当前位置:文档之家› 压差旁通控制单台变频的水泵并联工作特性研究

压差旁通控制单台变频的水泵并联工作特性研究

龙源期刊网 https://www.doczj.com/doc/486334244.html,

压差旁通控制单台变频的水泵并联工作特性研究

作者:陶佳

来源:《科技资讯》2013年第16期

摘要:理论分析了压差旁通控制下单台变频的水泵并联工作特性,结合工程实例进行了

验证。结果表明,工频泵能耗随变频泵运行频数的降低而增加,随冷源侧管路阻力的增大而减小;冷源侧管路阻力越小,工频泵能耗变化越小,运行越稳定。

关键词:压差旁通并联水泵变频能耗

中图分类号:TU991.3 文献标识码:A 文章编号:1672-3791(2013)06(a)-0080-03

Study on characteristics of parallel pumps with single variable-speed pump by pressure difference bypass

TAO jia

(Technician College,Guangdong Province,Huizhou Guangdong,516100,China)

Abstract:Theoretical analysis is implemented on characteristics of parallel pumps with single variable-speed pump by pressure difference bypass,the practical project verifies the results.The results show that the energy of constant-speed pumps increase when the operating frequency of variable-speed pump reduces.The energy of constant-speed pumps reduce when the pipeline resistance of cold source increases.The less pipeline resistance of cold source, the less energy of constant-speed pumps and the more stable operation of constant-speed pumps.

Key Words:Pressure bypass;Parallel pumps;Variable-speed;Energy

随着变频器技术的日趋成熟,产量的迅猛增加以及价格的不断下降,变频器的应用场合不断扩大。目前,在大型楼宇、生产厂房的供水及冷热源系统中,变频泵的应用越来越广泛。其中多台定速泵加一台变频泵并联运行的系统配置方式越来越多的被采用[1]。本文根据水泵的

特性曲线,对压差旁通控制条件下单台变频的水泵并联工作特性进行了探讨。

1 系统组成

一般的压差旁通控制冷冻水泵并联系统如图1所示。将供水压力和回水压力引入压差控制器,根据设定值控制旁通电动阀,通过调节旁通水量,恒定冷水系统供水和回水之间的压差。使冷水系统能够在末端负荷较低的情况下,仍能保证冷冻机等设备的正常运转。