障,分段断路器自动将故障段切除,保证正常段母线不间断供电和不致使重要用户停电。

缺点:(1)当一段母线或母线隔离开关故或检修时,该段母线的回路都要在检修期间内停电。

(2)扩建时需向两个方向均衡扩建。

适用范围:35-63kV配电装置的出线回路数为4-8回时。

方案II:采用双母线接线

优点:供电可靠,调度灵活,扩建方便。

适用范围:一般适用于出线回路多,容量较大的配电装置中,35-60kV出线数超过8回,或连接电源较大,负荷较大时。

经过对比,决定采用双母线接线方式。

2.2.3 10kV主接线设计

该变电站低压10kV侧计划出线14回,其中4回备用,2回接站用变压器。10kV 侧负荷如下表2-2所示:

表2-2 10kV母线侧所带负荷

负荷名称有功功率(MW)功率因数

纺织厂1 1 0.9

纺织厂2 2.3 0.9

纺织厂3 2.3 0.9

塑料厂 2.2 0.9

加工厂 2 0.9

材料厂 1.2 0.9

食品厂0.8 0.9

化工厂0.8 0.9

方案I:采用单母线接线

优点:接线简单、设备少、操作方便、经济性好,并且母线便于向两端延伸,便于扩建。

缺点:(1)可靠性差。母线或母线隔离开关检修或故障时,所有回路都要停止运行,造成全站长期停电。

(2)调度不方便,电源只能并列运行,不能分列运行,并且线路侧发生短路时,有较大的短路电流。

适用范围:这种接线形式一般只用在出线回路少,并且没有重要负荷的发电厂和变电站中。

方案II:采用单母线分段接线

优点:(1)用断路器把母线分段后,对重要用户可以从不同段引出两个回路,有两个电源供电。

(2)当一段母线发生故障,分段断路器自动将故障段切除,保证正常段母线不间断供电和不致使重要用户停电。

缺点:(1)当一段母线或母线隔离开关故或检修时,该段母线的回路都要在检修期间内停电。

(2)扩建时需向两个方向均衡扩建。

适用范围:6 -10kV配电装置的出线回路数为6回及以上时。

为保证对重要负荷的可靠供电,和快速检修,经过以上论证,决定采用单母线分段接线。

图2-1和图2-2分别为所选用的单母线分段接线和双母线接线形式。

图2-1单母线分段接线

图2-2 双母线接线

本章小结:

本章主要对变电站三个电压侧(110kV、35kV和10kV)的主接线方式进行方案分析比较。从经济方面、运行可靠性方面和维修灵活性方面综合研究分析并确定各侧均采用单母线分段接线方式。此方案可以保证重要负荷在一部分线路故障时的可靠运行,并减少维修时繁琐的步骤跟时间,实现最优化运行。

3 主变压器的选择

3.1 变压器容量和台数的确定

首先确定主变压器的容量。变电站容量确定原则如下:

(1)按供电负荷和5~10年规划负荷确定

(2)重要变电站按一台停运其余满足负荷的供电。

(3)非重要变电站按一台停运,其余变满足全部负荷(70~80)%。

可得到变压器的容量为:

MVA S S c N 45.59%)81(5110=+=

其中8%为当地经济增长率,5为符合规划的5年。

变压器台数与电压等级、接线形式、传输容量及与系统联系紧密有关。变压器台数确定原则如下:

(1)与系统联系紧密大中站,2台以上。

(2)与系统联系弱小型厂站,1台。

(3)地区孤立的变电站或大型企业变电站设3台变压器。

结合所给资料可知,该变电站应选用两台一样,并且容量都为63MV A 的主变压器,其中一台为备用。

3.2 变压器型号的确定

变压器相数的确定:

在330kV 及以下的电路系统中,一般采用三相变压器。

绕组数的确定:

在具有三种电压的变电所中,如果通过主变压器的功率达到该主变压器容量的15%及以上,或低压侧虽然无负荷,但在变电所内需要装设无功功率补偿装置时,主变压器宜采用三绕组变压器。结合本次设计的具体实际情况,都应选择三绕组变压器。

绕组连接组号的确定:

变压器三相绕组的连接组号必须和电压相位一致,否则不能并列运行。电力系统采用的绕组连接方式只有星型“Y ”和三角型“d “两种,为保证消除三次谐波的影响,必须有一个绕组为“d ”型。我国110kV 及以上的电压等级均为大电流接地系统,为取得中性点,所以都需要选择“Y ”的连接方式,而35kV 经消弧线圈接地采用Y ,6~10kV 侧采用“d ”型连接方式。

所以本次设计的变电站主变压器绕组连接方式为:Y/Y/d

调压方式的确定:

变压器的调节方式有两种:无励磁调压和有载调压。无励磁调压的调整范围通常在±2×2.5%以内;有载调压的调整范围可达30%,其结构复杂,价格较贵,只有在以下情况才予以选用:接于输出功率变化大的发电厂的主变压器,特别是潮流方向不固定,且要求变压器二次电压维持在一定水平时,接于时而为送端、时而为受端、具有可逆工作特点的联络变压器,为保证供电质量,要求母线电压恒定时。

为了保证供电质量,110kV及以下变压器应至少有一级电压的变压器采用有载调压。因此该站的主变压器110kV高压侧选择有载调压。

变压器冷却方式的确定:

油浸式电力变压器的冷却方式随其型式和容量的不同而异,一般有自然风冷却、强迫风冷却、强迫油循环水冷却、强迫油循环风冷却、强迫油循环冷却等。中小型变压器通常采用依靠装在变压器油箱上的片状或管形辐射式冷却器及电动风扇的自然风冷却及强迫风冷却方式散发热量。

容量在31.5MV A及以上的大容量变压器一般采用强迫油循环风冷却方式;容量在350MV A及以上的特大容量变压器一般采用强迫油循环导向冷却方式。因此主变压器选用强迫油循环风冷却方式。

根据以上设计原则,本次110kV变电站设计所采用的变压器确定为三绕组有载调压变压器,相关数据如下:

型号:SFSZ11-63000/110

额定容量:63/63/63MV A

额定电压:115±8?1.25%/37?

±2 2.5%/10.5kV

高压侧调压范围:110±8?1.25%kV

中压侧调压范围:37±2?2.5%kV

本章小结:

本章针对变电站计划运行的情况,对负荷功率进行计算。针对计算结果,主变压器决定选择两台63MV A的三相变压器,一方面可以保证近期负荷的可靠供电,一方面也提供相对大的容量供远期扩展。站用电方面也预备了足够的容量,确保了检修时站用电关键区的可靠运行。

4 短路电流的计算

4.1 短路计算的原因与目的

电力系统由于设备绝缘破坏,架空线路的线间或对地面导电物短接,或雷击大气过电压以及工作人员的误操作,都可能造成相与相、相与地之间导电部分短接,短路电流高达几万安、几十万安培。这样大的电流所产生的热效应及机械效应,会使电气设备损坏,人身安全受到威胁,由于短路时系统电压骤降,设备不能运行。单相接地在中性点直接接地系统中,对邻近通信设备将产生严重的干扰和危险影响,所以电力系统必须进行短路故障计算。另外,对于电气设备的规格选择,继电保护的调整整定,对载流导体发热和电动力的核算,都需要对系统短路故障进行计算。

短路计算选择有足够机械稳定度和热稳定度的电气设备。为了合理地配置各种继电保护和自动装置并正确整定其参数,必须对电力网中发生的各种短路进行计算和分析。在设计和选择发电厂。电力系统电气主接线时,为了比较各种不同方案的接线时,确定是否需要采用限制短路电流的措施等,都需要进行必要的短路电流计算。计算电力系统暂态稳定计算,研究短路对用户工作的影响等,也包含有短路计算的内容。在确定输电线路对通讯的干扰,对已经发生的故障进行分析,都必须进行短路计算。

4.2 短路计算的条件

4.2.1短路计算原则

短路计算中采用以下假设条件和原则:

(1)正常工作时,三相系统对称运行。

(2)所有电源的电动势相位角相同。

(3)电力系统中各元件的磁路不饱和,即带铁芯的电气设备电抗值不随电流大小发生变化。

(4)短路发生在短路电流为最大值的瞬间。

(5)不考虑短路点的电弧阻抗和变压器的励磁电流。

(6)除计算短路电流的衰减时间常数和低压网络的短路电流外,元件的电阻都略去不计。

(7)元件的计算参数均取其额定值,不考虑参数的误差和调整范围。

(8)输电线路的电容略去不计。

4.2.2短路计算的一般规定

(1)验算导体和电器的动稳定、热稳定以及电器开断电流所用的短路电流,应按本工程设计规划容量计算,并考虑电力系统5—l0 年的远景发展规划。确定短路电流时,应按可能发生最大短路电流的正常接线方式,而不应按仅在切换过程中可能并列运行的按线方式。

(2)选择导体和电器用的短路电流,在电气连接的网络中,应考虑具有反馈作用的异步电动机的影响和电容补偿放电电流的影响。

(3)选择导体和电器时,对不带电抗器回路的计算短路点,应选择在正常接线方式时短路电流为最大的点;对带电抗器6—l0kV 出线,选择母线到母线隔离开之间的引线、套管时,短路计算点应取在电抗器之前、其余导体和电器的计算短路点一般选择在电抗器后。

(4)电器的动稳定、热稳定以及电器的开断电流,一般按三相短路电流计算。若中性点直接接地系统及自耦变压器等回路中的单相、两相接地短路较三相短严重时,则应按严重的计算。

4.3 最大最小运行方式分析

在选择保护方式分析时,对大多数保护都必须认真分析与考虑哪种运行方式来作为计算的依据,一般而言所选用的保护方式,应在系统的各种故障参数增加而动作的保护,如电流保护,通常应根据系统最大运行方式来确定保护的定值,以保证选择性,因为只要在最大运行方式下能保证选择性。那么,在其他运行方式下,必然能保证选择性;而对灵敏性校验,则应根据最小运行方式来进行,因为只要在最小运行方式下,灵敏性合格,那么在其他运行方式下的灵敏性就会更好,对反映鼓掌参数减小而动作的欠量保护。如低压保护,刚刚好相反,此时应根据最小运行方式来整定,而根据最大运行方式来校验灵敏性。

4.3.1最大运行方式

根据系统最大负荷的要求,电力系统中的所有可以投入的发电设备都投入运行(全部或绝大部分投入运行),以及所有线路和规定的中性点全部投入运行的方式称为系统最大运行方式即QF1、QF2都在闭合的状态。对继电保护而言,则是指在系统最大运行方式下短路时,通过该保护的短路电流为最大时的系统连接方式。本设计题目中,本变电站的最大运行方式为两台63MV A的变压器并联运行,以及所有负荷投入时的运行方式。但由于纵联差动保护,由于其保护范围外故障时,保护不应动作。为了方便变压器

纵联差动的整定计算,在变压器高压侧和低压侧的短路点的电流应为支路电流。所以变压器高压侧的短路点电流为变电站高压侧投入的,断路器闭合时,流过变压器高压侧的短路电流。变压器低压侧的短路电流为系统并联运行桥短路器连接,变压器单台投入时流入变压器低压侧的短路电流。

4.3.2最小运行方式

根据系统负荷为最小,投入与之相适应的系统连接且系统中性点只有少部分接地的运行方式称为系统的最小运行方式。本设计题目中,变电站的最小运行方式为,变压器单台投入时的运行方式即QF1、QF2都在打开状态。

4.3.3基本假定

(1)系统运行方式为最大运行方式。

(2)磁路饱和、磁滞忽略不计。即系统中各元件呈线性,参数恒定,可以运用叠加原理。

(3)在系统中三相除不对称故障处以外,都认为是三相对称的。

(4)忽略对计算结果影响较小的参数,如元件的电阻、线路的电容以及网内的电容器、感性调和及高压电机向主电网的电能反馈等。

(5)短路性质为金属性短路,过渡电阻忽略不计。

(6)系统中的同步和异步电机均为理想电机。

4.3.4基准值的选择

为了计算方便,通常取基准容量Sj =100MV A ;

基准电压Uj 取各级电压的平均电压,即:

基准电压:

U j =U p =1.05Ue

(4-1) 基准电流:

j j

j U S I 3= (4-2)

基准电抗:

j j j j

j S U I U X 23== (4-3)

常用基准值如表4-1所示。

表4-1常用基准值表(S

=100MV A )

4.3.5各元件参数标幺值的计算

电路元件的标幺值为有名值与基准值之比,计算公式如下:

j U U U =* (4-4)

j S S S =* (4-5)

j j j S U I I I I 3*== (4-6) 2*j j j U S X X X X == (4-7)

采用标幺值后,相电压和线电压的标幺值是相同的,单相功率和三相功率的标幺值也是相同的,某些物理量还可以用标幺值相等的另一些物理量来代替,如I *=S *。

电抗标幺值和有名值的变换公式如表4-2所示。

表4-2中各元件的标幺值可由表4-1中查得。

表4-2各电气元件电抗标幺值计算公式

元件名称

标幺值 备注 发电机 ?cos S 100%''''*N j d d P X X ?= X d “%为发电机次暂态电抗的百分值。

变压器 N j k T S S U X ?=100%* U k %为变压器短路电压百分值,S N 为最大容量线圈额定容量。

电抗器 2N N *

S I 3U 100%j j k k U X X ??= X k %为电抗器的百分电抗值。

线路 2

0*j j

l U S l X X = l 为线路长度。

系统阻抗 S S S S X b kd b C ==* S kd 为与系统连接的断路器

的开断容量;S 为已知系统

短路容量。

其中线路电抗值的计算中,0X 的取值为:

6~220kV 架空线,取0.4 Ω/km

35kV 三芯电缆,取0.12 Ω/km

6~10kV 三芯电缆,取0.08 Ω/km

表4-2中S N 、S b 单位为MV A ,U N 、U b 单位为kV ,I N 、I b 单位为kA 。

4.4 短路电流的计算

电力系统的状态有三种:正常运行状态、不正常运行状态、短路故障。在电气设计和运行中,不仅要考虑系统正常运行状态,而且要考虑它发生故障时的情况,最严重的故障是电路乃至系统发生短路。电力系统正常运行时,其相与相之间,中性点接地系统的中性线与相线之间,都是通过符合或阻抗连接的。

4.4.1短路计算的目的

计算短路电流的目的是为了正确选择和校验电气设备,避免在短路电流作用下损坏电气设备,如果短路电流太大,必须采用限流措施,以及进行继电保护装置的整定计算。

短路电流计算的规定:

(1)电力系统中所用电源都在额定负荷下运行。

(2)同步调相机都具有自动调整励磁装置(包括强行励磁)。

(3)短路电流为最大值的瞬间。

(4)所有电源的电动势相位角相同。

(5)正常工作时,三相系统对称运行。

因考虑短路电流值有影响的所有元件,但不考虑短路点的电弧电阻对异步电动机的作用,仅有确定短路电流的冲击值和最大全电流的有效值时才给予考虑。

最大运行方式:计算短路电流是所用的接线方式是可能发生最大短路电流的正常接线方式(及最大运行方式),而不能用仅在切换过程中的能并列的接线方式。

三相短路:一般按三相短路计算,若发电机出口的两相短路或中性点直接接地系统

220KV变电站设计毕业论文(学术参考)

引言 随着经济的腾飞,电力系统的发展和负荷的增长,电力网容量的增大,电压等级和综合自动化水平也不断提高,科学技术突飞猛进,新技术、新电力设备日新月异,该地原有变电所设备陈旧,占地较大,自动化程度不高,为满足该地区经济的持续发展和人民生活的需要,电网正在进行大规模的改造,对变电所的设计提出了更高、更新的要求。建设新的变电所,采用先进的设备,使其与世界先进变电所接轨,这对提高电力网的供电可靠性,降低线路损耗,改善电能质量,增加电力企业的经济效益有很大的现实意义。 1、绪论 由于经济社会和现代科学技术的发展,电力网容量的增大,电压等级的提高,综合自动化水平的需求,使变电所设计问题变得越来越复杂。除了常规变电所之外,还出现了微机变电所、综合自动化变电所和无人值班变电所等。目前,随着我国城乡电网建设与改革工作的开展,对变电所设计也提出了更高、更新的要求。 1.1 我国变电所发展现状 变电技术的发展与电网的发展和设备的制造水平密切相关。近年来,为了满足经济快速增长对电力的需求,我国电力工业也在高速发展,电网规模不断扩大。目前我国建成的500kV变电所有近200座,220kV变电所有几千座;500kV电网已成为主要的输电网络,大经济区之间实现了联网,最终将实现全国联网。电气设备的制造水平也在不断提高,产品的性能和质量都有了较大的改进。除空气绝缘的高压电气设备外,GIS、组合化、智能化、数字化的高压配电装置也有了新的发展;计算机监控微机保护已经在电力系统中全面推广采用;代表现代输变电技术最高水平的750kV直流输电,500kV交流可控串联补偿也已经投入商业运行。我国电网供电的可靠性近年来也有了较大的提高,在发达国家连续发生严重的电网事故的同时,我国电网的运行比较稳定,保证了经济的高速发展。 1.2 变电所未来发展需要解决的问题

110kV变电站设计开题报告

110kv变电站110kv线路保护及主系统设计 1课题来源 本课题为某110kv中心变电站110kv线路保护记主系统设计课题。该变电站是最末一个梯级电站,装机容量600万千瓦,年发电量301亿千瓦时,用地总面积为8070.1374公顷。向家坝水电站110kV中心变电站为向家坝水电站提供施工供电电源和电站建成以后作为厂用电备用电源的一座变电站。设计容量为3 50MVA,电压等级为110/35/10kV, 110kV进出线有5条,中压35kV侧有10 回出线,低压10kV侧有20 回出线. 2 设计的目的和意义 110kV变电所是电力配送的重要环节,也是电网建设的关键环节。变电所设计质量的好坏,直接关系到电力系统的安全、稳定、灵活和经济运行。它是联系发电厂和用户的中间环节,起着变换和分配电能的作用。电气主接线是发电厂变电所主要环节,电气主接线连接直接影响运行的可靠性、灵活性。它的拟定直接关系着全厂电气设备的选择、配电装置的布置、继电保护、自动装置和控制方式的确定。 随着变电所综合自动化技术的不断发展与进步,变电站综合自动化系统取代或更新传统的变电所二次系统,继而实现“无人值班”变电所已成为电力系统新的发展方向和趋势。 3 国内外的现状和发展趋势 目前,我国小城市和西部地区经济的不断发展对电能资源的要求也越来越高,西部主要是高原地带,在高海拔的条件下,农村现有的变电技术远达不到经济的快速发展,这也在一定程度上影响了西部地区和中小城市变电技术的推广和应用技术的深化。因此,一方面需要创造条件有针对性地提高对小城市以及农村的变电站的建设,加强专业知识的培训来提高变电技术;另一方面,可以通过媒介积极开展技术交流,通过实践去体验、探索。 当今世界各方面因素正冲击着全球电力工业,在国外变电所技术有十分剧烈的竞争,而世界范围内的变电所都采用了新技术; 其次,不同的环境要求给所有的电力供应商增加了额外的责任,使电力自动化设备尤其是高压大功率变电站的市场开发空间大大拓展。另外高压变电所的最终用户对变电站的自动控制、节能、

变电所设计毕业论文

前言 在这次设计的选题上我是根据自己现在所实习的岗位来确定的,题目是《110KV降压变电站的部分设计》,而且我认为这次选题也是很好的结合了我在学校所学的工厂供电这门课程,让实践和理论知识相结合。 学习了工厂供电,为了更好的掌握这门功课,切实保证工厂生产的正常工作需要,我们进行了这次设计.要完成这次设计就必须了解工厂供电的基本知识.包括供电系统的一般原则,内容和程序.须要进行负荷计算,无功补偿以及继电保护。 首先介绍工厂供电设计的基本知识,包括供电设计的内容和程序,供电设计依据的主要技术基础,供电设计常用的电气图形符号和文字符号.接着依次讲述负荷计算和无功补偿,变配电所主接线方案的设计,短路计算及一次设备选择,继电保护及二次回路的选择,变配电所的布置与结构设计,供配电线路的设计计算,防雷保护和接地装置的设计。本次设计最重要的设计原则和方法,我们认为,就是在设计中一定要遵循国家的最新标准和设计规范.因此设计中着力介绍与工厂供电设计有关的最新标准和设计规范的规定和要求.限于我们的水平,加之时间非常的紧促,因此设计书中可能有错漏和不妥之处,是很难避免的,请老师批评指正。 毕业设计(论文)任务书 题目110kV降压变电站电气一次部分设计 一、毕业设计(论文)内容 本所位于某市区。向市区工业、生活等用户供电,属新建变电所。 电压等级: 110kV:近期2回,远景发展2回; 10kV:近期12回,远景发展2回。 电力系统接线简图、负荷资料及所址条件见附件。 二、毕业设计(论文)应达到的主要指标 1、变电所总体分析; 2、负荷分析计算与主变压器选择; 3、电气主接线设计; 4、短路电流计算及电气设备选择; 5、配电装置及电气总平面布置设计。 三、设计(论文)成品要求 1.毕业设计说明书(论文)1份; 2.图纸:1套(电气主接线)。

(完整版)110KV变电站及其配电系统设计_毕业设计

河南机电职业学院毕业论文(实习报告) 题目:110KV变电站及其配电系统设计 所属系部:电子工程系 专业班级:输变电工程12-1 学生姓名:刘康 指导教师:梁家裴 2015年6月6日

毕业论文(实习报告)任务书

指导教师签字:教研室主任签字: 年月日 毕业论文(实习报告)评审表

摘要

本文主要进行110KV变电站设计。首先根据任务书上所给系统及线路和所有负荷的参数,通过对所建变电站及出线的考虑和对负荷资料分析,满足安全性、经济性及可靠性的要求确定了110KV、35KV、10KV侧主接线的形式,然后又通过负荷计算及供电范围确定了主变压器台数、容量、及型号,从而得出各元件的参数,进行等值网络化简,然后选择短路点进行短路计算,根据短路电流计算结果及最大持续工作电流,选择并校验电气设备,包括母线、断路器、隔离开关、电压互感器、电流互感器等,并确定配电装置。根据负荷及短路计算为线路、变压器、母线配置继电保护并进行整定计算。本文同时对防雷接地及补偿装置进行了简单的分析,最后进行了电气主接线图及110KV配电装置间隔断面图的绘制 关键词:变电站设计,变压器,电气主接线,设备选择

目录 摘要 ..................................................................................................................... I I 1 变电站的介绍. (1) 1.1 变电站的作用 (1) 1.2 我国变电站及其设计的发展趋势 (2) 1.3 变电站设计的主要原则和分类 (4) 2 电气主接线设计 (4) 2.1 电气主接线设计概述 (5) 2.2 电气主接线的基本形式 (7) 2.3 电气主接线选择 (7) 3 变电站主变压器选择 (10) 3.1 主变压器的选择 (10) 3.2 主变压器选择结果 (11) 4 短路电流计算 (13) 4.1 短路的危害 (13) 4.2 短路电流计算的目的 (13) 4.3 短路电流计算方法 (13) 5 继电保护的配置 (14) 5.1 继电保护的基本知识 (14) 5.2 110kv线路的继电保护配置 (14) 5.3 变压器的继电保护 (14) 5.4 母线保护 (15) 5.5 备自投和自动重合闸的设置 (16)

110KV变电站毕业设计论文

110KV变电站电气部分设计 摘要 本说明书以110kV地区变电站设计为例,论述了电力系统工程中变电站部分电气设计(一次部分)的全过程。通过对变电站的主接线设计,站用电接线设计,短路电流计算,电气设备动、热稳定校验,主要电气设备型号及参数的确定,运行方式分析,防雷及过电压保护装置的设计,电气总平面及配电装置断面设计和无功补偿方案设计,较为详细地完成了电力系统中变电站设计。 限于毕业设计的具体要求和设计时间的限制,本毕业设计只对变电站电气一次部分做了较为详细的理论设计,而对其电气二次部分并没有涉及,这有待于在今后的学习和工作中进行研究。 关键词:变电站短路电流动稳定热稳定

ABSTRACT The statement about the 110kv transformer area substation design, discussed some electrical transformer substation design (one part) in power systems engineering of the entire process. Through the main transformer stations wiring design, stations wiring design stations, short circuit current calculations, check electrical equipment moving and thermal stability, set the main electrical equipment models and the parameters, the operating mode, design over-voltage protection and mine devices , design general electric graphic and distribution devices flood, and without power compensation. Completed substation design in power system,lastly. Limited to the specific design requirements and design time of constraints, the design only is a part of the electrical transformer stations, and its second part did not involve, which research it in future study and work. KEY WORDS: Substation, Short circuit currents , Moving stability,Thermal stability

ZY市郊110KV变电站设计 毕业设计(论文)

绪论 毕业设计是专业学习的一个重要组成部分,做毕业设计的目的是通过设计实践,综合所学知识,贯彻学习我国电力工业有关的方针政策,培养理论联系实际,独立分析解决问题的能力。 在本次设计中,首先温习了相关内容和有关学习资料,熟悉了设计中各个项目的要求和方法步骤,然后再进入实际设计阶段,力争做到有根据,有过程,有论证,简洁明快,条理清晰。. 电力系统是由发电机,变压器,输电线路,用电设备(负荷)组成的网络,它包括通过电的或机械的方式连接在网络中的所有设备。电力系统中的这些互联元件可以分为两类,一类是电力元件,它们对电能进行生产(发电机),变换(变压器,整流器,逆变器),输送和分配(电力传输线,配电网),消费(负荷);另一类是控制元件,它们改变系统的运行状态,如同步发电机的励磁调节器,调速器以及继电器等。 供电的中断将使生产停顿,生活混乱,甚至危及人身和设备安全,形成十分严重的后果。停电给国民经济造成的损失远远超过电力系统本身的损失。因此,电力系统运行首先要满足可靠,持续供电的要求。 我国目前电力工业的发展方针是:1.在发展能源工业的基本方针指导下发展电力工业。2.电力工业发展速度必须与国民经济发展速度相适应。3.发挥水电优势,加快水电建设。4.建设大型矿口电厂,搞好煤,电,运平衡。5.在煤,水能源缺乏地区,有重点有步骤地建设核电厂。6.政企分开,省为实体,联合电网,统一调度,集资办电。7.因地制宜,多能互补,综合利用,讲求利益。8.节约能源,降低消耗9.重视环境保护,积极防止对环境的污染。 变电所是联系发电厂和用户的中间环节,起着变换和分配电能的作用。变电所根据它在系统中的地位,可分为下列几类: 1.枢纽变电所位于电力系统的枢纽点,连接电力系统高压和中压的几个部分,汇集多个电源,电压为330~500kV的变电所,称为枢纽变电所。全所停电后,将引起系统解列,甚至出现瘫痪。 2.中间变电所高压侧以交换潮流为主,起系统交换功率的作用,或使长距离输电线路分段,一般汇集2~3个电源,电压为220~330kV,同时又降压供当地用电,这样的变电所起中间环节的作用,所以叫中间变电所。全所停电后,将引起区域电网解列。 3.地区变电所高压侧一般为110~220kV,向地区用户供电为主的变电所,这是一个地区或城市的主要变电所。全所停电后,仅使该地区中断供电。 4.终端变电所在输电线路的终端,接近负荷点,高压侧电压为110kV,经降压后直接向用户供电的变电所,即为终端变电所。全所停电后,只是用户受到损失。 在电力系统中,除应采取各项积极措施或减少发生故障的可能性以外,故障一旦发生,必须迅速而有选择性地切除故障元件,这是保证电力系统安全运行的最有效方法之一。切除故障的时间常常要求小到十分之几甚至百分之几秒,实践证明只有装设在每个电气元件上的保护装置才有可能满足这个要求。这种保护装置直到目前为止,大多是由单个继电器或继电器与其附属设备的组合构成的,故称为继电保护装置。在电子式静态保护装置和数字式保护装置出现以后,虽然继

110KV降压变电所设计_毕业设计论文

《发电厂电气部分》结业论文 110KV降压变电所设计 课程名称:发电厂电气部分 任课教师:姜新通 所在学院:信息技术学院 专业:电气工程及其自动化 中国·大庆 2012 年 5 月 毕业设计(论文)原创性声明和使用授权说明

原创性声明 本人郑重承诺:所呈交的毕业设计(论文),是我个人在指导教师的指导下进行的研究工作及取得的成果。尽我所知,除文中特别加以标注和致谢的地方外,不包含其他人或组织已经发表或公布过的研究成果,也不包含我为获得及其它教育机构的学位或学历而使用过的材料。对本研究提供过帮助和做出过贡献的个人或集体,均已在文中作了明确的说明并表示了谢意。 作者签名:日期: 指导教师签名:日期: 使用授权说明 本人完全了解大学关于收集、保存、使用毕业设计(论文)的规定,即:按照学校要求提交毕业设计(论文)的印刷本和电子版本;学校有权保存毕业设计(论文)的印刷本和电子版,并提供目录检索与阅览服务;学校可以采用影印、缩印、数字化或其它复制手段保存论文;在不以赢利为目的前提下,学校可以公布论文的部分或全部内容。 作者签名:日期:

学位论文原创性声明 本人郑重声明:所呈交的论文是本人在导师的指导下独立进行研究所取得的研究成果。除了文中特别加以标注引用的内容外,本论文不包含任何其他个人或集体已经发表或撰写的成果作品。对本文的研究做出重要贡献的个人和集体,均已在文中以明确方式标明。本人完全意识到本声明的法律后果由本人承担。 作者签名:日期:年月日 学位论文版权使用授权书 本学位论文作者完全了解学校有关保留、使用学位论文的规定,同意学校保留并向国家有关部门或机构送交论文的复印件和电子版,允许论文被查阅和借阅。本人授权大学可以将本学位论文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本学位论文。 涉密论文按学校规定处理。 作者签名:日期:年月日 导师签名:日期:年月日

110kV变电所毕业设计说明书

目录 第一章原始资料分析 (2) 第二章变电所接入系统设计 (3) 第三章变电所地方供电系统设计 (4) 第四章主变压器的选择 (6) 第五章所用变压器的选择 (14) 第六章主接线的设计 (16) 第七章变电所电器设备的选择 (19) 第八节继电保护的配置 (24) 参考资料 (27)

第一章原始资料分析 一、原始资料 1、待建110KV降压变电所从相距30km的110KV东郊变电站受电。 2、待建110KV降压变电所年负荷增长率为5%,变电站总负荷考虑五年发展规划。 3、地区气温: ?1?年最高气温35℃,年最低气温–15℃。 ?2?年平均气温15℃。 4、待建110KV降压变电所各电压级负荷数据如下表: 二、对原始资料的分析计算 为满足电力系统对无功的需要,需要在用户侧装设电容器,进行无功补偿,使用户的功率因数提高,35kV线路用户功率因数提高到0.9为宜,10kV线路用户功率因数应不低于0.9。 根据原始资料中的最大有功及调整后的功率因数,算出最大无功,可得出以下数据:

第二章变电所接入系统设计 一、确定电压等级 输电线路电压等级的确定应符合国家规定的标准电压等级。选择电压等级时,应根据输送容量和输电距离,以及接入电网的额定电压的情况来确定,输送容量应该考虑变电所总负荷和五年发展规划。因此待建110KV变电所的最高电压等级应为110kV。 二、确定回路数 该110KV变电所建成后,所供用户中存在Ⅰ、Ⅱ类重要负荷,因此110KV变电所应采用双回110KV线路接入系统。 三、确定110KV线路导线的规格、型号 由于该待建110KV变电所距离受电110KV东郊变电站30KM,处于平原河网地区,因此应采用架空线路,导线选择LGJ型。 四、110KV线路导线截面选择 导线截面积选择的一般方法是:先按经济电流密度初选导线标称截面积,然

10KV变电站的设计毕业论文

10KV变电站的设计毕业论文 目录 第一章绪论..................................................... - 1 - 1.1 变电站发展的历史与现状.................................. - 1 - 1.1.1 概况............................................... - 1 - 1.1.2 变电站综合自动化系统的设计原则..................... - 1 - 第二章变电站的负荷计算和无功率补偿计算......................... - 3 - 2.1 负荷计算................................................ - 3 - 2.3变电所主变压器的选择..................................... - 5 - 2.4变电所安装位置........................................... - 6 - 第三章变电站主接线设计......................................... - 7 - 3.1 电气主接线的基本要求.................................... - 7 - 3.2 常用的主接线............................................ - 7 - 3.3工厂变电所主要接线方案选择............................... - 9 - 第四章短路电流计算............................................ - 11 - 4.1短路电流计算的目的...................................... - 11 - 第五章电气设备的选择及校验.................................... - 15 - 5.2变电所一次一次设备的选择校验............................ - 16 - 5.2.1高压侧电气设备的选择校验.......................... - 16 - 5.2.2低压侧电气设备的选择校验.......................... - 19 - 5.3变电所进出线的选择及校验................................ - 20 - 5.3.1导线选择的原则.................................... - 21 - 5.3.2变电所导线的选择.................................. - 21 - 第六章变电所继电保护.......................................... - 24 - 6.1电力变压器的故障形式.................................... - 24 -

10kv变电站毕业设计

毕业设计(论文)任务书 一、题目:10kv变电所设计 指导思想和目的: 1、灵活运用本专业所学的基础和专业知识。 2、培养学生的专业技术知识和技能,能运用所学理论知识和技能解决生产第一线的运行、维护、检修及技术管理等实际工作,具有分析解决一般技术和业务问题的能力。 3、对学生进行一次高级人才基本技能的综合训练,培养学生分析和解决本专业技术实际问题的能力,包括技术经济政策的理解能力;查阅和综合分析各种文献资料、掌握使用工程技术规范和手册、图表等技术资料的能力;计算机应用能力;绘图和设计说明书(论文)的撰写等方面的能力。 4、培养学生树立严肃认真的工作作风,实事求是、严谨论证的科学态度,团结勤奋、协同作战的优良作风和应有的职业道德。 二.设计任务或主要技术指标: 1.设计任务 要求根据用电负荷实际情况,并适当考虑发展。按照安全可靠、技术先进、经济合理的要求,确定变电所的位置与形式,确定变电所主变压器的参数、容量与类型。选择变电所主接线方案及高低压设备和进出线,确定二次回路方案,选择整定继电保护装置、确定防雷和接地装置,最后按要求写出设计说明书,绘制设计图纸。 二、设计进度与要求: 第1周:收集10kv降压变电所资料。 第2周:了解掌握10kv降压变电站的基本组成。 第3周:根据设计背景计算变电所负荷。 第4周:短路电流计算。 第5周:电气主接线选择与校验。 第6周:继电保护预防雷保护的设计。 弟7周:制作10kv降压变电站设计报告。 弟8周:答辩 三、主要参考书及参考资料: [1]刘介才编著.《工厂供电》,第4版,机械工业出版社,2005 [2]雷振山编著.《中小型变电所实用设计手册》,第1版,中国水利水电出版社,2000。 [3]雷振山编著.《实用供配电技术手册》,第1版,中国水利水电出版社,2002。 [4]王子午编著.《常用供配电设备选型手册》,第一版,煤炭工业出版社,1998。 [5]徐泽植编著.《10kV及以下供配电设计与安装》,第一版,煤炭工业出版社,2002。 教研室主任(签名):系(部)主任(签名):2012年2月21日

变电站的发展与设计毕业论文

变电站的发展与设计毕业论文 第一章原始资料分析 一、原始资料 1、待建***变电所年负荷增长率为5%,总负荷考虑五年发展规划。 2、待建***变电所受电方案(1)从距离30km的110kV东郊变电站受电,方案 (2)从距离70km的110kV灌南变受电。 3、其他资料: (1)、地形地势平坦,土壤电阻率为1.5х104欧?厘米,所址高于百年一遇最高洪水位; (2)交通:仅靠国家二级公路,进所公路为0.4km。 (3)水源:供水方便,水源充足; (4)气象资料:地区最高气温38°C,最热月平均气温28°C,最热月地下0.8m 处平均气温22°C,年主导风力为东风,年雷暴雨日数为20天。 4、待建城北变电所各电压等级负荷参数如下表:

二、对原始资料进行分析计算 为满足电力系统对无功的要求,需在用户侧安装合理的电容器,进行无功补偿,提高用户功率因数,减小主变压器容量,35kV及10kV线路用户功率因数均提高到0.9为宜。 按原始资料表中的有功及计划补偿后的功率因数,计算出最大无功,得出以下

三、网络系统图

第二章 ***变电所接入系统设计 一、电压等级确定 输电线路电压等级的确定应符合国家规定的标准。选择电压等级时,应根据输送的容量和距离,以及接入电网的额定电压来确定,输送容量按五年发展规划。所以待建城北变电所的受电电压等级为110kV 。 二、确定回路数 ***变电所所供负荷为I 、 II 类重要负荷,因此***变电站应采用双回110kV 线路接入系统。 三、110kV 线路导线规格、型号确定 因待建***变电站距离110kV 东郊变30km,地处平原,采用架空线路,导线选择LGJ 型。 四、导线截面选择 导线截面选择的方法一般是:按经济电流密度初选导线标称截面积,后进行电压损失校验 1、待建***变电站总负荷计算 042 .4593)233.8823.0624.11265.7718.8(1719241518~353535j j jQ P S +=+++++++++=+=737 .51825.106%)51)(042.4593(9.0%)51)((%)51(~5535355j jQ P S +=++?=++=+

(完整版)110kv变电站一次系统设计毕业设计

以下文档格式全部为word格式,下载后您可以任意修改编 辑。 沧州职业技术学院 毕业设计 《110kv变电站一次系统设计》

目录 引言................................................................................................................................... - 1第1章概述..................................................................................................................... - 2第2章负荷计算及变压器选择..................................................................................... - 4 2.1负荷计算................................................................................................................. -4 2.1.1 计算负荷的目的.............................................................................................. - 4 2.1.2 负荷分析.......................................................................................................... - 4 2.2主变压器的选择..................................................................................................... -5 2.2.1 主变压器台数和容量的确定.......................................................................... - 5 2.2.2 变压器型号的选择.......................................................................................... - 5 2.3本变电站站用变压器的选择................................................................................. -6 2.4小结......................................................................................................................... -7第3章无功补偿装置的选择......................................................................................... - 8 3.1补偿装置的意义..................................................................................................... -8 3.2无功补偿装置类型的选择..................................................................................... -8 3.2.1 无功补偿装置的类型...................................................................................... - 8 3.2.2 常用的三种补偿装置的比较及选择.............................................................. - 8

110KV变电所毕业设计毕业设计

“发电厂及电力系统”专业大学毕业设计任务书 设计题目:区域电力网及降压变电所设计 毕业设计任务书 一、区域电网的设计内容 1、根据负荷资料,待设计变电所的地理位置。据已有电厂的供电情况。作出功率平衡。 2、通过技术经济综合比较,确定电网供电电压、电网接线方式及导线截面。 3、进行电网功率分布及电压计算,评定调压要求,选定调压方案。 4、评定电网接线方案。 二、在区域电网设计的基础上,设计110 kV;kV A降压变电所的电气部分。具体要求如下: 1、对B 变电所在系统中的地位作用及所供用户的分析。 2、选择变电所主变压器的台数、容量、型式。 3、分析确定高低压主接线方式及配电装置型式。 4、分析确定所用电接线方式。 5、进行继电保护及互感器的配置。 6、进行选择设备所必须的短路电流计算。 7、选择变电所高低压侧回路的断路器、隔离开关。 8、选择10kV 硬母线。 9、进行防雷及保护接地的规划。 三、设计文件及图纸要求: 1、设计说明书一份; 2、计算书; 3、图纸(2号)。 (1)区域电网接线图; (2)变电所一次接线图;

原 始 资 料 一、区域电网设计的有关原始资料 1、发电厂、变电所及新选定变电所地理位置(见附图一):D 图; 2、原有发电厂、变电所主接线图及设备规范(见附图二); 3、新变电所有关资料; 变电所 编 号 最大负荷 MW 功率因数 COSφ 二次侧 电压kV 调 压 要 求 负荷曲线 性 质 重要负荷 % A 20 0.92 10 顺 A 60 B 23 0.9 10 逆 B 51 C 27 0.9 10 逆 B 60 D 20 0.92 10 常 A 70 4、典型日负荷曲线 典型日负荷曲线(A ) % 100 90 80 70 60 50 40 30 20 10 0 2 4 6 8 10 12 14 16 18 20 22 24

论文--110kv变电站设计(上海电力学院)

本科毕业论文 发电厂设计 上海电力学院 施春迎 第一章 主变及所用变的选择 第一节 主变压器的选择 一、负荷统计分析 1、 35kV 侧 Q 1max=var 44.61971000085.0/10000cos /222max 1212max 12 K P P =-=-? Q 2max=var 44.61971000085.0/10000cos /222max 2222max 22K P P =-=-? Q 3max =var 47.3718600085.0/6000cos /222max 3232max 32K P P =-=-? Q 4max =var 4500600080.0/6000cos /222max 4242max 42 K P P =-=-? Q 5max = var 4500600080.0/6000cos /222max 5252max 52 K P P =-=-? ∑35 P =P 1max +P 2max +P 3max +P 4max +P 5max =10000+10000+6000+6000+6000=38000(KW) ∑35 Q =Q 1max +Q 2max +Q 3max +Q 4max +Q 5max =6197.44+6197.44+3718.47+4500+4500=25113.35(KVar ) S 35MAX =2max 352max 35Q P +=22 35.25113 80003+=45548.66(KVA ) 35?Cos = MAX S P 35max 35∑= 66 .4554838000 =0.83 考虑到负荷的同时率,35kV 侧最大负荷应为: S ’35MAX =S 35MAX ?35η=45548.66?0.85=38716.36(KVA)

10KV变电所毕业设计(论文)

10KV变电所毕业设计 1 变电所总体设计及供配电系统分析 1.1 变电所设计原则 进行变电所设计时须遵照变电所设计规范所规定的原则。 根据《35—10kV变电所设计规范》要求: 第1.0.3条变电所的设计应根据工程的5—10年发展规划进行,做到远近结合、以近为主,正确处理近期建设与远景发展的关系,适当考虑扩建的可能性。 第1.0.4条变电所的设计必须从全局出发、统筹兼顾,按照负荷性质、用电容量、工程特点和地区供电条件,结合国情合理地确定设计方案。 第1.0.5条变电所的设计,必须节约用地的原则。 1.2 变电所设计目的与任务 毕业设计是本专业教学计划中的重要环节。此次毕业设计的目的是通过变电所设计实践,综合运用所学知识,贯彻执行我国电力工业有关方针政策,理论联系实践,锻炼独立分析和解决电力工程设计问题的能力,为未来的实际工作奠定必要的基础。 1.3 PG新校区供电需求分析 PG新校区10KV变电所为位于PG新校的变电所,由系统S1、系统S2向PG 新校区供电,来供给该校教学、实验、施工及生活用电,PG新校区变电所的建立可保障新校区的正常用电,提高供电质量和供电可靠性。PG新校区变电所变电压等级为10/0.4KV,是以向终端用户供电为主的变电所,全所停电后将对该校中断供电。 1.4 变电所总体分析 1.4.1 建站必要性与建站规模 1 建站必要性 PG新校区10KV变电所为终端变电所,在系统中主要起变配电作用,全所停电将造成全校停电,它供给该校教学、实验、施工及生活用电。故为满足该校用电要求决定建设本变电站。 2 建站规模

PG新校区10KV变电所电压等级为10/0.4KV 线路回路数: 近期6回,远期2回; 近期最大负荷4627KW。 1.4.2 所址概况与所址条件 1 所址概况 PG新校区10KV变电所位于该校图书馆周围,西部电源和东部电源进线先通过10kV变电所高压侧开关站进行电能分配,然后馈出六回线分配给两个独立变电所和四个箱式变电站,独立变电所和箱式变电站经过变压后供给其所带负荷用电。 2 所址条件 依据《10kV及以下变电所设计规范》GB50053-94 第2.0.1条,变电站所址的选择,应根据下列要求经技术、经济比较确定: 一、接近负荷中心; 二、进出线方便; 三、接近电源侧; 四、设备运输方便; 五、不应设在有剧烈振动或高温的场所; 六、不宜设在多尘或有腐蚀性气体的场所,当无法远离时,不应设在污染源盛行风向的下风侧; 七、不应设在厕所、浴室或其他经常积水场所的正下方,且不宜与上述场所相贴邻; 八、不应设在有爆炸危险环境的正上方或正下方,且不宜设在有火灾危险环境的正上方或正下方,当与有爆炸或火灾危险环境的建筑物毗连时,应符合现行国家标准《爆炸和火灾危险环境电力装置设计规范》的规定; 九、不应设在地势低洼和可能积水的场所。 PG新校区10KV变电所建在该校内部,为节约用地、接近负荷中心、进出线方便,故采用建立两个独立变电所和四个箱式变电站的方针。 1.5 负荷分析 1.5.1 负荷的分类与重要性 1一级负荷: 对供电要求最高,要求不断电或可极短时间断电。必须有两个独立电源供电,且当任何一个电源断开后,能保证对全部一级负荷不间断供电; 2 二级负荷: 对供电要求较高,要求基本不断电或可短时间断电。一般要有

变电站设计毕业设计(论文)

毕业论文声明 本人郑重声明: 1.此毕业论文是本人在指导教师指导下独立进行研究取得的成果。除了特别加以标注地方外,本文不包含他人或其它机构已经发表或撰写过的研究成果。对本文研究做出重要贡献的个人与集体均已在文中作了明确标明。本人完全意识到本声明的法律结果由本人承担。 2.本人完全了解学校、学院有关保留、使用学位论文的规定,同意学校与学院保留并向国家有关部门或机构送交此论文的复印件和电子版,允许此文被查阅和借阅。本人授权大学学院可以将此文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本文。 3.若在大学学院毕业论文审查小组复审中,发现本文有抄袭,一切后果均由本人承担,与毕业论文指导老师无关。 4.本人所呈交的毕业论文,是在指导老师的指导下独立进行研究所取得的成果。论文中凡引用他人已经发布或未发表的成果、数据、观点等,均已明确注明出处。论文中已经注明引用的内容外,不包含任何其他个人或集体已经发表或撰写过的研究成果。对本文的研究成果做出重要贡献的个人和集体,均已在论文中已明确的方式标明。 学位论文作者(签名): 年月

关于毕业论文使用授权的声明 本人在指导老师的指导下所完成的论文及相关的资料(包括图纸、实验记录、原始数据、实物照片、图片、录音带、设计手稿等),知识产权归属华北电力大学。本人完全了解大学有关保存,使用毕业论文的规定。同意学校保存或向国家有关部门或机构送交论文的纸质版或电子版,允许论文被查阅或借阅。本人授权大学可以将本毕业论文的全部或部分内容编入有关数据库进行检索,可以采用任何复制手段保存或编汇本毕业论文。如果发表相关成果,一定征得指导教师同意,且第一署名单位为大学。本人毕业后使用毕业论文或与该论文直接相关的学术论文或成果时,第一署名单位仍然为大学。本人完全了解大学关于收集、保存、使用学位论文的规定,同意如下各项内容:按照学校要求提交学位论文的印刷本和电子版本;学校有权保存学位论文的印刷本和电子版,并采用影印、缩印、扫描、数字化或其它手段保存或汇编本学位论文;学校有权提供目录检索以及提供本学位论文全文或者部分的阅览服务;学校有权按有关规定向国家有关部门或者机构送交论文的复印件和电子版,允许论文被查阅和借阅。本人授权大学可以将本学位论文的全部或部分内容编入学校有关数据 库和收录到《中国学位论文全文数据库》进行信息服务。在不以赢利为目的的前提下,学校可以适当复制论文的部分或全部内容用于学术活动。 论文作者签名:日期: 指导教师签名:日期:

110kv变电站设计-毕业论文

毕业设计报告 课题名称 110kV变电站一次部分设计学生姓名 学号 专业 班级 指导老师 ?目录

摘要 (3) 概述 (4) 第一章电气主接线 (6) 1.1110kv电气主接线 (7) 1.235kv电气主接线 (8) 1.310kv电气主接线 (10) 1.4站用变接线 (12) 第二章负荷计算及变压器选择 (13) 2.1负荷计算…………………………………………………(13) 2.2主变台数、容量和型式的确定 (14) 2. 3 站用变台数、容量和型式的确定 (16) 第三章最大持续工作电流及短路电流的计算…………………(17) 3.1 各回路最大持续工作电流 (17) 3.2 短路电流计算点的确定和短路电流计算结果…………(1

8) 第四章主要电气设备选择 (19) 4.1高压断路器的选择 (21) 4.2隔离开关的选择 (22) 4.3 母线的选择 (23) 4.4 绝缘子和穿墙套管的选择…………………………………(24) 4.5 电流互感器的选择…………………………………………(24) 4.6电压互感器的选择…………………………………………(26) 4.7各主要电气设备选择结果一览表 (29) 附录I 设计计算书 (30) 附录II 电气主接线图 (37) 10kv配电装置配电图 (39) 致谢 (40) 参考文献 (41)

摘要 本文首先根据任务书上所给系统与线路及所有负荷的参数,分析负荷发展趋势。从负荷增长方面阐明了建站的必要性,然后通过对拟建变电站的概括以及出线方向来考虑,并通过对负荷资料的分析,安全,经济及可靠性方面考虑,确定了110kV,35kV,10kV以及站用电的主接线,然后又通过负荷计算及供电范围确定了主变压器台数,容量及型号,同时也确定了站用变压器的容量及型号,最后,根据最大持续工作电流及短路计算的计算结果,对高压熔断器,隔离开关,

电气工程及其自动化毕业论文

电气工程及其自动化毕业论文 本科生毕业设计(论文) 摘要 本设计的主要内容包括:10/0.4kV变电所主变压器选择;变电所电气主接线设计;短路电流计算;负荷计算;无功功率补偿;电气设备选择(母线、高压断路器、隔离开关、电流互感器、电压互感器、避雷器和补偿电容器);配电装置设计;继电保护规划设计;防雷保护设计等。 根据电气主线设计应满足可靠性、灵活性、经济性的要求,本变电所电气主接线的高压侧采用单母线接线,低压侧采用单母线分段的电气主接线形式;对低压侧负荷的统计计算采用需要系数法;为减少无功损耗,提高电能的利用率,本设计进行了无功功率补偿设计,使功率因数从0.69提高到0.9;短路电流的计算包括短路点的选择及其具体数值计算;而电气设备选择采用了按额定电流选择,按短路电流计算的结果进行校验的方法;继电保护设计主要是对变压器进行电流速断保护和过电流保护的设计计算;配电装置采用成套配电装置;本变电所采用避雷针防直击雷保护。 本设计十分注重运用我国电气设计的新技术和新的设备,实用性及强,考虑到是实际工程的应用,便以通俗易懂的语言进行阐述。 关键词:变电所设计;电气主接线;继电保护 I 本科生毕业设计(论文) Abstract

The design on the topic of "Liaoning Institute of Technology Teaching Building substation expansion preliminary design." The main design elements include : 10/0.4kV main transformer substation choice; Electrical Substation main wiring design; Short-circuit current calculation; Load Calculation; Reactive power compensation; Electrical Equipment (bus, HV circuit breakers, isolation switches, current transformer and voltage transformer, and compensation capacitor MOA); Distribution Equipment design; relay Planning and Design; Lightning protection design. According to the main line of electrical design should meet the reliability, flexibility, economy requirements, The substation main electrical wiring High Side single-bus wiring, low voltage side of the single-bus above the main electrical wiring form; the low-pressure side load calculated using the statistical needs coefficient; To reduce the reactive power loss, increased energy utilization, The design of reactive power compensation design, power factor from 0.69 to 0.9; short-circuit current calculations include short-circuit point for the selection and specific numerical calculation; and electrical equipment chosen by the choice of rated current, short-circuit current calculation by the results of the calibration methods; relay design of the main transformer Current Protection and over-current protection design; distribution installations complete set of power distribution equipment; The substation using direct lightning stroke prevention lightning protection.