Medium voltage products

GSec

Gas-insulated switching and

isolating apparatus

Index

3 1. Description

6 2. Selection and ordering

14 3. Specific product characteristics 20 4. Overall dimensions

2

3

6

4

7

5

8

2

9

1

1 Opening and closing push-buttons 2. Line operating lever seat 3. Earth operating lever seat

4. Voltage indicators (if applicable)

5. Top insulators

6. Enclosure (power part)

7. Housing of the operating mechanism 8. Bottom insulators 9 Mimic diagram

GSec is a three-position SF6 gas-insulated switch-disconnector designed for use in medium voltage switchgear for secondary distribution.

GSec is used in line ingoing/outgoing panels, in those with circuit-breakers or in a combination with fuses. Typical

applications are supplying lines, protecting transformers and use in ring networks.

Thanks to its size, GSec can be installed in panels 375 mm in width or wider.

The contacts of the three phases can be set to the following positions:

LINE – OPEN – EARTH.

The enclosure of the GSec switch-disconnector consists of two half-shells, the top part being made of resin and the bottom part in stainless steel.

GSec apparatus is “sealed for life” in accordance with standard IEC 60694, wich means that the gas tightness is guaranteed for more than 30 years.

GSec has a wide range of “plug&play” accessories that can be easily installed and replaced from the front part of the apparatus.

The GSec series has been designed and tested in compliance with Standards IEC 60694, IEC 62271-102, IEC 62271-105 and IEC 60265-1.

Line Open Earth

Electrical characteristics

Rated voltage kV1217.524

Power frequency withstand voltage (50/60 Hz, 1 min)

- Line to line and line to earth kV283850

- Between open contacts kV324560

Lightning impulse withstand voltage (BIL 1.2/50 μs)

- Line to line and line to earth kVp7595125

- Between open contacts kVp85110145

Rated frequency Hz50-6050-6050-60

Rated current (40 °C)A800 (1)800 (1)630

Rated short-time withstand current kA25 (2s) (2)20 (3s) (2)(3)16 (3s) - 20 (3s) (2)(3) Making capacity (peak current)kAp62.552.540-52.5 Breaking capacity

- Active load A800 (1)800 (1)630

- No-load transformers A161616

- No-load lines A252525

- No-load cables A505050

- Ring circuits A800 (1)800 (1)630

Mechanical and electrical performance

Electrical endurance of the line contact class E3 - up to 5 makings and 100 rated current interruptions

Electrical of the earth contact class E2 - up to 5 makings

Mechanical endurance of the line contact with operating

mechanism 1S - Single spring

class M2 – 5000 mechanical operations

Mechanical endurance of the line contact with operating

mechanism 2S - Double spring

class M1 – 1000 mechanical operations

Mechanical endurance of the earth contact class M0 – 1000 mechanical operations

(1) 630A for GSec/T2

(2) 16kA (3s) for GSec/T2

(3) For 21kA (3s) please contact ABB

Other characteristics

Distance between the phases mm230

SF6 absolute pressure kPa148

Internal volume I25

IP protection class IP2X

Operating temperature (4)

- Min°C-5

- Max°C+40 (5) Maximum installation altitude (6)m3000

(4) In accordance with standard IEC 62271

(5) Consult ABB for higher values

(6) Consider the Ka correction factor for the insulating components, in accordance

with standard IEC 62271-100.Standards used

Standard Title

IEC 60694High-voltage switchgear and controlgear

- Part 1: Common specifications.

IEC 62271-102

High-voltage switchgear and controlgear

- Part 102: Alternating current disconnectors and

earthing switches.

IEC 60265-1

High-voltage switchgear and controlgear

- Part 103: Switches for rated voltages above

1 kV up to and including 5

2 kV.

IEC 62271-105

High-voltage switchgear and controlgear

- Part 105: Alternating current switch-fuse

combinations.

4

Safety

– The stainless steel bottom part of GSec provides metallic segregation between the cable and busbar compartments, ensuring that the two compartments are earthed and therefore making conditions safer for the personnel.

– Thanks to GSec design, it can be used to create switchgear with PM (Metallic Partitions) classification for the segregation between the busbar and cable compartments.– Safety valve for exhausting accidental gas overpressure. It is installed in the rear part of the apparatus.

– Mechanical interlocks for the safety of the personnel.

– The door lock prevents the panel door from being opened when the GSec contacts are not in the earthed position. Vice versa, the lock prevents the switch-disconnector from setting to the open or line positions when the door is open.– The operating lever with “anti-reflex” function. Maintenance free

– The enclosure of GSec is guaranteed “sealed for life” for more than 30 years, in accordance with IEC 60694 standards

– Up to 5000 mechanical operations without maintenance for GSec with the 1S - Single spring operating mechanism

– Up to 1000 mechanical operations without maintenance for GSec with the 2S - Double spring operating mechanism Reliability

– The apparatus can house VPIS voltage indicators in accordance with standard IEC 61958, for voltage detection on the cable side

– Mechanical signalling of the state of the apparatus connected directly to the operating shaft (Annex A of standard IEC 62271-102)Ease of use

– Both the GSec operating mechanisms are equipped with springs so the operating speed is independent of the operator.

– The operating mechanism has two separate seats, one for line operation and one for earthing operation.

Customizing

– A full range of “plug & play” accessories that can be easily installed on the front part of the operating mechanism allows the apparatus to be adapted to suit many applications.

– GSec can be used for incoming/outgoing units, in combination with fuses, circuit-breakers with lateral operating mechanisms, current and voltage transformers. Compactness

– Thanks to the upper resin part it is possible to design small size apparatus and switchgear panel, while still ensuring a high level of insulation.

– The capacitive sockets for voltage indicator (VPIS) and the cable connections are already integrated in the apparatus bottom insulators. This allows to reduce the number of components of the the panel.

5

6

Fig. 1

Types

Rated voltage [kV]Rated current [A]Short-time withstand current [kA (s)]Type of operating mechanism GSec/T1 24.06.162463016 (3)1S - Single spring GSec/T1 24.06.202463020 (3)1S - Single spring GSec/T1 17.08.2017.580020 (3)1S - Single spring GSec/T1 12.08.25

12

800

25 (2)

1S - Single spring

Standard supply Optional accessories Switch-disconnector

Auxiliary contacts

1S - Single spring operating mechanism Motor for the operating mechanism Door interlock VPIS voltage indicators Operating lever Key lock for line seat

Key lock for earth seat

Coil for preventing lever insertion in earth seat Gas presence indicators

Coil for preventing lever insertion in line seat

a. GSec/T1

Three-position switch disconnector with 1S - Single spring operating mechanism.

Performs opening and closing operations at operating speeds independent of the operator.This type is generally used for creating incoming/outgoing units.

2. Selection and ordering

Types

7

Fig. 2

Types

Rated voltage [kV]Rated current [A]Short-time withstand current [kA (s)]Type of operating mechanism GSec/T2 24.06.16

24

630

16 (3)

2S - Double spring

Standard supply Optional accessories Switch-disconnector

Auxiliary contacts

2S - Double spring operating mechanism Motor for the operating mechanism Door interlock VPIS voltage indicators Operating lever

Key lock for line seat Key lock for earth seat

Coil for preventing lever insertion in earth seat Shunt opening release Shunt closing release Undervoltage release Gas presence indicators

b. GSec/T2

Three-position switch disconnector with 2S - Double spring stored energy operating mechanism. Performs opening and closing operations at operating speeds independent of the operator.This type is generally used for creating incoming/outgoing units.

8

Fig. 3

Types

Rated voltage [kV]Rated current [A]Short-time withstand current [kA (s)]Type of operating mechanism Making capacity of separate earthing switch [kAp]GSec/T2F 24.06.162463016 (3)2S - Double spring 5GSec/T2F 24.06.202463020 (3)2S - Double spring 5GSec/T2F 17.08.2017.580020 (3)2S - Double spring 5GSec/T2F 12.08.2512

800

25 (2)

2S - Double spring

5

Standard supply Optional accessories Switch-disconnector

Auxiliary contacts

2S - Double spring operating mechanism Motor for the operating mechanism Door interlock VPIS voltage indicator

Operating lever Fuses blown signalling contact.Fuses blown indicator

Key lock for line seat Tripping system in case of blown fuses

Key lock for earth seat

Separate earthing switch 5 kAp with relative transmission (*)Coil for preventing lever insertion in earth seat Fuse holder (*)

Shunt opening release Shunt closing release Undervoltage release Gas presence indicators

(*) Components supplied loose

c. GSec/T2F

Three-position switch disconnector with 2S - Double spring stored energy operating mechanism. Suitable for use in combination with fuses, e.g. for transformer protection units.

2. Selection and ordering

Types

9

Fig. 4

Types

Rated voltage [kV]Rated current [A]Short-time withstand current [kA (s)]Type of operating mechanism Making capacity of separate earthing switch [kAp]GSec/IB 24.06.162463016 (3)1S - Single spring 62,5GSec/IB 24.06.202463020 (3)1S - Single spring 62,5GSec/IB 17.08.2017.580020 (3)1S - Single spring 62,5GSec/IB 12.08.2512

800

25 (2)

1S - Single spring

62,5

Standard supply Optional accessories Switch-disconnector

Auxiliary contacts

1S - Single spring operating mechanism Motor for the operating mechanism Door interlock VPIS voltage indicator Operating lever

Key lock for line seat Separate earthing switch 62.5 kAp with relative transmission (*)

Key lock for earth seat

Coil for preventing lever insertion in earth seat Gas presence indicators

Coil for preventing lever insertion in line seat

(*) Components supplied loose

d. GSec/IB

Three-position switch disconnector with 1S - Single spring operating mechanism. Suitable for use in panels with circuit-breaker for incoming/outgoing use.

10

2. Selection and ordering

Accessories

a. Key locks

Allow each of the operation seat of the apparatus (line and earth) to be locked in the open or closed positions. Up to a maximum two keys for the line and two keys for the earth can be used.Three types of keys are available. standard, Ronis and Profalux.The line switching lock of switch-disconnectors with the 2S - Double spring operating mechanism cannot be locked in the closed position.

Key locks

Gsec/T1 Gsec/IB Gsec/T2Gsec/T2F 1S operating mechanism - Single spring

2S operating mechanism - Double spring

Line

2 free keys

- 1 open and 1 closed x 1 key free - open x x 1 key free - closed

x Earth

2 free keys

- 1 open and 1 closed x x 1 key free - open x x 1 key free - closed

x

x

c. Auxiliary contacts

Allow the position of the apparatus to be signalled to a remote location. 4 auxiliary contacts are available for the line and 4 for the earth. Each contact can be used as a normally closed (NC) or normally open (NO) circuit.

Maximum rating AC DC Voltage [V]250250Current [A]

16

0,3

d. VPIS voltage signalling devices

The switch-disconnector can be equipped with VPIS (Voltage Presence Indicating System) voltage signalling devices in accordance with standard IEC 61958. These indicators

detect the presence of voltage in the cables connected to the switch-disconnector itself. Phase concordance can also be performed with these devices.

b. Pre-engineering for padlocks

Allows padlocks to be housed so as to lock the apparatus in the open, line or earthed positions. Up to three padlocks can be used per apparatus.

The maximum diameter of the padlock latch is 6 mm.

It is part of the standard equipment for all GSec apparatus. The padlocks are not supplied.

e. Motor for the GSec/T1 and GSec/IB (-MAD)

operating mechanism

The motor automatically loads the spring of the 1S – Single spring operating mechanism for line operations.

This allows the switch-disconnector to be operated by remote control.

The switch-disconnector's closing (Tclose) and opening (Topen) times are less than 5 seconds (see diagram in Fig. 5).

a) single spring

DC DC / AC (50Hz)

Power supply voltage [V]2448110220 Power demand [W / VA]90

If the motor functions in a faulty way, the switch-disconnector can always be operated in the manual mode with the operating lever.

f. Motor for the GSec/T2 and GSec/T2F (-MAD)

operating mechanism

The motor automatically loads the spring of the 2S – Single spring operating mechanism for line operations.

Thanks to this motor and the closing and opening releases, the switch-disconnector can be operated by remote control. When the motor is installed, the springs take less than 4 seconds to load, as indicated in the diagram of Fig. 6.

b) double spring

DC DC / AC (50Hz)

Power supply voltage [V]2448110220 Power demand [W / VA]260

The motor drive is available with the following modes:

– CCO (Charge - Close - Open) in three separate operations: the motor loads the spring operating mechanism. Closing and subsequent opening take place through two separate actions which can be operated by buttons or closing shunt releases

– CO (Charge and close - Open) in two separate operations: the motor loads the spring operating mechanism and the closing shunt release closes the switch-disconnector. Opening takes place through a separate action which can be operated by a button or opening shunt release

If the motor functions in a faulty way, the switch-disconnector can always be operated in the manual mode with the operating lever.g. Opening shunt release -MBO4

(for GSec/T2 and GSec/T2F)

This electromechanical device opens the line contact of

the apparatus after the electromagnet has been energized. The total opening time of the switch-disconnector contacts (Topen, see Fig. 6) is 300 ms.

Characteristics:

AC (50-60 Hz)DC

Power supply voltage LV [V]48, 6024, 48, 60

Power supply voltage HV [V]110-127, 220-250110-132, 220-250 Inrush power consumption200 VA200 W

h. Closing shunt release -MBC4

(for GSec/T2 and GSec/T2F)

This electromechanical device closes the line contact of the apparatus after the electromagnet has been energized.

The total closing time of the switch-disconnector contacts (Tclose, see Fig. 6) is 300 ms.

Characteristics:

AC (50-60 Hz)DC

Power supply voltage LV [V]48, 6024, 48, 60

Power supply voltage HV [V]110-127, 220-250110-132, 220-250 Inrush power consumption200 VA200 W

11

2. Selection and ordering

Accessories

i. Under-voltage release -MBU

(for GSec/T2 and GSec/T2F)

This release opens the line contact of the switch-disconnector when the auxiliary power supply voltage drops or is interrupted.

Characteristics:

AC (50 Hz)DC

Power supply voltage LV [V]48, 6024, 48, 60

Power supply voltage HV [V]110-132(*),

220-250(*)110-132, 220-250

Inrush power consumption150 VA150 W

Inrush time [ms]150150 Continuous power 3 VA 3 W

Tripping limits 35-70% of the rated voltage of

the auxiliary power supply

(*) also available for 60 Hz

j. Coil to prevent the operating lever insertion in the line seat -RLE5 (for GSec/T1 and GSec/IB) When the coil is not supplied, it prevents the lever from being fitted into the line seat.

This accessory is only available for the 1S - Single spring operating mechanism.

DC Power supply voltage [V]24, 30, 48, 60, 110, 220, 240 Rated power [W]250

Continuous power [W]5

Inrush time [ms]150k. Coil to prevent the operating lever insertion in the earth seat -RLE3

When the coil is not energized, it prevents the lever from being fitted into the earth seat.

This accessory is supplied as an alternative to the key lock for the earth switching lock.

DC Power supply voltage [V]24, 30, 48, 60, 110, 220, 240 Rated power [W]250

Continuous power [W]5

Inrush time [ms]150

l. Fuses blown signalling contact

When a fuse blows, a kinematic chain activates an indicator that can be seen on the front of the panel (part of the standard equipment for all GSec/T2F devices).

A signalling contact can also be requested so as to transmit information about blown fuses by remote control.

The contact can be normally closed (NC) or normally open (NO).

12

13

m. Pressure gauge

The pressure gauge displays the pressure of the gas and provides an analog indication of the value.

The information can be seen on the front of the panel and can also be transmitted by remote control via dedicated wiring and a terminal box.

n. Temperature compensated gas density gauge

The density gauge monitors the gas pressure and provides an alarm that signals when the pressure is low.

Signal Description

OK Correct operating pressure

LOW Indicates the minimum gas level for which operation of the switch-disconnector is guaranteed VERY LOW

The switch-disconnector cannot be operated

The state of the signals can also be transmitted by remote control via dedicated wiring and a terminal box.

a. Power part

The enclosure of the GSec switch-disconnector consists

of two half-shells, the top part being made of resin and the bottom part in stainless steel.

Smaller sized apparatus can be created thanks to the top part in resin while still guaranteeing a high insulation capacity.

The stainless steel part provides metallic segregation between the cable and busbar compartments, ensuring that the cable compartment is fully earthed and therefore making conditions safer for the personnel. GSec can be used to create panels in the PM (Metallic Partitions) class because it provides metallic segregation between the busbar and cable compartments of the panel.

The power section of the GSec is filled with SF6 at 148 kPa absolute pressure. The gas is used as an interruption and insulation medium. Gas tightness is guaranteed for 30 years, in accordance with the specifications established by standard IEC 60694. GSec apparatus is called “sealed for life” for this reason.The rear part of the switch-disconnector is equipped with a safety valve with predetermined rupture value that allows gas overpressure caused by an accidental fault to be relieved in safe conditions.

The GSec contacts can set to the following positions:

- LINE: The line contacts are closed

- OPEN: the apparatus ensures that there is insulation between the cable side and busbar side

- EARTH: the contacts on the cable side are earthed.

A mechanical signal visible from the front of the apparatus indicates the position of the contacts. In accordance with annex A of standard IEC 62271-102, this device is connected straight to the operating shaft.

The capacitive sockets for the voltage signalling devices (accessory available on request) are housed inside the three bottom insulators. Moreover, the cable connection can be created on the apparatus without the need for a cross-beam for the insulators. This cuts down on the number of components that need to be installed in the panel.

3. Specific product characteristics

14

15

b. Operating mechanism

The GSec switch-disconnector can be equipped with two types of operating mechanisms: – 1S - Single spring – 2S - Double spring.

Both operating mechanisms have separate lever seats for the line and earthing operations and both can be equipped with a motor for loading the springs. Even when a motor is installed for loading the springs, it is always possible to operate GSec in the manual mode in case of emergency.

Position of the line contact Spring load state

Ts1

Spring loading time

- manual operation: depends on the operator - motor-driven operating mechanism = 3-4 s.

Tc

Contact opening or closing time < 0.3 s.Tclose Total closing time < 5 s.

(motor driven operating mechanism)Topen

Total opening time < 5 s.

(motor driven operating mechanism)

Fig. 5 - Diagram of 1S - Single spring operating mechanism operation.

1S - Single spring operating mechanism

– It opens and closes the GSec line contacts. The energy required for the operation is obtained by compressing a spring with a lever, which closes (or opens) the device once dead center has been passed. The operating speed is independent of the operator.

– It opens and closes the earth contact at operating speeds independent of the operator. In the case of GSec/IB units, it also closes and opens the separate earthing switch at operating speeds independent of the operator. – Manual operation: with the operating lever

– Automatic or remote controlled operation: with motor

16

2S - Double spring operating mechanism

– It opens and closes the GSec line contact using the

energy stored in two springs: the springs of the operating mechanism are loaded by means of a lever, after which the switch-disconnector is operated by pressing the closing and opening push-buttons. The springs must be reloaded after a closing and opening cycle. The operating speed is independent of the operator.

– It opens and closes the earth contact at operating speeds independent of the operator. In the case of GSec/T2F

Position of the line contact Spring load state

Ts2

Spring loading time

- manual operation: depends on the operator - motor-driven operating mechanism = 3-4 s.

Tc

Contact opening or closing time < 0.3 s.Tclose Total closing time < 0.3 s.Topen

Total opening time < 0.3 s.

Fig. 6 - Diagram of 2S - Double spring operating mechanism operation.

units, it closes and opens the separate earthing switch at operating speeds independent of the operator

– Manual operation: using the operating lever and push-buttons

– Automatic or remote controlled operation: with a motor and opening and closing coils

– The contacts of the switch-disconnector also open even if only one fuse blows (GSec/T2F) or when the undervoltage coil trips

– The load state of the springs is signalled by an indicator on the front of the panel

3. Specific product characteristics

17

5

8

7

c. Front cover

1. Lever seat line operating

2. Lever seat earth operating 3 Mimic diagram

4. Operating mechanism push-buttons

5. Voltage signalling device

6. Springs loaded indicator

(only for the 2S - Double spring operating mechanism)7. Blown fuses indicator (only for GSec/T2F)8. Pre-engineering for padlocks

d. Mechanical interlocks

GSec has been designed to ensure maximum safety for the operators. It therefore features the following interlocks:

– Interlock between the line and earthing operations obtained by means of separate lever seats

– Panel door interlock thanks to the door lock device: the cable compartment can only be accessed when the earthing switch is closed. Moreover, the earthing switch cannot be opened or the panel be put into service unless the door has been closed. The cables can still be tested with the door open by removing the front guard from the apparatus.

– Interlock for the push-buttons of the 2S - Double spring operating mechanism: these push-buttons cannot be operated when the operating lever is connected.

– Motor interlock: if the operating mechanism is a motor operator, operation of the motor is disabled when the operating lever is in the line lock.

18

ABB CEF fuses for transformer protection Standard IEC 60282-1/DIN 43625

Three fuses (one for each phase) for transformer protection can be connected in series with the switch-disconnector.Selection of the fuses according to the voltage and power of the transformer, must be made in conformity with the data indicated in the table below.

Transformer protection and choice of fuses

When the isolators are used to control and protect

transformers, they are fitted with a particular type of current-limiting fuses which guarantee selectivity with other protection devices and can take the high transformer connection currents without deteriorating.

In this case, protection against overcurrents on the medium voltage side of the transformer is not indispensable since this task is carried out by the protection provided on the low voltage side. Protection on the medium voltage side can be entrusted just to the fuse, which must be chosen taking into account the no-load connection current since this can be the same or 10 times more that the rated current depending on the power of the transformer and the type of laminations used (hot-rolled or grain oriented).

There is maximum connection current when circuit-breaker closing takes place, corresponding to the voltage passing through zero.

A further result to be guaranteed is protection against faults in the low voltage winding and in the part of the connection between this and the circuit-breaker on the secondary, thus avoiding the use of fuses with rated current which is too high, in order to ensure tripping within a short time even under these fault conditions.

Rapid calculation of the short-circuit current at the secondary terminals of the transformer and on

the supply side of the circuit-breaker on the secondary,if installed at a significant distance, allows the tripping time to be verified on the fuse blowing curve.

The usage table given below takes both the required

conditions into account, i.e. rated current high enough to prevent untimely fuse blowing during the no-load connection stage and, in any case, of a value which guarantees

protection of the machine against faults on the low voltage side.

Choice of fuses for transformer protection Rated voltage of transformer [kV]Transformer power rating [kVA] Rated voltage of fuses [kV]

255075100125160200250315400500630800100012501600Fuse CEF In [A]

3 1625 25 40 40 50 63 80 100 125 ––––––3,6/7,2

5 101

6 25 25 25 40 40 50 63 80 100125––––6616 16 25 25 25 40 40 50 63 80100125–––1061016161620202531,540506380100125–1212661016161620202540405063801001251566101016161620202540405063808017,520666101016161620202531,5405063802424

6

6

6

6

10

10

16

16

16

20

20

25

40

40

50

63

3. Specific product characteristics

19

Altitude

The insulating properties of the air diminish as the altitude increases. This must be taken into account with regard to the external insulation of the equipment.

The phenomenon must always be considered when the insulating components of equipment that must be installed at more than 1000 m above sea level are designed.

In this case, one must consider a correction coefficient that can be taken from the graph on the following page, created in accordance with the indications provided by Standards IEC 62271-1.

The example below gives a clear interpretation of the indications described above.

20

DETAIL A 2 : 7

4. Overall dimensions

GSec/T1TN 2RDA017740A0001Type

12.08.2517.08.2024.06.1624.06.20

Weight [kg]

70

断路器事故故障分析与处理案例

断路器事故故障分析与处理案例本文介绍的断路器为弹簧储能操作机构27.5KV真空断路器。 1.事故案例1:断路器拒动特例: ①故障现象:断路器发生拒动故障后,检修人员现场试验正常;过一段时间,断路器从备用投入运行时又拒动,检修人员现场试验正常;请断路器厂家售后服务人员到现场调试两次,过一段时间,断路器投入运行时又拒动;断路器厂家请操作机构厂家人员到现场进行了一次调试,从此断路器再没有拒动。 ②故障原因:a、断路器操作机构间隙配合、合闸弹簧调整不不合理。B、断路器长时间不操作,各转动部分和脱扣器不灵活(油泥影响),第一次操作断路器拒动,但使脱扣器产生了位移,第二次操作断路器动作正常。 ③处理措施:请操作机构厂家人员到现场进行调试。长时间不用的断路器必要时进行分合闸2次。 2.事故案例2:真空灭弧室真空度降低故障: 真空度降低将严重影响真空断路器开断短路电流的能力和极间绝缘水平,并导致断路器的使用寿命急剧下降,严重时会引起真空灭弧室爆炸。 ①故障现象:运行人员巡视时,听到断路器真空灭弧室范围由放电声,但闻不到臭氧味,断路器在备用断开状态。将断路器

手车摇出时,拉弧放电声比正常大。 ②故障原因:将断路器手车操作到室外检修位车上,用真空测试仪对断路器真空灭弧室进行真空度测试,真空度由正常值10-6降低到了10-1,给断路器加交流耐压试验,电压升到20KV 时真空灭弧室极间击穿放电,远小于标准值42KV。因此说明断路器真空灭弧室真空度降低,造成灭弧室内极间放电。 ③处理措施:A. 立即更换真空灭弧室。B. 在进行断路器定期停电检修时,必须使用真空测试仪对真空灭弧室进行真空度的定性测试,当真空灭弧室真空度降低到10-4时,要对真空灭弧室进行交流耐压试验,耐压试验合格后监视运行;当真空灭弧室真空度降低到10-3时,再对真空灭弧室进行交流耐压试验,耐压试验不合格后,更换真空灭弧室。

变频器选型如何正确选择中小型断路器

变频器选型如何正确选择中小型断路器 集团标准化工作小组 [Q8QX9QT-X8QQB8Q8-NQ8QJ8-M8QMN]

如何正确选择中小型断路器 配电(线路)、电动机和家用电器等的过电流保护断路器,因保护对象(如变压器、电线电缆、电动机和家用电器等)的承受过载电流的能力(包括电动机的起动电流和起动时间等)有差异,选用的断路器的保护特性不同。 配电用断路器的选择 配电用断路器是指在低压电网中专门用于分配电能的断路器,包括电源总断路器和负载支路断路器。在选用这一类断路器时,需特别注意下列选用原则: (1)断路器的长延时动作电流整定值≤导线容许载流量。对于采用电线电缆的情况,可取电线电缆容许载流量的80%。 (2)3倍长延时动作电流整定值的可返回时间≥线路中最大起动电流的电动机的起动时间。 (3)短延时动作电流整定值I1为: I1=(Ijx+ 式中:Ijx———线路计算负载电流(A); k———电动机的起动电流倍数; Ied———电动机额定电流(A)。 (4)瞬时电流整定值I2为: I2=(Ijx+klkIedm) 式中:kl———电动机起动电流的冲击系数,一般取kl=~2; Iedm———最大的一台电动机的额定电流。 (5)短延时的时间阶段,按配电系统的分段而定。一般时间阶段为2~3级。每级之间的短延时时差为~,视断路器短延时机构的动作精度而定,其可返回时间应保证各级的选择性动作。选定短延时阶梯后,最好按被保护对象的热稳定性能加以校核。 电动机保护型断路器的选择 微型断路器(MCB)不能用于对电动机的保护,只可作为替代熔断器对配电线路(如电线电缆)进行保护。电动机在起动瞬间有一个5~7倍Ied,持续时间为 10s的起动电流,即使C特性在电磁脱扣电流设定为5~10倍Ied,可以保证在电动机起动时避过浪涌电流。 但对热保护来讲,其过载保护的动作值整定于,也就是说电动机要承受45% 以上的过载电流时MCB才能脱扣,这对于只能承受<20%过载的电机定子绕组来讲,

断路器的控制原理

断路器的控制原理 在发电厂和变电站中对断路器的跳、合闸控制是通过断路器的控制回路以及操动机构来实现的。控制回路是连接一次设备和二次设备的桥梁,通过控制回路,可以实现二次设备对一次设备的操控。通过控制回路,实现了低压设备对高压设备的控制。 一、控制信号传送过程 (一)常规变电站控制信号传输过程 某线路高压开关控制信号传递过程 由上图可以看出,断路器的控制操作,有下列几种情况: 1主控制室远方操作:通过控制屏操作把手将操作命令传递到保护屏操作插件,再由保护屏操作插件传递到开关机构箱,驱动跳、合闸线圈。 2就地操作:通过机构箱上的操作按钮进行就地操作。 3遥控操作:调度端发遥控命令,通过通信设备、远动设备将操作信号传递至变电站远动屏,远动屏将空接点信号传递到保护屏,实现断路器的操作。 4开关本身保护设备、重合闸设备动作,发跳、合闸命令至操作插件,引起开关进行跳、合闸操作。 5母差、低频减载等其他保护设备及自动装置动作,引起断路器跳闸。

可以看出,前三项为人为操作,后两项为自动操作,因此断路器的操作据此可分为人为操作和自动操作。 根据操作时相对断路器距离的远近,可分为就地操作、远方操作、遥控操作。就地通过开关机构箱本身操作按钮进行的操作为就地操作,有些开关的保护设备装在开关柜上,相应的操作回路也在就地,这样通过保护设备上操作回路进行的操作也是就地操作,保护设备在主控室,在主控室进行的操作为远方操作,通过调度端进行的操作为遥控操作。 (二)综自站控制信号传输过程 某线路高压开关控制信号传递过程 操作方式与常规变电站相比,仅在远方操作和遥控操作时不同。 在主控室内进行远方操作,一般是通过后台机进行,操作命令传达到测控装置,启动测控装置跳、合闸继电器,跳、合闸信号传递到保护装置操作插件,启动操作插件手跳、手合继电器,手跳、手合继电器触点接通跳、合闸回路,启动断路器跳、合闸。当后台机死机或其它原因不能操作时,可以在测控屏进行操作。 遥控操作由调度端(或集控站端)发送操作命令,经通讯设备至站内远动通讯屏,远动通讯屏将命令转发至站内保护通讯屏,然后保护通讯屏将命令传输至测控屏,逐级向下传输。 需要指出,有些老站遥控命令是通过后台机进行传输的,如虚线图所示,但由于后台机死机

断路器常见的问题及处理办法

高压断路器是电力系统中最重要的开关设备,它担负着控制和保护的双重任务,如断路器不能在电力系统发生故障时及时开断,就可能使事故扩大,造成大面积停电。为了满足开断和关合,断路器必须具备三个组成部分;①开断部分,包括导电、触头部分和灭弧室。②操动和传动部分,包括操作能源及各种传动机构。③绝缘部分,高压对地绝缘及断口间的绝缘。此三部分中以灭弧室为核心。 断路器按灭弧介质的不同可分为: 油断路器,利用绝缘油作为灭弧和绝缘介质,触头在绝缘油中开断,又可分为多油和少油断路器。 压缩空气断路器,利用高压力的空气来吹弧的断路器。 六氟化硫断路器,指利用六氟化硫气体作为绝缘和灭弧介质的断路器。 真空断路器,指触头在真空中开断,利用真空作为绝缘和灭弧介质的断路器。 断路器的分合操作是依靠操作机构来实现,根据操作机构能源形式的不同,操作机构可分为:电磁机构,指利用电磁力实现合闸的操作机构。 弹簧机构,指利用电动机储能,依靠弹簧实现分合闸的操作机构。 液压机构,指以高压油推动活塞实现分合闸的操作机构。 气动机构,指以高压力的压缩空气推动活塞实现分合闸的操作机构。 操作机构还有组合式的,例如气动弹簧机构是由气动机构实现合闸,由弹簧机构分闸。操作机构一般为独立产品,一种型号的操作机构可以配几种型号的断路器,一种型号的断路器可以配几种型号的操作机构。 下面就不同灭弧介质的断路器和不同型式操作机构分别介绍断路器在运行时最常见的故障,以及原因分析。 1.断路器本体的常见故障 1.1油断路器本体 序号常见故障可能原因 1 渗漏油固定密封处渗漏油,支柱瓷瓶、手孔盖等处的橡皮垫老化、安装工艺差和固定螺栓的不均匀等原因。 轴转动密封处渗漏油,主要是衬垫老化或划伤、漏装弹簧、衬套内孔没有处理干净或有纵向伤痕及轴表面粗糙或轴表面有纵向伤痕等原因。 2 本体受潮帽盖处密封性能差。 其他密封处密封性能差。 3 导电回路发热接头表面粗糙。 静触头的触指表面磨损严重,压缩弹簧受热失去弹性或断裂。 导电杆表面渡银层磨损严重。 中间触指表面磨损严重,压缩弹簧受热失去弹性或断裂。 4 断路器本体内部卡滞导电杆不对中。灭弧单元装配不当、传动部件及焊接尺寸不合格和灭弧单元与传动部件装配时间隙不均匀。 运动机构卡死。拉杆装配时接头与杆不在一条直线、各柱外拐臂上下方向不在一条直线上。 5 断口并联电容故障并联电容器渗漏油。 并联电容器试验不合格。 2真空断路器本体

ABB S型塑壳断路器

ABB S型塑壳断路器 一、性能描述 SACE Isomax S系列的不断发展使其成为今天市场上最大、最完善的低压塑壳断路器家族,可应用于任何民用、工业供电系统以及马达保护系统。具有高质量、高性能和高可靠性的特点。且安装简单,适用方便。 SACE Isomax S合理地分为额定电流从125A到1600A的7种 *规格:S1、S2、S3、S4、S5、S6、S7 *安装方式:固定式、抽出式、插入式 *分断能力:从16至200KA依次为:B、N、S、H、L、V、X(以便最大限度的满足任何电流系统的需要) SACE Isomax S的完整性还体现在其使用上的合理化:外形尺寸、安装方式以及同断路器安装方式无关的相同的附件。 二、产品组成 1、固定式塑壳断路器本体 2、脱扣单元 - 热磁脱扣 (在型号后没有PRxx之型号) 电磁脱扣值 Im=10Ith - 带微处理器过电流脱扣器 (在型号后有PR211/PR212之型号) - PR211-LI - PR212-LSI/LSIG 3、接线形式 - FF (前接线) - FR (后接线) - FFC (前接电缆) - FEF (前接线长端子) 1)塑壳断路器(S型) - 插入式固定部份 *插入式断路器底座 - 电缆前接线 (FC) FP: S4 PFC *插入式断路器底座 - 加长前接线 (EF) FP: S4 PEF

*插入式断路器底座 -后接线 ( R) FP: S4 PR 2)塑壳断路器(S型) - 抽出式固定部份*抽出式断路器底座 - 电缆前接线 (FC) FP: S4 WFC *抽出式断路器底座 - 加长前接线 (EF) FP: S4 WEF FP: S6 WEF FP: S7 WEF *抽出式断路器底座 -后接线 ( R) FP: S4 WR **抽出式断路器底座 -水平后接线 (HR) FP: S6 WHR FP: S7 WHR *抽出式断路器底座 -垂直后接线 ( VR) FP: S6 WVR FP: S7 WVR 三、产品选型 1、TM热敏电磁脱扣器的常用规格 2、微处理器脱扣器的常用规格

塑壳断路器的选用

1.引言 塑料外壳式断路器以下简称MCCB,作为低压配电系统和电动机保护回路中的过载、短路保护电器,是应用极广的产品。随着现代科技水平的不断发展,新技术、新工艺、新材料不断出现,断路器的生产工艺及各种材质不断改进,使断路器的性能有了很大的提高,除国际知名品牌,如ABB、施耐德外,国内一些企业也不甘落后,自行开发、研制或引进国外先进技术,并加以消化、吸收,也向市场推出了成熟了的产品如常熟开关厂的CMl、天津低压开关厂TM30等。这类产品具有零飞弧、高分断、大容量、进出线方向可以互换、智能型、四极、内部附件结构模块化、安装积木化、体积小型化等特点。实现了MCCB所需的选择性保护功能和多种辅助功能,并带有通信接口,使低压配电系统实现自动化和组网成为可能;降低了低压成套配电装置的动、热稳定性的要求;缩小了成套配电装置的体积;大大地提高了供配电系统和设备运行的可靠性。 然而,目前在一些电气设计方案中,对MCCB的正确合理选用并不尽人意,往往忽略了所选厂家的MCCB规格、型号、附件等其它电气参数,特别是对一些新型MCCB 的电气参数理解不透,标注不全、应用类别、使用场合及用途等考虑不周。选用了不合适的MCCB,导致成套厂订货困难,保护的选择性变差,灵敏性,合理性不符合设计规范要求,不但使MCCB没有物尽所用,反而造成了浪费,降低了配电系统的可靠性,影响了工矿企业的生产和人们的生活。为此,本文结合有关MC—CB的常用参数和国家标准谈谈自己对MCCB正确选用的一些看法。 2.断路器的常用基本相关符号其合义及相互之间的关系 Inm——断路器壳架等级电流,它所指的含义是本断路器内所能安装的最大 开关及脱扣器电流值。 In——断路器的额定电流,它所指的含义是该断路器内选用的额定热动型脱 扣器电流值,在不可调固定式热脱扣器中In=Ir1。 Ir1——断路器的长延时整定电流,它所指的含义是该断路器的过载保护脱 扣器所整定的电流值。 Ir2——断路器的短延时整定电流,它所指的含义是该断路器的短延时脱扣 器整定的电流,它的数值在电子可调式脱扣器中为~12Irl左右可调。 Ir3——断路器的瞬时整定电流,它所指的含义是该断路器瞬时脱扣器整定 的电流,它的数值在不可调固定式脱扣器中,配电型为5Irl、10Irl两种,电动机保护型为12Ir1,在电子可调式中,为~16Irl左右可调。 Ir4——断路器的单相接地整定电流,它所指的含义是该断路器保护的线路或设备发生单相接地故障时,接地保护脱扣器整定的电流值,它的数值为0.2~0.6Irl 左右可调。 Ire——断路器的漏电动作电流,它所指的含义是该断路器保护的线路或设 备发生不正常泄漏电流时,漏电保护脱扣器整定的电流值。它的数值为 0.03/0.1/0.3/0.5A几种。 Ir0——断路器预报警动作电流,它所指的含义是该断路器负载电流超出预 先设定的电流时,预报警装置发出报警指示信号,它的数值为~lIr1左右可调。 Ir2——短延时脱扣器的脱扣时间整定值,可调时间为0.05~0.45s。 3.MCCB的额定分断能力、Ics 根据IEC947—2《低压开关设备和控制设备,低压断路器》规范,

ABB微型断路器型号 文档

SH200-B 系列微型断路器型号 SH201-B6 SH201-B10 SH201-B13 SH201-B16 SH201-B20 SH201-B25 SH201-B32 SH201-B40 SH201-B50 SH201-B63 SH201-B6NA SH201-B10NA SH201-B13NA SH201-B16NA SH201-B20NA SH201-B25NA SH201-B32NA SH201-B40NA SH201-B50NA SH201-B63NA SH202-B6 SH202-B10 SH202-B13 SH202-B16 SH202-B20 SH202-B25 SH202-B32 SH202-B40 SH202-B50 SH202-B63 SH203-B6 SH203-B10 SH203-B13 SH203-B16 SH203-B20 SH203-B25 SH203-B32 SH203-B40 SH203-B50 SH203-B63 SH203-B6NA SH203-B10NA

SH203-B13NA SH203-B16NA SH203-B20NA SH203-B25NA SH203-B32NA SH203-B40NA SH203-B50NA SH203-B63NA SH204-B6 SH204-B10 SH204-B13 SH204-B16 SH204-B20 SH204-B25 SH204-B32 SH204-B40 SH204-B50 SH204-B63 SH200-C 系列微型断路器型号 SH201-C6 SH201-C8 SH201-C10 SH201-C13 SH201-C16 SH201-C20 SH201-C25 SH201-C32 SH201-C40 SH201-C50 SH201-C63 SH201-C6NA SH201-C8NA SH201-C10NA SH201-C13NA SH201-C16NA SH201-C20NA SH201-C25NA SH201-C32NA SH201-C40NA SH201-C50NA SH201-C63NA SH202-C6

断路器的控制原理图

四动力车间一月份车间培训讲义 授课人:高成波 授课时间:12月29日 一、断路器的规范及铭牌数据代表的意义 我车间110KV断路器为SF6气体断路器,灭弧介质为SF6气体;型号为LW35-126/3150-40;其中126代表断路器的额定电压(KV),3150为断路器的额定电流(A),40为断路器的额定短路断开电流(KA) 额定电压:是指断路器在运行中所承受的正常工作电压。 额定电流:是指断路器长时间通过的最大工作电流。 额定开断电流:是指断路器在额定电压下允许开断的最大电流。 二、高压断路器的用途 高压断路器是电力系统最重要的控制和保护设备,它在电网中起两方面作用。在正常运行时,根据电网的需要,接通或断开电路的空载电流和负载电流,这时起控制作用。而当电网发生故障时,高压断路器和保护装置及自动装置相配合,迅速、自动地切断故障电流,将故障部分从电网中断开,保证电网无故障部分的安全运行,以减少停电范围,防止事故扩大,这时起保护作用。 三、高压断路器的分类及组成部分 1、按灭弧介质分可分为: 1)油断路器 2)磁吹断路器 3)真空断路器 4)六氟化硫断路器 5)空气断路器 6)自产气断路器 2、高压断路器的组成部分 大体可分为:1)导电部分 2)灭弧部分 3)绝缘部分 4)机构及传动部分 5)附件 四、SF6断路器的种类及性能特点 SF6断路器的种类按构造分有敞开式和封闭式;按灭弧方式分有单压式各双压式;按总体分有落地箱式和支撑绝缘式。 SF6断路器的性能特点是: 1)灭弧能力强,介质绝缘强度高,单元额定电压较高。 2)在开断大电流时,产生的电弧电压不高,触头寿命长。 3)切断小电流电容电流时,过电压值较小,不需并联电阻。 4)本体寿命高,检修周期长,维护方便。 5)体积小,重量轻,结构简单,噪音小 五、断路器的简单灭弧原理 断路器的简单灭弧原理是利用热游离和去游离的矛盾,加速去游离的进行,减弱热游

断路器拒分故障的判断与处理方法

断路器的“拒分”对系统安全运行威胁很大,当设备发生故障时,断路器拒动,将会使电气设备烧坏或越级跳闸而引起电源断路器跳闸,使变配电所母线电压消失,造成大面积停电。对“拒分”故障的处理方法如下: 根据事故现象,判断是否属断路器“拒分”事故。当出现表记全盘摆动,电压表指示值显著降低,回路光字牌亮,信号掉牌显示保护动作,则说明断路器拒绝分闸。 确定断路器故障后,应立即手动拉闸。当尚未判明故障断路器之前而主变压器电源总断路器电流表指示值碰足,异常声响强烈,应先拉开电源总断路器,以防烧坏主变压器。当上级后备保护动作造成停电时,若查明有分路保护动作,断路器未跳闸,应拉开拒动的断路器,恢复上级电源断路器。 若查明各分路开关均未动作(也可能是保护拒掉牌),则应检查停电范围内设备有无故障,若无故障应拉开所有分路断路器,合上电源断路器后,逐一试送各分路断路器,当送到某一分路时电源断路器又再跳闸,则可判明该断路器为故障(“拒分”)断路器。这时不应再送该断路器,但要恢复其他回路供电。 在检查“拒分”断路器除属可迅速排除的一般电气故障(如控制电源电压过低,或控制回路熔断器接触不良,熔丝熔断等)外,对一时难以处理的电气或机械性故障,均应联系调度,作为停用、转检修处理。对断路器“拒分”故障的分析判断方法如下: 1、检查是否为跳闸电源的电压过低所致。 2、检查跳闸回路是否完好,如果跳闸铁芯动作良好而断路器拒分,则说明是机械故障。 3、如果电源良好,若铁芯动作无力、铁芯卡涩或线圈故障造成拒分,可能是电气和机械方面同时存在故障。 4、若操作电压正常,操作后铁芯不动,则很可能是电气故障引起“拒分”。常见的电气和机械方面的故障分别有: ·电气方面原因有:控制回路熔断器熔断或跳闸回路各元件如控制开关触点、断路器操动机构辅助触点、防跳继电器和继电保护跳闸回路等接触不良;跳闸回路断线或跳闸线圈烧坏;继电保护整定值不正确;直流电压过低,低于额定电压的80%以下。 ·机械方面原因有:跳闸铁芯动作冲击力不足,说明铁芯可能卡涩或跳闸铁芯脱落;触头发生焊接或机械卡涩,传动部分故障(如销子脱落等)。 艾驰商城是国内最专业的MRO工业品网购平台,正品现货、优势价格、迅捷配送,是一站式采购的工业品商城!具有 10年工业用品电子商务领域研究,以强大的信息通道建设的优势,以及依托线下贸易交易市场在工业用品行业上游供

断路器的分类及用途

旗开得胜 1、线路保护器可分为: 配电箱是将各种规格的高分断小型断路器,漏电断路器有机的结合起来。拼装箱体内,用于工业厂房、住宅、宾馆、商店等场所,它适用于交流220V、380V, 频率 501 E 的线路上。配电箱分明装、暗装、空箱、实箱(空箱断路器)。分为2-6 回路、 8 回路、12 回路、 15 回路、 16 回路及 24 回路。 断路器俗称空气开关MCB(塑料外壳)开关的一种。由手柄、动触头、静触头、弹簧、双金属片、连 杆、脱扣装置、铁芯、线圈、导弧片、灭弧片、导电部件和接线孔等部件组成。主要用于低压供电、配电 系统线路及电气设备过载及短路保护; 2、断路器的分类:(1)单断。( 2)双断。(3)双级。( 4)三级。 3、断路器的用途: (1)单断、双断、双级均用于家用。 (2)三级断路器若是380V 电压,则用于工业用电。 4、断路器的功能: (1)按安培数从小到大分为10A、16A、20A、25A、32A、40A、63A. (2)断路器都具有线路过载保护和短路保护作用。 5、配置方法: (1)10A 适用于照明线路。

旗开得胜(2)16A 适用于插座线路,一般家用电器。 (3)25A 适用于 2 匹左右空调或大于功率电器。 (4)32A 以上适用于柜式空调或更大功率电器。 6、注意事项: 每个电箱须装有一个带漏电的总制,以免发生漏电事故。只能运行于额定电流下,不得超越,以免起 不到保护作用。 7、断路器又可分为 塑壳式断呼器塑壳断路器用于分配电能和保护电路及电源设备的过载和短路,以及正常工作条件下, 作不频繁分断和接通电力线路之用。 高分断小型断路器适用于线路和电动机的边裁,短路保护。当线路发生过载和短路时,断路器会在 0.01 秒内切断电源,对线路起到保护作用,同时可做为不频繁转换和不频繁启起动之用。

低压断路器如何选型

低压断路器如何选型 低压断路器如何选型 低压电器选型的一般原则: 1、低压电器的额定电压应不小于回路的工作电压,即Ue≥Ug。 2、低压电器的额定电流应不小于回路的计算工作电流,即Ie≥Ig。 3、设备的遮断电流应不小于短路电流,即Izh≥Ich 4、热稳定保证值应不小于计算值。 5、按回路起动情况选择低压电器。如,熔断器和自动空气开关就需按起动情况进行选择。 断路器的选型:保护:过载,短路,欠电压。 一般选型: 1、断路器额定电压≥线路额定电压; 2、断路器额定电流≥线路计算负荷电流; 3、断路器脱扣器额定电流≥线路计算负荷电流; 4、断路器极限通断能力≥线路中最大短路电流; 5、线路末端单相对地短路电流不小于1.25倍的自动开关瞬时(或短延时)脱扣整定电流; 6、断路器欠电压脱扣器额定电压等于线路额定电压。

配电用断路器的选型: 1、长延时动作电流整定为导线允许载流量的0.8~1倍; 2、3倍长延时动作电流整定值的可返回时间不小于线路中最大起动电流的电动机的起动时间; 3、短延时动作电流整定值不小于1.1(Ijx+1.35kIedm)。Ijx为线路计算负荷电流;k为电动机起动电流倍数,Iedm为最大一台电动机额定电流; 4、短延时时间按被保护对象的热稳定校验; 5、无短延时时,瞬时电流整定值不小于 1.1(Ijx+1.35k1kIedm)。k1为电动机起动电流的冲击系数,取1.7~2。 如有短延时,则瞬时电流整定值不小于1.1的下级开关进线端计算短路电流值。 电动机保护用自动开关的选型: 1、长延时电流整定值=电动机额定电流; 2、6倍长延时电流整定值的可返回时间≥电动机起动时间; 3、鼠笼形瞬时整定电流为8~15倍脱扣器额定电流;绕线形瞬时整定电流为3~6倍脱扣器额定电流。 照明用自动开关的选型: 1、长延时电流整定值不大于线路计算负荷电流; 2、瞬时电流整定值=6倍的线路计算负荷电流。

断路器作用

断路器作用: 1.正常情况下接通和断开高压电路中的空载及负荷电流. 2.在系统发生故障时能与保护装置和自动装置相配合,迅速切断故障电流, 防止事故扩大,从而保证系统安全运行. 其实断路器就是一种开关,它和其他普通开关的不同点主要在:1.适用电压 等级高2.灭弧介质及方式,有真空,少油,多油及六氟化硫等等3.灭弧能力强,效果好. 一般情况下断路器本身不存在润滑方面的问题,需要润滑的常常是它的操 动机构 热继电器作用: 热继电器的作用是电动机过负荷时自动切断电源,热继电器的构造是两片膨胀系数不同的金属片构成,电流过大时膨胀系数大的先膨胀,起到切断电源的作用。热继电器动作后有人工复位和自动复位。 熔断器作用: 当电路发生故障或异常时,伴随着电流不断升高,并且升高的电流有可能损坏电路中的某些重要器件或贵重器件,也有可能烧毁电路甚至造成火灾。若电路中正确地安置了熔断器,那么,熔断器就会在电流异常升高到一定的高度和一定的时候,自身熔断切断电流,从而起到保护电路安全运行的作用 如果电路中安装了断路器就可以不用熔断器,热继电器需要与交流接触器

配合使用,因过载时热继电器上的触点断开切断控制回路,目前熔断器一般多用于控制回路。

断路器: 断路器是控制电气回路的分合开关,若以空气为灭弧介质的称空气断路器(开关)、若以SF6气体为灭弧介质的称六氟化硫断路器(开关)。断路器一般以额定电流(负荷)选择,做为电气回路的总开关使用。 漏电保护器和漏电保护开关: 漏电保护器和漏电保护开关:当一个空气开关带有漏电保护功能时,称之为漏电保护开关。如果是一个单单用于漏电保护的电气装置,则称之为漏电保护器。如图是一个漏电保护器,因为它并没有手动关断和合上的机构。 判定是否漏电的的原理依据是:流进和流出开关的电流必须相等,否则就判定为漏电。当漏电电流达到和超过一定的程度时,产生保护动作----跳闸。判定的阈值是可以设定的,因为电路就是我们设计的。只是应用时要根据不同的场合,选用不同灵敏度的保护器。 如果是用于人身安全保护为目的,则漏电电流小于30mA,视为安全,如大于30mA,则视为不安全,将产生保护动作。漏电保护的额定电流30mA的漏电保护器或保护开关,属于同敏度漏电保护器或保护开关。其生产保护动作时间还应在0.1秒以内。这两个参数的选择主要依据是: 30mA:人体的感知电流----男为1.1mA女为0.7mA;摆脱电流男为16mA女为10.5mA,儿童要较成人为小;在较短时间内危及生命的电流是致使电流,从两个方面理解----一是电流达到50mA就会引起心室颤动,有生命危险,

断路器的拒动处理

广铁集团 变电值班员技师培训 结 业 论 文 长沙供电段严凯 2012年8月

ZN42-27.5真空断路器的拒动处理 长沙供电段:严凯 摘要:在供电系统中最活跃的设备是断路器,断路器是高压开关设备中最重要、最复杂的一种,既能切换正常负载,又可切除短路故障,同时承担着控制和保护的双重任务。电气化铁道必须供电可靠,以保证列车的运行。能否可靠供电,关键之一断路器拒动能否正常运行。因此,在牵引供电中断路器必须可靠地工作,当断路器发生拒动时,值班人员应及时地排除故障,避免造成供电事故。 关键词:拒动故障处理 一、断路器在牵引变电所的重要性 《牵引变电所运行检修规程》规定“发现断路器拒动时应立即停止运行。”因此对断路器的拒动处理的能力是对牵引变电所值班人员的一项基本要求,也是牵引变电所值班人员的一个重要工作。 由于断路器要在正常工作时接通和切断负载电流,短路时切断短路电流。因此,断路器的可靠运行是保证铁道电气化可靠供电的重要设备,同时也是保证牵引变电所所内设备不受外界影响的关键设备。 断路器与隔离开关的配合使用,可实行多种不同的供电方式,这样可进一步加强供电的灵活性和可靠性。当牵引变电所主变压器出现故障必须退出运行时,断路器与隔离开关配合能自动投入另一台变压器运行,保证供电的连续性;当进线电源电压不保证时,断路器与隔离开关的配合能自动地把运行的变压器改由另一路电压正常的电源运行;当馈出线出现故障时,断路器能及时切断短路电流,同时进行一次自动重合,避免短路电流对所内设备造成损害。 二、断路器的基本要求

由于断路器要在正常工作时接通和切断负载电流,短路时切断短路电流,并受环境变化的影响,故对高压断路器的要求比较严,要求有如下几个方面: 1、工作可靠。断路器在额定条件下,应能长期可靠地工作。 2、应具有足够的开断能力。由于电网电压较高,电流较大,当断路器在断开电路时,触头间会出现电弧,只有将电弧熄灭,才能断开电路。因此,要求断路器有足够的开断能力,尤其在短路故障时,应能可靠地切断短路电流,并保证具有足够的热稳定和动稳定。 3、具有尽可能短的切断时间。当电力网发生短路故障时,要求断路器迅速切断故障电路,这样可以缩短电力网的故障时间和减轻短路电流对电气设备的危害。 4、结构简单、维修方便。 对于以上的第2至第4点的要求,是对断路器生产厂方的要求,基本上是在购买时就已经确定。因此我们运营单位,必须在可靠性方面下功夫;着眼于断路器的运行方式和控制系统,加大力度提高值班人员和维修人员在设备异常情况下的处理能力。 三、断路器拒动的故障处理 断路器是在牵引供电系统中是被操作最多的设备,馈线27.5KV断路器,基本上每天都会有合闸、分闸操作,因此,在变电所中断路器是故障多发设备。其故障中最使人头痛的是断路器的拒动。如果故障是断路器的组成元件故障则只有报废更换,这种故障不需值班人员处理,在此亦不作探讨。下面主要对断路器的拒动进行一些浅谈: 断路器的拒动只有拒分和拒合两种,然而不管断路器拒分还是拒合,其处理办法都基本一样。

万能断路器说明书..

智能型万能式断路器使用说明书 1.概述 1.1适用范围 HJW1系列空气断路器(以卜简称断路器)主要适用于交流50Hz,额定工作电压为400V、690V,额定电流为400A-6300A的配电网络中,用来分配电能和保护线路及电源设备免受过载、欠电压、短路取和接地等故障的危害。断路器核心部件采用智能型控制器,具有精确的选择性保护,可避免不必要的停电,提高供电系统的可靠性、连续性和安全性。 1.2型导及其舍义 1 3正常的使用,安装和运输条件 1.3.1正常使用条件 a)周围空气温度上限不超U+40℃,下限不低于-5℃,24h的平均值不超过+35℃, 注:在周围空气温度高于+40℃或低-5℃的条件下使用的断路器应与制造厂协商。 b)安装地点的海拔不超过2000m, c)大气的相对湿度在周围最高温度+40℃时不超过50%,在较低在温度下可以有较高的相对湿度(侧如 20℃时的90%),并考虑到因温度变化发生在产品表面上的凝露。 1.3.2正常安装条件 a)安装位置应垂直、各方向的倾斜度不超过5℃; b)污染等缎:3级 c)安装类别:断路器主电路及欠电压脱扣器线圈、电源变压器初级线圈为Ⅳ级,辅助电路、控制电路为 Ⅲ级。 1 3 3正常贮存和运输条件 a)温度下限不低于-25℃,上限小超过十55℃, b)相对湿度(25℃时)不超过95%, c)产品在运输过程中,应轻搬轻放,小应倒放,应尽量避免剧烈碰撞。 2.技术特征 21分类 2.1.1按安装方式分:固定式、抽屉式。 2 1 2按操作方式分:电动操作、手动操作。 2 1 3按脱扣器种类:具有智能型控制器、欠电压瞬时(或延时)脱扣器和分励脱扣器。 2 1 4智能型控制器分娄: a) Perfection-L(简称L)型(经济型,光柱显示), h) Perfection-M(简称M)型(普通型,LED数码显示), c) Perfection-H (简称H)型(增强型,LCD液晶显示)。

关于断路器异常运行及故障原因分析(终审稿)

关于断路器异常运行及故障原因分析 文稿归稿存档编号:[KKUY-KKIO69-OTM243-OLUI129-G00I-FDQS58-

关于断路器异常运行及故障原因分析 贾献居 (山东曹县供电公司) 摘要:高压断路器是重要的电网设备,其运行状态直接影响整个电力系统的运行稳定性和供电可靠性,所以做好高压断路器的异常分析,提高检修人员对各类异常的认识,对电网的稳定运行和提升检修人员的业务素质有着积极的意义。本文就断路器常见运行故障进行分析。 关键词:断路器、常见故障、原因分析。 断路器是接通和切断电路的主要电气设备.由于它的操作非常频繁,因此经常出现一些故障。例如,断路器合不上或拉不开.断路器不正常的自动分闸或自动合闸.泊断路器缺油或油质炭化,断路器操作能源失常,甚至还会发生断路器着火或爆炸的重大事故.等等。 一、断路器运行中发生拒绝跳闸故障的分析、判断与处理 断路器的"拒跳"对系统安全运行威胁很大,一旦某一单元发生故障时,断路器拒动,将会造成上一级断路器跳闸,称为"越级跳闸"。这将扩大事故停电范围,甚至有时会导致系统解列,造成大面积停电的恶性事故。因此,"拒跳"比"拒合"带来的危害性更大。对"拒跳"故障的处理方法如下。 1.拒跳”故障的特征为:回路光字牌亮,信号掉牌显示保护动作,但该回路红灯仍亮,上一级的后备保护如主变压器复合电压过流、断路器失灵保护等动作。在个别情况下后备保护不能及时动作,元件会

有短时电流表指示值剧增,电压表指示值降低,功率表指针晃动,主变压器发出沉重嗡嗡异常响声,而相应断路器仍处在合闸位置。 2.确定断路器故障后,应立即手动拉闸。 (1)当尚未判明故障断路器之前而主变压器电源总断路器电流表指示值碰足,异常声响强烈,应先拉开电源总断路器,以防烧坏主变压器。 (2)当上级后备保护动作造成停电时,若查明有分路保护动作,但断路器未跳闸,应拉开拒动的断路器,恢复上级电源断路器;若查明各分路保护均未动作(也可能为保护拒掉牌),则应检查停电范围内设备有无故障,若无故障应拉开所有分路断路器,合上电源断路器后,逐一试送各分路断路器。当送到某一分路时电源断路器又再跳闸,则可判明该断路器为故障(拒跳)断路器。这时应隔离之,同时恢复其他回路供电。 (3)在检查“拒跳”断路器除属可迅速排除的一般电气故障(如控制电源电压过低,或控制回路熔断器接触不良,熔丝熔断等)外,对一时难以处理的电气或机械性故障,均应联系调度,作为停用、转检修处理。 3.对“拒跳”断路器的电气及机械方面故障的分析判断方法。 (1)断路器拒跳故障查找方法。 首先应判断是电气回路故障还是机械方面故障: ①检查是否为跳闸电源的电压过低所致;

万能断路器结构及原理

前排左一:控制器 前排中:储能机构,上部—绿色为欠压脱扣器,蓝色为合闸线圈(合闸电磁铁),赭石色为分励脱扣器 前排右:电动机,上部——绿色部件为与欠压脱扣器联合使用的:欠压延时控制器。 后排断路器本体(导电机构,灭弧室,进出线排),上部浅灰色部分为二次接线端子。 框架断路器分为这样几个大的版块: 1、触头导电部件 由于承载电流多数在630A以上,最高可至6300A,出于支承,绝缘,以及预期短路电流较大,电弧能量强等方面因素的影响,触头导电部分,被密封在一个腔体内。外壳材料由专用的DMC材料压制而成。各相导电触头上,分别装设有专用的速饱和互感器。将该相的电流信号,传递至控制器。 2、储能操作机构 利用一系列复杂的机械机构,拉伸一根大直径弹簧储能,利用脱扣机构,将主弹簧自拉伸位置解锁释放,进而执行合闸或者分闸的操作。 主弹簧,及相连接整合在一起的这些连杆,弹簧,称为储能机构。 主弹簧的拉伸,一方面可以通过一个手柄,可以人力完成。 更多地,通过一个电机和相连的减速齿轮机构,依靠电机为主拉簧储能。电操,储能电机,MOE,叫法有点混乱。 三(四)极触头,均分别与储能机构相连接。 储能机构 操作机构,是机械产品。基于所学专业原因,觉得这部分比之控制器更重要,所以多看了好多。 【四两拨千斤是什么?看看这些较弱的塑料件就知道了。】

【下面这些红字,是说,红字所代表的附件与储能机构在此连接】 【千斤:主拉簧】 【最后:操作机构正面标准照】 3、关于控制器 (1)取_信号 电流: A相互感器,B相互感器,C相互感器,N相互感器,变压器中心点接地互感器; 返回:电流值集合IA/IB/IC/IN/Ig/IΔn 电压: A相电压,B相电压,C相电压 返回:电压值集合 Uab Uac Ubc 频率: 返回:f (2)数据预处理 这部分用来根据电压电流信号,计算出功率,功率因数,有功功率,无功功

最新断路器拒动(拒分、拒合)和误动应急救援

断路器拒动(拒分、拒合)和误动应急救援 1 故障描述及原因简析: 断路器操作时拒分拒合,操作电源空开(或保险)和SF6气压经检查属正常,它可能的原因有操作机构机械异常、分合闸线圈异常、监控装置异常、通讯异常、直流系统电压异常等。 2 人员部署: 工作班成员由继保组人员组成,(检查处理保护屏端子排以内范围故障,检查处理保护屏端子排以外故障。 3、工具材料准备: 序号名称数量准备单位备注1绝缘电阻测试仪1台继保组 2保护试验仪1套继保组 3手提工具箱(含万用表)2套继保组 4开关特性测试仪1套继保组根据必要4、工作票或应急抢修单准备: 办理人:继保组 办理方式:调出预存票样,日期、名称、编号、人员等留空,现场填写。 抢修现场工作负责人:由继保组人员担任。 5、工作流程及重点: 序号工作流程重点事项说明1工作负责人联系集控室,详询故障

设备情况,根据故障情况准备工器具、仪器,检查无误,出发到现场。如果怀疑开关本体绝缘及特性有问题,汇报领导。2办理工作许可手续 31、分合闸线圈有无异常; 2、机构箱内接线及电源有无异常; 3、机械部分有无异常; 4、开关本体及机械部分有无异常; 5、操作电源有无异常; 6、保护装置及屏内接线有无异常; 7、出口继电器及压板有无异常; 8、监控装置、通讯有无异常; 4工作负责人汇总检查情况,安排相应处理: 1、更换、检修故障部件。 2、就地机械分合闸,观察动作情况。 3、远方电动分合闸,观察监控、出口继电器、开关动作情况1、更换、检修故障部件时,操作及合闸电源均断开。 2、检修机械部分时机构应释能。 3、电动、机械分合闸试验时,相互告知,人员不得接触开关及机构,防止机械伤害。5恢复设备接线,仔细检查设备上有无遗留工器具和试验用导地线 6 办理工作终结手续、做好修试记录、向值班员交待相关事项。 7询问值班员是否会马上投运,如果会,等待投运。投运时,观察一二次设备是否正常。8工作负责人向抢修任务下达人汇报任务

断路器拒动的常见原因分析

断路器拒动的常见原因分析 【摘要】伴随着电力系统智能化和自动化程度的不断提高,操作者所需操作的断路器越来越远。但断路器拒动现象时有发生,从断路器本体、操作回路等方面总结、分析拒动的常见原因,有利于故障发生时快速准确处理故障。 【关键词】断路器;拒动;操作回路 0.前言 在进行断路器操作时,如果断路器拒动,电网的安全与稳定将受到影响,甚至引起停电范围扩大。笔者发现以下几个因素在断路器拒动故障时出现的几率较高:一是断路器本身存在机械故障;二是操作回路故障;三是远方操作回路的不完整或通讯、网络故障。 1.断路器本身存在机械故障造成拒跳事故 在一次操作断路器分闸时,B相拒动。通过灭弧室解体检查发现,在操作断路器分闸后,B相动静触头仍处于合位,而金属拉杆断裂并被电弧烧损,导电筒上有一道纵向裂纹,可分析得出该故障是因导电筒开裂引起的。导电筒是固定部件,它和下支撑座之间通过热套紧固成一体,组装成整体的动弧触头、灭弧喷嘴、加热筒在分合闸过程中在导电筒内上下滑动完成分合闸操作。由于导电筒产生裂纹使其和下支撑座之间发生松动,在合闸操作时因导电筒和加热筒之间导电弹簧带的摩擦力作用带着松动的导电筒上移,分闸操作时也带着导电筒下移。因为弹簧带摩擦力和导电筒惯性的共同作用,在断路器分、合操作若干次后使导电筒逐渐上移到一定位置。断路器在做故障发生前的合闸操作时,导电筒先于弧触头起弧并使不耐电弧的触指与其烧结并随后正常运行。由于触指和导电筒已烧结,无法脱离机构的分闸操作力,使金属拉杆在其最薄弱的长条孔某处断裂并起弧,电弧沿上下两侧分别烧蚀金属拉杆直至断口电弧不足以维持而熄灭。 2.操作回路故障,造成断路器拒动 2.1在一次断路器合闸操作时断路器拒合,经过二次回路检测发现,开关合闸线圈烧毁,造成断路器不能合闸。经检修人员更换合闸线圈后,故障消除,操作人员对开关进行分合试验,开关操作恢复正常。 2.2辅助接点故障也是造成断路器拒动的常见原因之一。在一次线路送电操作中,断路器拒合。随后发现断路器就地操作正常,判断故障点发生在控制回路上。继电保护人员到现场通过电位测量,模拟实际断路器控制开关转动位置的电位变化,发现断路器控制开关辅助接点不通。经过更换备用断路器控制开关后,故障消除,开关分合正常。 2.3发生保护回路继电器触点粘连的现象。电动合闸瞬间,红灯闪亮,表示油断路器已合闸,但瞬时红灯熄灭,绿灯又亮,断路器又分闸,同时观察跳闸铁芯动作。这种合闸后瞬间又分闸的异常现象,常出现在用于速断(1.2LJ)过流( 3.4LJ)保护的电流继电器,因保护定值调整把手在刻度盘的前半部分,弹簧反作用力矩小,使常开触点在事故跳闸后不返回,造成触点粘连。跳闸回路长时间带电,或者在开关合闸瞬间开关柜上继电器接点受震动瞬间粘连造成。有时也出现在作用于断路器跳闸的时间继电器(SJ)触点的粘连,这是因为时间继电器铁芯卡死,在线圈失电后不返回。此外,直流电压过低,发出合闸命令后虽机构动作,但不能合闸、手车开关弹簧机构未储能、液压机构开关压力不足、SF6 气体开关气压过低、运行位置的行程开关切换不到位或开关触点接触不良等,这些

ABB S260微型断路器选型指南

ABB S260系列微型断路器选型指南 本文选自:工控商务网 规格:ABB S260微型断路器选型指南 意义:为了更快更精确筛选出客户要求的产品,提高客户的满意度和交易率 事件类别:产品选型(自动生成) 应用岗位:[业务业务助理技术后勤] 需备资质:[对S260微型断路器主要技术参数了解和熟悉] 品牌:ABB 系列:S260 品名:微型断路器客户类型:全部行业:全部 一. 名词解释 1.1额定电流: 电气设备的额定电流是指在基准环境温度下,在额定电压工作条件下,发热不超过长期发热允许温度时所允许长期通过的最大电流。 1.2分断能力: 断路器的分断能力是指该断路器安全切断故障电流的能力。 1.3脱扣器:s260系列微型断路器有电磁脱扣器与热脱扣器。 (1)电磁脱扣器: 只提供磁保护,也就是短路保护,其实际上是一个磁回力,当电流足够大时产生的 磁场力克服反力弹簧吸合衔铁打击牵引杆从而带动机构动作切断电路。 (2)热磁脱扣器: 由于每相电流都对应安装有一个电磁脱扣装置和一个热脱扣装置,在任何一相短路 或者过载时,相应的电磁脱扣装置或热脱扣装置均会动作。

1.4接线方式:两用端子可同时连接电缆和汇流排 当额定电流小于40A时,用0.75-25的导线 当额定电流为50、63A时,用0.75-35的导线 二. 了解信息 2.1 S260微型断路器的选型必须向客户了解以下技术参数信息: 2.2 S260微型断路器的系列:S260 S260OV S260UC S260(PT) S260(G) S260(M) S260H 2.3 S260微型断路器的额定电流(A):0.5、1、2、3、4、6、10、16、20、25、32、40、50、63 0.5~50(S260(G)脱扣特性为C) 3、6、10(S260(PT)) 2.4 S260微型断路器脱扣器形式:热磁式(S260、S260OV、S260UC S260(G)、S260(M)、S260H) 单磁式(S260(PT)、S260(M))2.5 极数:1、2、3、4 、1+NA 脱扣特性:B、C、D、K 注意事项