当前位置:文档之家› 住宅小区供配电系统设计

住宅小区供配电系统设计

住宅小区供配电系统设计
住宅小区供配电系统设计

XX学院

毕业论文(设计)

住宅小区供配电系统设计Residential quarters for the distribution design

系别物理与电子信息工程系

专业电气工程及其自动化

学号 XX

姓名 XX

指导教师 XX

2009年 5月10日

摘要

要提高高层建筑配电系统的可靠性,要正确选择各类配电设备的容量,就必须科学、合理的进行负荷计算。本文对符合计算中的相关问题进行了分析和探讨,就重要设备的容量选择做了较为详细的论述,提出了一些进一步提高配电系统可靠性的措施,并结合工程实例进行负荷计算,计算结果证明本文所述方法是正确合理,可在实际中应用。高层建筑比一般建筑遭受雷击的概率要大得多,而一旦遭受雷击,损失将非常严重。另外,普通建筑物防雷系统不但不能保护高层建筑物内的电子设备与计算机系统,反而可能会引入雷电。因此,高层建筑的防雷保护就越显重要,相应地对防雷保护提出了更高的要求。本文对于高层建筑物的防雷保护措施做了较为仔细的分析。

关键词:配电系统;负荷计算;防雷设计;照明

Abstract

In order to improve the reliability of power distribution system of high building,choice capacity of power distribution debice rightly,it is necessary tocalculate charge rightly,the author analyacs and investigatcs relative question with charge calculation,expatiates particularly capacity choice of important equipment,puts forward these measure being used to improve the reliability of power distribution system,makes charge calculation combination to project example,the result shows that these means is right and reasonable,these means can guide project practice. High buiding is easy suffered from lightning stroke,in case being suffered lightning stroke,it should bring huge losing,lightning protection system of common building can not protect electronic device,on the contrary,it may intoduce lifhtning therefore high building’s lightning protection is more important.The author analyses and research these question of over voltage and of lifhtning stroke,puts forward these means of lightning protescition of in high building.

Keywords: power distribution system ;load calculation synthetic; lightning protection;Illumination

目录

摘要 ..................................................................... I Abstract ................................................................. I 第一章前言 .. (1)

第二章工程概述 (2)

第三章电气照明设计 (3)

3.1照明系统的概述 (3)

3.1.1照明系统的发展现状 (3)

3.1.2照明计量单位 (3)

3.2照度方式和种类 (3)

3.2.1照明方式 (3)

3.2.2照明种类 (4)

3.3照度计算 (5)

3.3.1利用系数法 (5)

3.3.2单位容量法 (6)

3.4该小区的电气照明设计 (8)

3.4.1电气照明设计的基本原则 (8)

3.4.2电气照明详细设计计算 (8)

3.5 插座系统 (14)

3.5.1插座系统的概述 (14)

3.5.2一般规定(规范) (14)

3.5.3 插座的安装 (14)

3.5.4该小区住宅的插座系统设计 (16)

3.5 该小区标准层照明设计 (17)

第四章低压配电系统设计 (18)

4.1 高层建筑一般规定 (18)

4.2低压配电系统线路的选择 (20)

4.2.1 低压线路接线方式 (20)

4.2.2导线和电缆的选择 (22)

4.3低压配电系统电气设备的选择 (22)

4.3.1 基本要求 (22)

4.3.2漏电保护 (23)

4.4配电变压器的选择 (23)

4.5小区的低压供配电系统设计 (23)

4.5.1 小区整体低压配电设计(见附录1) (23)

4.5.2 小区1号楼与4号楼低压配电设计(见附录2) (24)

4.5.3 小区2号楼与3号楼低压配电设计(见附录2) (24)

4.5.4小区商业、电梯、车库、消防、物管用电低压配电设计(见附录3) (25)

4.6负荷计算的方法 (26)

4.7小区住宅的负荷计算 (27)

第五章防雷接地系统设计 (32)

5.1防雷与接地系统概述 (32)

5.1.1 防雷系统概述 (32)

5.1.2 建筑物的防雷等级 (32)

5.1.3高层建筑物的防雷措施 (33)

5.1.4接地系统概述 (34)

4.4小区1#楼接地设计 (37)

第六章技术经济分析 (38)

第七章结论 (39)

参考文献 (39)

致谢 (39)

附录1 小区整体低压配电平面布置图

附录2 小区1号楼与4号楼低压配电平面布置图

附录3 小区商业、电梯、车库、消防、物管用电低压配电平面布置图

附录4 小区1号楼、2号楼配电系统接线图

第一章前言

本次设计的题目是厦门某住宅小区电气系统设计。通过具体的实例工程设计,初步掌握高层建筑供配电系统设计的基本方法,更好的将理论和实践相结合,将大学四年来所学的课程及知识应用到自己的专业中去,也为将来的工作打下良好的基础。同时也可以更加详细地学习建筑规范,提高自己独立完成工程设计的实际操作和研究能力。

本工程为一类高层建筑,按三级负荷供电,二类防雷建筑物、二级防火进行电气系统设计。在本设计中,要求完成对住宅小区供配电系统设计,主要包括照明系统、低压供配电系统、负荷计算、防雷与接地系统。论文针对住宅小区电气的设计和使用需要,在重点表述低压供配电系统、负荷计算和防雷与接地系统的同时,侧重于电气基本理论和基本知识。设计中,总体按照民用建筑设计规范来建立设计的整体思路,并完成低压供配电、负荷计算、设备选型、系统构成以及施工图的绘制。

本毕业设计论文共分七章。其中第1章是前言;第2章为工程概述;第3章为电气照明设计;第4章低压配电系统设计;第5章为防雷接地系统设计;第6章为技术经济分析;第7章为结论。

第二章工程概述

本次设计具体项目为厦门某住宅小区项目。该住宅小区总面积大约为57000平方米,建筑面积约为37000平方米,共有四栋楼,一号楼、二号楼分别有25层,每层有6户,共300户。三号楼、四号楼分别有6层,每层6户,除去第一层为商业店面共60户。每户面积在90平方米至120平方米之间。本设计为普通民用高层住宅,为一类高层建筑,按三级负荷供电。防火等级为二级,按二类防雷建筑物设计防雷。

本设计采用10kv/0.4kv进线形式,接地形式采用TN-C-S系统进户处设重复接地,采用综合接地方式,接地利用建筑物基础作接地极,接地电阻不大于10欧。电源进线采用YJV22-10kv-3*95电缆引入。本次电气系统设计主要包括:照明系统设计,低压供配电系统设计,小区负荷计算,防雷与接地系统。

防雷接地设计,根据防雷等级进行设计,对主要建筑物和电气设备采取防雷和接地措施,以保护国家财产免遭损失和保障人身安全。

第三章电气照明设计

3.1照明系统的概述

3.1.1照明系统的发展现状

在照明上不再是60-70年代住宅2W/㎡,办公室4 W/㎡,而是各类建筑物的照度在适应国情下尽可能与国际接轨,如体育馆的拳击厅照度为1000-2000 lx,乒乓球台面照度为500-1000 lx;住宅也按不同用途,照度自20-300 lx变化;一般办公室的照度为100-200 lx;绘图、设计、打字室工作面照度为300-500 lx 等。

在同一栋建筑物中,照明的种类也增多了,有一般的工作照明、局部工作照明、备用照明、安全照明、疏散指示照明、值班照明、障碍照明、节日照明等。不同的照明类别,其供电要求也不同,控制方式也各异。如备用照明应有二路电源;安全照明、疏散指示照明、障碍照明不仅应有二路电源,而且还应在末级配电设备上设置备电自投装置。大面积的工作照明,要求集中控制或按工作时间自动开启及关闭。为节约电能,外围有自然采光部分的灯具,还应设置按照明度标准自动调光的装置;疏散指示照明在火警时消防控制室可按需要进行控制;障碍照明应按日照照度进行自动控制等。

由此可见,照明在照度、照明质量、照明方式、灯具外型、供电要求及控制上,都有不同程度的发展和更高的要求。

3.1.2照明计量单位

当前各种量都逐步实现采用国际单位制,简称SI。光学计量基本单位为光强I(坎德拉cd),导出单位有光通Φ(流明lm)﹑照度E(勒克斯lx)﹑出射度M(流明/米2lm/m2)、亮度L(坎德拉/米2cd/m2)等。

3.2照度方式和种类

3.2.1照明方式

?一般照明

为使整个照明场地获得均匀明亮的水平照度,使用照明器在整个照明场所基本均匀布置的照明方式。

?分区一般照明

根据需要提高特定区域照度的一般照明称为分区一般照明。根据工作面布置的实际情况,将照明器集中或分区集中均匀地布置在工作区上方,使室内不同被照面上产生不同的照度,可以有效地节约能源。

?局部照明

以满足照明范围内某些部位的特殊需要而设置的照明称为局部照明。它仅限于照亮一个有限的工作区,通常采用从最适宜的方向装设台灯、射灯或反射型灯泡。起优点是灵活、方便、节电,能有效地突出重点。

?混合照明

有一般照明和局部照明共同组成的照明称为混合照明。其实质是在一般照明的基础上,在另外需要提供特殊照明的局部,采用局部照明。

3.2.2照明种类

?正常照明

为满足正常工作而设置的室内外照明称为正常照明。它起着满足人们基本视觉要求的功能,是照明设计中的主要照明。它一般可单独使用,也可与应急照明和值班照明同时使用,但控制线路必须分开。

?应急照明

在正常照明因事故熄灭后,供事故情况下继续工作、人员安全或顺利疏散的照明称为应急照明。它包括备用照明、安全照明、和疏散照明三种。应急照明的设置原则,从安全角度考虑,应在较多的建筑内设置应急照明,而从经济的观点出发,只能在一些最需要的建筑内设置。

?值班照明

在非工作时间供值班人员观察用的照明称为值班照明。可利用正常照明中能单独控制的一部分或应急照明的一部分或全部作为值班照明。

3.3照度计算

照度计算方法有利用系数法、单位容量法和逐点法等3种[1]。任何一种计算方法,都只能做到基本准确。

3.3.1利用系数法

此法适用于灯具均匀布置的一般照明以及利用墙和天棚作为光线反射面的场合。当选用反射式、半反射式或漫射式等主要利用反射光通的照明灯具时,必须采用此法计算在工作面上的平均照度E系由光源光通的直射分量以及经房间多次反射的分射分量所造成的。投射在工作面上的这两个光通之和ΣF与照明灯具在受照房间内所发出的总光通NF之比称为利用系数η。即

η5ΣF/NF 3-1

式中F——每一个照明灯具所发出的光通量,流明。

照明装置的利用系数与下列因素有关:

?照明灯具的效率及光强分布的情况;

?墙壁、天棚和地板的反射系数Pq、Pt和Pd;

?室形指数。

对于方形的房间,室形指数i按下式确定:

i=A·B/h(A+B)3-2式中AB——房间的长度和宽度,米;

h——照明灯具的计算高度,米。

利用系数法的基本公式为

F=EminKZS/Nη流明3-3

Emin=FNη/KZS勒克斯3-4式中 F-每一个灯泡的光通量,流明;

Emin-最小照度

K-减光补偿系数

S-房间面积

N-灯具数量

Z-最小照度

-光通利用系数

3.3.2单位容量法

单位容量法的基本公式:

W=P/A 3-5

W—在最低照度下每单位面积的安装功率(W)

P—房间内全部灯泡(管)的总安装功率(W)

A—房间的面积(㎡)

根据已知的面积和所选的灯具形式、最小照度E、计算高度h,从表3-1到表3-3查得每单位面积的安装容量W,从上式算出全部灯泡的总安装功率P。然后除以灯具的功率,再考虑到室形及对灯具布置的要求即可得灯具数量。

表3-1住宅建筑照明的标准值

表3-2荧光灯单位面积安装功率

表3-3灯单位面积安装功率

3.4该小区的电气照明设计

3.4.1电气照明设计的基本原则

?本设计照度标准选用国家民用建筑照明标准为基准,并参照有关国外照明标准进行设计。

?照明电源,根据国家节能要求特殊装修要求外,均选用高效,低耗的节能型日光灯和节能筒灯为主。

3.4.2电气照明详细设计计算

本设计采用单位容量法

对本次的小区住宅1#共有A、B两个户型来说明设计。

?A户型的照度计算

表3-4A户型详情

①主卧室:

房间面积A=15.74m2,取照度E=50lx,

选用荧光灯(2×36W),查表3-3得单位容量W=4.5 W/m2

根据W=P/A得,房间内的总安装功率P=W×A=4.5×15.74=71W

所以在主卧室中央位置设置双管荧光灯一盏,2×36W,P0=2×36=72W

②次卧室:

房间面积A=12.4m2,取照度E=50lx,

选用荧光灯(2×36W),查表3-3得单位容量W=5.2 W/m2

根据W=P/A得,房间内的总安装功率P=W×A=5.2×12.4=57 W,

所以在次卧室中央设置一盏2×36W双管荧光灯一盏,P0=2×36=72W

③客厅:

房间面积A=27.68 m2,取照度E=30lx,

选用花灯(6×60W),查表3-3得单位容量W=14.8 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=14.8×27.68=410W,

所以在客厅中央位置设置一盏6×60W花灯,以及一盏60W的圆球吸顶灯做辅助照明,P0=6×60W+60W=420W

④餐厅:

房间面积A=11.2m2,取照度E=30lx,

选用花灯(4×60W),查表3-3得单位容量W=20.9 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=11.2×20.9=234 W,

所以在餐厅中央位置设置一盏4×60W花灯,P0=4×60W=240W

⑤主卧室卫生间:

房间面积A=4.94 m2,取照度E=15lx,

选用防水防潮灯(40W),查表3-3得单位容量W=11.6 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=11.6×4.94=57 W,

所以在主卧室卫生间中央设置一盏40W的防水防潮吸顶灯,以及一盏20W 镜前防水壁灯,P0=40W+20 W =60W

⑥卫生间:

房间面积A=4.02m2,取照度E=15lx,

选用防水防潮灯(40W),查表3-3得单位容量W=11.6 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=11.6×4.02=47 W

所以在主卧室卫生间中央设置一盏40W的防水防潮吸顶灯,以及一盏20W 镜前防水壁灯,P0=40W+20W =60W

⑦书房:

房间面积A=12.86 m2,取照度E=150lx,

选用荧光灯(36W),查表3-3得单位容量W=15.6W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.6×12.86=200W

所以在书房中央位置设置一盏2×36W双管荧光灯,门口处设置一盏60W的圆球吸顶灯,书桌处可按放台灯做局部照明以达到照度要求。

P0=2×36W+60W =132W

⑧厨房:

房间面积A=6.58m2,取照度E=20lx,

选用防水防潮灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×6.58=100 W

所以在厨房中央设置一盏60W防水防潮灯。

⑨走廊:

房间面积A=8.56m2,取照度E=20lx,

选用圆球吸顶灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×8.56=130 W,

所以在厨房中央设置二盏60W防水防潮灯,P0=60W+60W =120W

⑩阳台:

房间面积A=3.32m2,取照度E=20lx,

选用圆球吸顶灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×3.32=50W,

所以在阳台中央设置一盏60W防水防潮灯。

A户型总照明功率共计1336W。

?B户型的照度计算

表3-5B户型详情

①主卧室:

房间面积A=15.74m2,取照度E=50lx,

选用荧光灯(2×36W),查表3-3得单位容量W=4.5 W/m2

根据W=P/A得,房间内的总安装功率P=W×A=4.5×15.74=71W,

所以在主卧室中央位置设置双管荧光灯一盏,2×36W ,

P0=2×36=72W

②次卧室:

房间面积A=12.4m2,取照度E=50lx,

选用荧光灯(2×36W),查表3-3得单位容量W=5.2 W/m2

根据W=P/A得,房间内的总安装功率P=W×A=5.2×12.4=57 W,

所以在次卧室中央设置一盏2×36W双管荧光灯一盏,

P0=2×36=72W

③客厅:

房间面积A=27.68 m2,取照度E=30lx,

选用花灯(6×60W),查表3-3得单位容量W=14.8 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=14.8×27.68=410W,

所以在客厅中央位置设置一盏6×60W花灯,以及一盏60W的圆球吸顶灯做辅助照明,

P0=6×60W+60W=420W

④餐厅:

房间面积A=11.2m2,取照度E=30lx,

选用花灯(4×60W),查表3-3得单位容量W=20.9 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=11.2×20.9=234 W,

所以在餐厅中央位置设置一盏4×60W花灯,

P0=4×60W=240W

⑤主卧室卫生间:

房间面积A=4.94 m2,取照度E=15lx,

选用防水防潮灯(40W),查表3-3得单位容量W=11.6 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=11.6×4.94=57 W,

所以在主卧室卫生间中央设置一盏40W的防水防潮吸顶灯,以及一盏20W 镜前防水壁灯,

P0=40W+20 W =60W

⑥卫生间:

房间面积A=4.02m2,取照度E=15lx,

选用防水防潮灯(40W),查表3-3得单位容量W=11.6 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=11.6×4.02=47 W,

所以在主卧室卫生间中央设置一盏40W的防水防潮吸顶灯,以及一盏20W 镜前防水壁灯,

P0=40W+20W =60W

⑦书房:

房间面积A=12.86 m2,取照度E=150lx,

选用荧光灯(36W),查表3-3得单位容量W=15.6W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.6×12.86=200W,

所以在书房中央位置设置一盏2×36W双管荧光灯,门口处设置一盏60W的圆球吸顶灯,书桌处可按放台灯做局部照明以达到照度要求。

P0=2×36W+60W =132W

⑧厨房:

房间面积A=6.58m2,取照度E=20lx,

选用防水防潮灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×6.58=100 W 所以在厨房中央设置一盏60W防水防潮灯。

⑨走廊:

房间面积A=8.56m2,取照度E=20lx,

选用圆球吸顶灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×8.56=130 W,所以在厨房中央设置二盏60W防水防潮灯,

P0=60W+60W =120W

⑩阳台:

a)阳台1:

房间面积A=3.32m2,取照度E=20lx,

选用圆球吸顶灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×3.32=50W,所以在阳台中央设置一盏60W圆球吸顶灯。

b)阳台2:

房间面积A=6.04m2,取照度E=20lx,

选用圆球吸顶灯(60W),查表3-3得单位容量W=15.2 W/ m2

根据W=P/A得,房间内的总安装功率P=W×A=15.2×6.04=92W,所以在阳台中央设置二盏60W圆球吸顶灯,

P0=60W+60W =120W

B户型照明功率共计1396W.

3.5 插座系统

3.5.1插座系统的概述

插座这个小小的电气装置元件,往往容易被人忽视,但在现代住宅中却随处可见,不管是在客厅、卧室、书房,还是在厨房、餐厅、卫生间,人们都要使用它,甚至阳台都忘不了装一个插座,以备它用。

现代生活水平不断的提高,人们对住宅电气装置的要求也越来越高,人们不再满足于照明、风扇、洗衣机、电冰箱、彩电等电气设备带来的方便,而更加热衷追求音响、空调、大屏幕彩电、电脑、电话带来的享受。随着当今知识经济、信息时代的到来,可视电话、电子购物、家庭办公等智能化住宅建筑将不断涌现。这些电能、信息的传递除通过电线、电缆外,还必须通过插座这个小小电气装置元件输送给用电设备或信息终端。可见,插座的种类和数量在现代住宅中呈日益增长的趋势。所以,现代住宅中插座的选型、布置位置、数量和安装高度都直接关系到住户今后的使用效果,是现代住宅电气设计中十分重要的内容。

现代住宅是由客厅、卧室、书房、厨房、餐厅、洗涤间、卫生间、阳台等组成的。住户的家用电器众多,而且又在不断地增加,好像根本无处着手。其实不然,我认为:只要明确住宅中各个房间主要会有哪些家用电器,然后根据建筑平面图,考虑住户一般会怎样去布置。按照这种思路去思考,目的性就很强。3.5.2一般规定(规范)

?当插座为单独回路时,数量不宜超过10个(组)。

?当灯具和插座混为一路过,其中插座数量不宜超过5个(组)。

?插座应由单独的回路配电,并且一个房间内的插座由同一路配电。

?在潮湿房间(住宅中的厨房除外)内,不允许装设一般插座,但设置有安全隔离变压器的插座可除外。

?备用电源、疏散照明的回路上不应设置插座。

3.5.3 插座的安装

依据《通用用电设备配电设计规范》GB 50055-93[2],插座的型式和安装高度,应根据其使用条件和周围环境确定:

?对于不同电压等级,应采用与其相应电压等级的插座,该电压等级的插座不应

被其他电压等级的插头插入。

?需要连接带接地线的日用电器的插座,必须带接地孔。

?对于插拔插头时触电危险性大的日用电器,宜采用带开关能切断电源的插座。?在潮湿场所,应采用密封式或保护式插座,安装高度距地不应低于1.5m。

?在儿童专用的活动场所,应采用安全型插座。

?住宅内插座,若安装高度距地1.8m及以上时,可采用一般型插座;低于1.8m 时,应采用安全型插座。

具体设计如下:

?起居室

①应保证每个主要墙面均有一个5孔插座(5孔插座指一个单相三线和一个单相两线的组合插座,以后不再赘述)。

②如果墙面长度超过3.6m应适当增加插座数量。墙面长度小于3.6m,插座可安置在墙面的中间位置。

③设置电视出线插座的墙面(此墙面为电器摆放集中之处)应至少设置两个5孔插座,其中一个插座应与电视出线插座相靠近并与之保持0.5m以上距离。

④空调器插座应采用专用带开关插座。在已知采用何种空调的情况下空调插座按以下位置布设:如是分体空调插座宜根据出线管预留洞位置距地1.8m设置, 如是窗式空调宜在窗旁距地 1.4m设置,如是柜式空调宜在相应位置距地0.3m 设置,否则按分体空调考虑预留空调插座。

?卧室

①应保证两个主要墙面至少各有一个5孔插座,设置电视出线插座的墙面至少有一个5孔插座与之相靠近。

②如卧室面积较大应适当增加插座数量。

?厨房

①厨房内插座应为防溅插座,宜组成一单独回路不与其它插座混连。

②参考厨房操作台、灶台、置物台、洗菜台布局选取最佳位置设置抽油烟机插座、电热插座。抽油烟机插座距地2.0m设置,电热插座距地1.4m或根据操作台和吊柜具体位置设置。

③电热插座应选用带开关16A单相三线插座,如电热器具有固定位置应注意

不要设置在电热器具的正上方,以避免人员手臂越过电热器具操作开关。如果某一电热器具额定电流超过15A,应对其所对应的电热插座采取放射式供电直接由户配电箱引来独立电源。

④如厨房内设置冰箱应对其设置专用插座,设置高度为距地0.3m。

?卫生间

目前,我国一般住宅的卫生间往往兼有浴室的功能,因此卫生间内均设有淋浴、盆浴设备。由于是严重潮湿场所,在洗浴时身体电阻降低使电击的危险大大增加,卫生间成为住宅中最容易有触电危险的地方。而不在卫生间内设置电气插座及用电器具虽然可以避免触电危险,给居民使用造成不便。因此电气设计师应在遵循更加严格的电气保护措施的同时在卫生间内适当位置设置插座,在最大安全的前提下满足人们在卫生间等潮湿场所内设置电器的要求。《民用建筑电气设计规范》规定“澡盆和淋浴盆的安全保护要求,仅限于三级及以上的旅(宾)馆、高级住宅和公寓以及商业性浴池等场所。一般旅馆和住宅的上述场所可参照有关条款,采取适当的保护措施”。

3.5.4该小区住宅的插座系统设计

该小区住宅的具体设计:

?主卧室:壁挂式空调插座1个,安装高度1.8M;五孔插座3个,安装高度0.3M。?次卧室:壁挂式空调插座1个,安装高度1.8M;五孔插座3个,安装高度0.3M。?客厅:柜式空调插座1个,安装高度0.3M;五孔插座4个,安装高度0.3M。?餐厅:五孔插座1个,安装高度0.3M。

?主卧室卫生间:带防溅盒插座1个,给热水器用,安装高度2M。

?卫生间:带防溅盒插座2个,给热水器用,安装高度2M,给洗衣机用,高度

0.3M。

?书房:壁挂式空调插座1个,安装高度1.8M;五孔插座2个,安装高度0.3M。?厨房:电热插座2个,安装高度1.4M;带防溅盒油烟机用插座1个,安装高度2M。

?阳台:带防溅盒插座1个。

某住宅小区供配电系统设计

For pers onal use only in study and research; not for commercial use 学号6 9 《工厂供电》 课程设计 (2010级本科) 题目:_某住宅小区供配电系统设计_ 学院:物理与机电工程学院 专业:电气工程及其自动化 作者姓名:甘孝田 指导教师:赵文忠职称:教授 完成日期:2012年12 月27 日

工厂供电课程设计任务书

四.需收集和阅读的资料及参考文献(指导教师推荐)

【1】刘涤尘、王明阳、吴政球?电气工程基础[M].武汉:武汉理工大学出版社.2003年【2】张学成.工矿企业供电设计指导书[M].北京:北京矿业大学出版社.1998年【3】刘介才.工厂供电简明设计手册[M].北京:机械工业出版社.1993年 【4】刘介才.实用供配电技术手册[M].北京:中国水利水电出版社.2002年 【5】刘介才.工厂供电[M].北京:机械工业出版社.1997年 【7】JGJ16-2008民用建筑电气设计规范 【8】GB50054-95低压配电设计规范 【9】GB50052-95供配电系统设计规范 【10】GB50217-2007电力工程电缆设计规范 【11】GB50060-92 3?110KV高压配电装置设计规范 指导教师签名:赵文忠 2012年12 月14 日

目录 一、设计说明 .............................................................. 1.. 1.1工程概况 ......... ... ..................................................... .1 1.2设计依据 (1) 1.3设计原则 (1) 1.4小区概况 (1) 二、小区负荷计算 .......................................................... 1.. 三、无功补偿方式 (3) 3.1无功补偿方式.......................................................... 3. 3.2无功补偿容量.......................................................... 3. 3.3并联电容器的选择及制 (4) 四、变配电所位置和型式的选择 .............................................. 4. 4.1 变配电所位置的确定 (4) 4.2变配电所的总体布置 (4) 五、主变压器台数和容量的确定 .............................................. 5. 5.1变压器主变台数的选择.......................................................... 5. 5.2变压器容量的选择 (5) 六、变配电所主接线方案的选择 .............................................. 5. 6.1变电所主接线方案的评价 (6) 七、短路电流的计算 ........................................................ 7. 7.1短路计算的意义和方法 (7) 7.2相关节点的短路计算............................................................ 7. 7.2.4 K-1点的短路电流计算 (8) 7.2.5 K-2点的短路电流计算 (8) 八、变电所低压侧一次设备的选择与校验 (9) 8.1低压母线的选择与校验 (9) 8.2低压电缆、设备的选择与校验 (10) 九、变压器保护设置 (13) 9.1变电所10kV馈线保护 (14)

居民小区供配电系统设计开题报告

华北理工大学轻工学院 本科毕业论文开题报告 题目:某小区10KV配电房设计 学部:信息科学与技术部 专业:电气工程及其自动化班级:12电气2班 姓名:董国旗 学号:201224390232 指导教师:赵伟 2015年月日

题目某小区10KV配电房设计 选题的目的及研究的意义 电力资源是支持国民经济发展不可或缺的一种宝贵能源,电能的生产、传输、储存高效、洁净,它是现代工农业生产、人们日常生活及社会各个领域中已获得了广泛应用。居民小区供配电系统是整个人们的动力源泉的命脉,它的正常运行直接影响人们的一切。现代居民小区供配电系统的主接线及运行方式都非常复杂,各种电器设备的数量和种类繁多。随着经济的快速发展、科技水平的不断进步,对电力的需求和要求也必然日益提高。 在我国城乡一体化加快,国内外倡导低碳经济的背景下。我国居民小区需求量很大,再加上居民生活水平的提高,大量现代化的家电进入普通老百姓家里,造成负荷的大大提高。而原有建筑电气国家设计标准和地方标准已经远远不能满足设计要。因此本设计试图探索适应当代小区电气设计模式。此外节能减耗是我国基本的国策之一,在充分满足,完善建筑物功能的要求前提下,减少能源消耗,提高能源利用率也是此设计探索之处。 进行该课题的设计,主要包括居民小区供配电系统的设计和理论与实践的应用。此次设计前期包括了居民的电力负荷计算,节约电能与无功补偿的基本方法,电气主接线方案的设计,变压器的选择,短路电流的计算,了解电器设备的原理、性能及选择方法,涵盖高低压电器设备的选择,一次二次设备的校验,及其回路的继电保护的配置,自动装置的配置等。后期进行电气设备防雷与接地的设计,施工设计的完善工作,进行图纸的规划。其中运用了居民小区供配系统设计和安全、经济运行的基本理论,以及工程实用的设计计算方法与运行维护的基本知识。 通过论文设计,加深对工厂居民小区供电的认识,能独立设计电气主接线,会选择和校验电气设备。 二、综述与本课题相关领域的研究现状、发展趋势、研究方法及应用领域等 居民小区的供电系统就是将电力系统的电能降压再分配电能到各个住户中间去,它由小区降压变电所,高压配电线路,低压配电线路及用电设备组成。总降压变电所及配电系统设计,是根据各个住户的负荷数量和性质,以及负荷布局,结合国家供电情况.解决对各个住户的安全可靠,经济技术的分配电能问题。 供配电技术,就是研究电力的供应及分配的问题。电力,是现代工业生产、民用住宅、及企事业单位的主要能源和动力,是现代文明的物质技术基础。没有电力,就没有国民经济的现代化。现代社会的信息化和网络化,都是建立在电气化的基础之上的。因此,电力供应如果突然中断,则将对这些用电部门造成严重的和深远的影响。故,作好供配电工作,对于保证正常的工作、学习、生活将有十分重要的意义。 供配电工作要很好的为用电部门及整个国民经济服务,必须达到以下的基本要求: (1)安全——在电力的供应、分配及使用中,不发生人身事故和设备事故。 (2)可靠——应满足电力用户对供电可靠性和连续性的要求。 (3)优质——应满足电力用户对电压质量和频率质量的要求。 (4)经济——应使供配电系统投资少,运行费用低,并尽可能的节约电能和减少有色金属消耗量。 供配电系统的发展趋势 1.供配电系统的规模越来越大 2.功率密度也越来越高 3.供配电系统可靠性要求越来越高 4.供配电系统的绿色节能 5.配电自动化 随着科技的进步和社会的发展,居民小区供配电系统运行和维护的安全技术要求得到了相关部门越来越广泛的重视。

某小区供配电系统设计

南阳理工学院本科生毕业设计(论文) 学院(系):电子与电气工程学院 专业:电气工程及其自动化 学生: 指导教师: 完成日期 2014 年 5 月

南阳理工学院本科生毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 总计: 36 页 表格: 10 个 插图: 9 幅

南阳理工学院本科毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 学院:电子与电气工程学院 专业:电气工程及其自动化 学生姓名: 学号: 指导教师(职称): 评阅教师: 完成日期: 南阳理工学院 Nanyang Institute of Technology

某小区供配电系统设计 [摘要]住宅小区供配电系统的稳定运行直接影响着人们的日常生活及秩序。因此研究小区供配电系统如何更好的实现安全、可靠、经济运行具有现实的意义。本课题初步对住宅小区的供配电系统进行设计,并根据国家相关标准对所设计的内容进行规范化。分析小区的原始数据和供电特点,对小区各类负荷进行计算;通过计算负荷选择变压器的容量和数目完成变电所的设计;合理选择电气主接线方式;根据短路电流选择合适的电力电缆;确定建筑物防雷等级,做好小区的防雷接地保护。设计过程中不仅要保证供电的质量和安全性,还应尽量满足供电的经济性,节省能源和材料。 [关键词]计算负荷;短路电流;变压器;供配电设计;防雷接地 Design for the Power Supply and Distribution System of a Residence Community Electrical Engineering and Automation Specialty MA Jun-yao Abstract: Residence community for safe and reliable operation of the distribution system directly affects people's daily lives.This project is initially designed for the power supply and distribution system of the residence community. And also the design is normalized in accordance with the relevant national regulations and standards. So the power supply and distribution system in residence community district how to realize the safe, reliable and economic operation has realistic meaning. Analysis the raw data for the residence community and load calculation of the residence community. Based on the calculated load the measures of power supply and distribution of the residence community is designed. It includes the electric main wiring design, transformer and distribution substation design. Meanwhile the appropriate electric power cable are selected according to the short-circuit current. And the protection design about grounding for lightning is also essential. Not only must the quality and safety of power supply be ensured, but also the economical power supply, energy-saving and material-saving should be met as much as possible. Key words:Load calculation; Short-circuit current; Transformer; Power supply and distribution design; Grounding for lightning 目录

住宅小区供配电系统设计

2012.06 167 建筑规划与设计 摘要:随着技术的进步,人们对城市配电网络供电可靠性要求越来越高,因此要求住宅小区的配电系统设计接线方式简单灵活、运行可靠。住宅小区的供配电设计应坚持“以人为本” 的原则,在确保安全可靠的大前提下,根据工程特点、建设规模、当地气候条件、地区供电条件及经济发展状况等诸多因素,兼顾技术先进性和经济合理性,综合确定小区的供配电方案。要正确处理近期建设和远期发展的关系,以近期为主,适当考虑发展的可能。 关键词:生活住宅小区;中压配电系统;低压配电系统1 前言 社会经济的快速发展使人们对居住条件的要求越来越高,各式各样的住宅小区层出不穷,在了解了小区的位置、环境、交通及户型等外观后,人们开始更加注重供配电等内在条件的质量。因此,安全可靠、技术先进、经济合理的小区供配电系统显得日趋重要。 2 供电电源 住宅小区一般应由10kV电源供电。住宅小区中的住宅楼和其他公用设施的用电负荷分级应符合现行的《建筑设计防火规范》和《高层民用建筑设计防火规范》等的规定。当住宅小区内仅有三级负荷时,供电电源可取自附近的110~35/10kV区域变电所的若干10kV供电回路,当住宅小区内同时具有一、二级负荷时,则应根据区域变电所的电源路数和变压器台数确定供电电源,若区域变电所的110~35kV电源仅为一路,则小区的备用电源应从另外的区域变电所引来。当住宅小区内的一、二级负荷较小,且设置自备电源比从城市电网取得第二电源更经济合理时,可设置自备电源。对规模较大的小区,当区域变电所的10kV出线走廊受到限制或配电装置间隔不足且无扩建余地时,宜在小区内设置10kV开闭所(开关站)。开闭所宜与10kV变电站联体建设。总之,住宅小区的供电方式必须与当地供电部门协商确定。 3 配变设置3.1 负荷计算 以前,住宅小区用电负荷的计算主要有单位面积法和需要系数法等,各地的计算标准千差万别。新的《住宅设计规范》出台后,对各类住宅的用电负荷标准、电表规格、进户线截面都规定了下限值。很多省、市、自治区也根据此规范并结合本地区情况,出台了地方住宅设计标准,对上述用电指标均作了等同或高于《住宅设计规范》的规定。据此,一般采用单位指标法进行负荷计算。 即Pc=ΣKx×Pe×N式中Pe——单位用电指标,如:4kW/户(不同户型的用电指标不同),可根据《住宅设计规范》或各地区的地方住宅设计标准的规定选取。 kWN——单位数量,即户数(对应不同面积户型的户数)Kx——需要系数,《住宅设计规范》对其取值未作规定,有些地方标准有规定,但是差别较大。如果地方标准无规定,可参照《全国民用建筑工程设计技术措施-节能专篇/电气》的推荐值,表2.2.4-1的规定取,具体按接三相配电计算时所连接的基本户数选定:9户以下取1;12户取0.95等。 对小区内的商业、办公等配套公建及路灯用电负荷需用其他方法单独计算。 3.2 配变选型 住宅小区配电的视在功率 S=Σ Pc/ 式中——功率因数,由于住宅以照明负荷和家用电器为主,一般取0.8—0.9(参见《住宅设计规范》条文说明6.5.1条)。当小区内有电梯、水泵、中央空调等动力设备时,其负荷应单独计算后再汇总。消防用电负荷一般不计入S——视在功率,kVA在计算设置变压器的容量时,应考虑变压器的经济负荷系数和功率因数补偿效果。变压器的经济负荷系数在0.6—0.75之间,变压器的负荷率应不大于0.85。10kV供电的功率因数应不低于0.9,否则应进行无功补偿。 由于住宅楼以单相负荷为主,容易造成三相不平衡负荷超出变压器每相额定功率15%的情况,因此,小区内应选用接线组别为D,yn11的变压器。 住宅小区用电负荷季节差别甚至昼夜差别都很大。所以宜选用空载损耗低的节能型变压器,如S9系列或非晶合金变压器。 小区内设置的变电站的型式和数量必须根据小区规模、建筑类别(别墅、多层、高层等)及配电总容量并结合当地电业部门的供电系统规划来确定。 目前住宅小区内设置的变电站的类型有多种:独立型、户内型和分散型。独立型变电站一般用于规模较小或负荷比较集中的住宅小区;分散型变电站一般用于规模较大、负荷分布比较分散的住宅小区,大多采用箱体移动式结构(即箱变),且一般设置开闭所(开关站);户内型变电站一般用于高层且单体面积较大的住宅建筑。 供电变压器的台数及单台容量可按以下原则确定:对于独立型或户内型变电站,配电变压器的安装台数宜为两台,单台变压器的容量不宜超过1000kVA;对于分散型变电站,根据小容量多布点的原则,对以多层住宅为主的小区单台变压器的容量不宜超过630kVA;对别墅区单台变压器的容量不宜超过315kVA。 3.3 配变选址 住宅小区内变电站的设置应遵循以下原则: (1)尽量接近小区负荷中心且进出线方便,以降低电能损耗、提高供电质量、节省设备材料。 (2)考虑合理的负荷分配及适宜的供电半径。单台变压器的容量一般不超过上节所述;中压供电半径:负荷密集地区不超过2km,其他地区应不超过3kin;380/220V配电线路的配电范围一般不宜超过250m。 (3)当小区内有高层、多层或别墅等多种类型住宅时,宜按不同类型分别划分供电范围。 (4)当小区规模较大时,如果分期开发,应尽量按分期片区划分供电范围。 (5)一般按小区内干道的自然分隔划分供电分区,避免大量管线穿越马路、交叉重叠。 (6)与住宅楼(尤其是住户的南卧室)保持一定距离,一般不低于6m (现行规范无明确规定),以满足防火、防噪声、防电磁辐射等要求。 (7)远离通信机房、微机机房和消防控制室等有防电磁干扰要求的房间。 4 低压配电 低压配电系统,应保障安全、配电可靠、经济合理、维护方 住宅小区供配电系统设计之我见 陈 勇 中国美术学院风景建筑设计研究院 下转169页

住宅小区的配电系统相关的设计

住宅社區的配電系統相關的設計 1居住建築用電負荷 居住建築用電負荷分為兩類:一類是住宅用電負荷,含住宅照明和家用電器;另一類是公共區用電負荷,含公共區照明和動力兩部分負荷。 1.1戶內照明負荷 住宅各種房間的不同使用功能及人員活動的頻率決定了光源的種類、燈具的形式及對光線變化的不同要求。反映在電氣設計上便是照度要求。 (1)確定建築標準。 根據國家住宅與居住環境工程中心在2002年編寫的《健康住宅技術設計要點2002年修訂版》,再根據建設住宅的平均建築面積參數,以建築面積100m2為例。 (2)確定照度標準:《建築照明設計標準》(GB50034-2004)對居住建築內照度標準及照明功率密度值做了規定(見表1)。 首先我們算出居室內燈具的光通量,然後通過光通量可以查表得出光源容量,將各居室的容量相加,便可以得出一戶的總照明燈具容量。計算過程不一一羅列,最後計算的結果是居室內照明容量約為400W. 1.2家用電器負荷 家用電器是住宅內負荷的主要因素。家用電器負荷的確定應考慮

兩個主要因素:第一,採暖、炊事及洗浴能源方式。當大範圍採用電採暖、單元式集中空調、電熱水器和電灶,住宅內用電負荷應根據具體情況進行計算;第二,家用電器的普及率。家用電器普及率是標誌著某類家用電器進入家庭的程度,當前的家用電器普及率可以反映出居民的生活水準,決定了居民用電負荷。 1.3公共區照明負荷 公共區照明含有幾部分:一是經常有人員來往的地方,如樓梯間、電梯前室、走道等;二是如人防、水泵房、設備層等公共設施所在場所;三是樓內的疏散照明及事故照明。場所不同,所選用燈具、光源不同,燈具控制方式不同,因此不同的公共區照明會有不同的需用係數。 1.4公共區動力負荷 一是高層住宅樓內的電梯負荷(受建築物及電梯本身的參數,以及運行條件影響);二是樓內的給、排水及通風設備負荷(排汙泵、生活水泵等);三是住宅供暖設備負荷。 2住宅社區負荷計算 住宅社區負荷計算在不同的設計階段採用不同的計算方法:在方案設計階段多採用單位面積功率法,在初步設計和施工圖設計階段多採用需用係數法。 (1)1999年8月,北京供電局下發了《關於城鎮居民新建住宅實施一戶一表的技術方案》(簡稱《方案》),即(99)首規辦秘字第319號。對住宅的"用電負荷標準及電度錶規格"(表2)做

住宅小区供配电系统设计

XX学院 毕业论文(设计) 住宅小区供配电系统设计Residential quarters for the distribution design 系别物理与电子信息工程系 专业电气工程及其自动化 学号 XX 姓名 XX 指导教师 XX 2009年 5月10日

摘要 要提高高层建筑配电系统的可靠性,要正确选择各类配电设备的容量,就必须科学、合理的进行负荷计算。本文对符合计算中的相关问题进行了分析和探讨,就重要设备的容量选择做了较为详细的论述,提出了一些进一步提高配电系统可靠性的措施,并结合工程实例进行负荷计算,计算结果证明本文所述方法是正确合理,可在实际中应用。高层建筑比一般建筑遭受雷击的概率要大得多,而一旦遭受雷击,损失将非常严重。另外,普通建筑物防雷系统不但不能保护高层建筑物内的电子设备与计算机系统,反而可能会引入雷电。因此,高层建筑的防雷保护就越显重要,相应地对防雷保护提出了更高的要求。本文对于高层建筑物的防雷保护措施做了较为仔细的分析。 关键词:配电系统;负荷计算;防雷设计;照明 Abstract In order to improve the reliability of power distribution system of high building,choice capacity of power distribution debice rightly,it is necessary tocalculate charge rightly,the author analyacs and investigatcs relative question with charge calculation,expatiates particularly capacity choice of important equipment,puts forward these measure being used to improve the reliability of power distribution system,makes charge calculation combination to project example,the result shows that these means is right and reasonable,these means can guide project practice. High buiding is easy suffered from lightning stroke,in case being suffered lightning stroke,it should bring huge losing,lightning protection system of common building can not protect electronic device,on the contrary,it may intoduce lifhtning therefore high building’s lightning protection is more important.The author analyses and research these question of over voltage and of lifhtning stroke,puts forward these means of lightning protescition of in high building. Keywords: power distribution system ;load calculation synthetic; lightning protection;Illumination

某学校供配电系统设计方案

第1章 绪论 供配电技术,就是研究电力的供应及分配的问题。电力,是现代工业生产、民用住宅、及企事业单位的主要能源和动力,是现代文明的物质技术基础。没有电力,就没有国民经济的现代化。现代社会的信息化和网络化,都是建立在电气化的基础之上的。因此,电力供应如果突然中断,则将对这些用电部门造成严重的和深远的影响。故,作好供配电工作,对于保证正常的工作、学习、生活将有十分重要的意义。 供配电工作要很好的为用电部门及整个国民经济服务,必须达到以下的基本要求: (1) 安全——在电力的供应、分配及使用中,不发生人身事故和设备事故。 (2) 可靠——应满足电力用户对供电可靠性和连续性的要求。 (3) 优质——应满足电力用户对电压质量和频率质量的要求。 (4) 经济——应使供配电系统投资少,运行费用低,并尽可能的节约电能和减少有 色金属消耗量。 另外,在供配电工作中,还应合理的处理局部和全局,当前与长远的关系,即要照顾局部和当前利益,又要有全局观点,能照顾大局,适应发展。 我们这次的毕业设计的论文题目是:某高校供配电工程总体规划方案设计;作为高校,随着本科教育工作的推进和未来几年的继续扩招,对学校的基础设施建设特别是电力设施将提出相当大的挑战。因此,我们做供配电设计工作,要作到未雨绸缪。为未来发展提供足够的空间:这主要表现在电力变压器及一些相当重要的配电线路上,应力求在满足现有需求的基础上从大选择,以避免一台变压器或一组变压器刚服役不到几年又因为容量问题而台而光荣下岗的情况的发生。 总之一句话:定位现实,着眼未来;以发展的眼光来设计此课题。 第2章 供配电系统设计的规范要点 供配电系统设计应贯彻执行国家的经济技术指标,做到保障人身安全,供电可靠,技术先进和经济合理。在设计中,必须从全局出发,统筹兼顾,按负荷性质、用电容量、工程特点,以及地区供电特点,合理确定设计方案。还应注意近远期结合,以近期为主。设计中尽量采用符合国家现行有关标准的效率高、能耗低、性能先进的电气产品。 2.1 负荷分级及供电要求 电力负荷应根据对供电可靠性的要求及中断供电在政治、经济上所造成的损失及影响的程度分为一级、二级、三级负荷。独立于正常电源的发电机组,供电网络中独立于正常的专用馈电线路,以及蓄电池和干电池可作为应急电源。二级负荷的供电系统,应由两线路供电。必要时采用不间断电源(UPS )。 2.1.1 一级负荷 一级负荷为中断供电将造成人身伤亡者;或将在政治上,经济上造成重大损失者;或中断将影响有重大政治经济意义的用电单位的正常工作者。 就学校供配电这一块来讲,我校现没有一级用电负荷。 2.1.2 二级负荷 二级负荷为中断供电将在政治上,经济上产生较大损失的负荷,如主要设备损坏,大量产品报废等;或中断供电将影响重要的用电单位正常的工作负荷,如交通枢纽、通信枢纽等;或中断供电将造成秩序混乱的负荷等。 在本次毕业设计中:我校现有的二级负荷有:综合楼(南)和综合教学楼(北)的消防电梯、消防水泵、应急照明,银行用电设备,专家楼用电设备,医院急诊室用电设备,

毕业设计方案(住宅小区供配电设计方案)

摘要 本设计主要阐述了现代化小区各系统电气设计的设计依据、原则和方法及设计选择的结论。本设计共主要包括强电部分设计部分设计及安防部分设计。 强电部分主要内容包括:低压配电系统、照明系统及防雷接地系统的设计,其中包括负荷计算、照度计算等。 本小区电气设计作为毕业设计,其目的是通过切身实践,综合运用所学知识,理论联系实际,锻炼独立分析和解决建筑电气设计问题的能力,为即将面临的工作奠定坚实的基础。 关键词:配电系统负荷防雷接地 目录 引言1 一设计简况2 二配电系统2 <一)设计要求2 <二)低压配电系统线路的选择2 <三)设备安装4 <四)电能计量方式选择5

三照明系统5 <一)照明系统的概述5 <二)照度方式6 <三)光源和灯具7 <四)照度计算8 <五)配电箱布置12 <六)负荷计算<需要系数法)12 <七)设备选型15 四防雷接地系统设计17 <一)建筑物防雷等级确定17 <二)防雷内容与设计方案20 总结23 致谢24 参考文献25

引言 本次设计的主要针对是现代化住宅小区楼内供配电系统设计。通过具体的实例工程设计,初步掌握高层建筑配电系统设计的基本方法,更好的将理论和实践相结合,将大学三年来所学的课程及知识应用到自己的专业中去,也为将来的工作打下良好的基础。 本工程为11层的民用普通高层建筑,为二类高层建筑,按三级负荷供电,三类防雷建筑物进行电气系统设计。在本设计中,要求完成对住宅小区楼内配电系统设计,主要包括低压供配电系统、照明系统、插座系统、防雷与接地系统。论文针对民用高层建筑电气的设计和使用需要,,侧重于电气基本理论和基本知识。设计中,总体按照民用建筑设计规范来建立设计的整体思路,并完成配电系统的负荷计算、设备选型、系统构成、照度计算等。 一设计简况 本次设计的主要针对是现代化住宅小区楼内供配电系统设计。通过具体的实例工程设计,初步掌握高层建筑配电系统设计的基本方法,更好的将理论和实践相结合,将大学三年来所学的课程及知识应用到自己的专业中去,也为将来的工作打下良好的基础。 本工程为11层的民用普通高层建筑,为二类高层建筑,按三级负荷供电,三类防雷建筑物进行电气系统设计。在本设计中,要求完成对住宅小区楼内配电系统设计,主要包括低压供配电系统、照明系统、插座系统、防雷与接地系统。论文针对民用高层建筑电气

大酒店供配电系统设计方案

课程设计说明书课程设计题目实验楼电气设计 学院专业班级 学生姓名学号 指导教师黄骏 成绩

设计日期 2011.12.5~2011.12.16 目录 第一章工程概述 2 第二章供配电系统设计 4 第一节供配电系统设计任务、内容及要求 (4) 第二节负荷计算 (6) 第三节无功功率补偿 (13) 第四节高低压配电系统设计 (16) 第五节短路电流计算 (19) 第六节设备选择 (25) 第三章照明系统设计26 第一节酒店照明设计的特点 (27) 第二节照度计算 (35) 第三节照明配电系统 (37) 第四节灯具选择 (39) 第五节房间插座布置 (40) 第六节标志照明 (40) 第四章防雷系统设计错误!未定义书签。 第五章消防系统设计 (44) 第一节系统设计 (45) 第二节本工程消防系统 (48) 参考文献错误!未定义书签。 第一章工程概述 本次设计的对象——“红藤大酒店”,它是集住宿、餐饮、娱乐、为一

体的大型建筑物,建筑面积约为17000平方米,地上13层、地下1层。其中一层有酒店大厅、服务台、休息厅、舞厅、美发厅、商场、KTV包房、健身房、商务中心、快餐厅、厨房、消防中心等设施;二层是各类餐厅酒吧、厨房等设施;三层有多功能厅、各种会议室、休息厅等;四到十一层为客房其中有套房、标准间;十二层是机房;地下一层有配电室、洗衣房、热交换间、水泵房、消防水池、风机房;另外还有一个游泳馆。屋顶有卫星接收室、风机房、水箱间、电梯机房等。 本次设计的主要任务是有关酒店的供配电系统、电气照明系统、消防系统及防雷接地系统的设计。 作为一个现代化的大酒店在电气部分中至少应该达到以下要求:

某小区供配电的设计开题报告

重庆大学 学生毕业设计开题报告 一、课题的目的及意义(含国内外的研究现状分析): 1.课题目的: 本设计主要阐述了现代化小区各系统供配电电设计的设计依据、原则和方法及设计选择的结论。本设计共主要包括强电部分设计部分设计及安防部分设计。 强电部分主要内容包括:低压配电系统、照明系统及防雷接地系统的设计,其中包括负荷计算、照度计算等。 本小区电气设计作为毕业设计,其目的是通过切身实践,综合运用所学知识,理论联系实际,锻炼独立分析和解决建筑电气设计问题的能力,为即将面临的工作奠定坚实的基础。 2.课题意义: 电能是人们生活中不可缺少的能源和生活工具,它的影响力和对社会的帮助可以说超过了任何媒介。当然如果只有电能这种单纯的物质,电能一样不能为人民服务。所以,必须要有专门的专业人员对其进行分配与传输,这样才能使电能造福于人,服务于人民群众。当前,电能的供配电系统的种类与形式纷繁复杂,所以选择一种适合的系统形式不是太容易。如果选择的不合适 可能会造成财产的损失、设备的浪费,有时甚至造成人类的伤亡。所以,选择一种适合的系统十分重要,不容马虎。 本课题就是住宅小区的供配电系统的设计,是一个典型的案例,设计内容主要包含以下几个方面的内容,住宅小区的负荷计算,小区变配电所的位置选取,小区变配电所内主变压器太熟与容量的选择,防雷,接地等内容。其中的每部分内容都十分重要每一部分都会影响住宅小区的整体效果与安全性能。 供配电系统的发展也是科技进步的表现,反过来一样,供配电系统越是需要发展就越需要科技的进步。当前,中国供配电事业飞速发展,这是人民需求增多的映射。当然,满足人民的各种需求也是供配电部门与人员的责任与义务。目前智能供配电系统也层出不穷,反映出进步与革新。总之,建立不仅满足要求同时考虑到未来发展需要的供配电系统是我们不尽的追求,需要我们的不懈努力。

高层住宅楼供配电

毕业设计 高层住宅楼供配电系统的设计 姓名: 学号: 班级: 11电气1 专业:电气工程及其自动化 所在系:自动化工程系 指导教师:

高层住宅楼供配电系统的设计 摘要 我国的城市建设过程中,住宅向着高层化趋势发展。高层住宅楼,因其为住户提供的安全、舒适、高效、节能的居住环境,受到了越来越多人的青睐,也成为现代人主要的居住方式。与此同时,高质量的高层住宅楼供配电系统的设计就显得尤为重要。在电气设计时既要考虑用电负荷日益增长的需要,又要满足供电的可靠性及安全性的要求。 本课题以高层建筑的供配电系统为研究对象。为了达到用户能够安全、可靠、高效用电的目的,我们对高层建筑的供配电系统整体进行设计。其中包括对建筑负荷的计算,选择恰当地供电方式;进行短路电流的计算,选择合适的导线及低压电器产品;对室照明进行设计;对防雷接地的设计等。同时为了提高设计质量及缩短设计周期,本课题采用功能强大的建筑电气软件CAD来设计供配电系统的电路图。 关键词:电气设计;安全性;负荷计算;防雷接地;软件AutoCAD

The Design of High-rise Residential Building Power Supply and Distribution System ABSTRACT In the process of urban construction in our country, the housing development trend towards upwards. High-rise residential buildings, because of its for residents to provide safe, comfortable, efficient and energy saving living environment, got the favour of more and more people, modern has become the main way of living. At the same time, the high quality of high-rise residential building design of power supply and distribution system is particularly important. In the electrical design should not only consider the increasing needs of the power load, and to meet the requirements of the reliability and security of the power supply. This topic in power supply system of high-rise building as the research object. In order to achieve the user to the purpose of safe, reliable and efficient utilization, our power supply system of high-rise building the overall design. Including the building load calculation, choose proper power supply way; For the calculation of short-circuit current, select the appropriate conductor and low-voltage electrical products; For indoor lighting design; The design of lightning protection grounding, etc. At the same time in order to improve the design quality and shorten the design cycle, this subject adopts powerful building electrical software AutoCAD to design the circuit diagram of power supply and distribution system. Key Words:Electrical Design ;security;Load calculation;Lightning protection and grounding;Software AutoCAD

楼宇供配电系统设计讲解

目录 一、高层建筑供配电系统概述 (1) 二、供配电设计 (2) (一)设计建筑概况 (2) (二)设计内容简介 (2) (三)负荷计算 (3) (四)高压配电系统设计 (8) 1概况 (8) 2设备选择 (9) (五)低压配电系统设计 (10) 1概况 (10) 2设备选择 (11) 三、照明设计 (13) 四、导线计算与线路敷设 (13) (一)导线计算 (13) (二)线路敷设 (16) (三)线路安装 (17) 五、设计依据 (18)

一、高层建筑供配电系统概述 (一)高层建筑电气的特点 1.用电设备种类多 从前,设备占整个投资的10%,现在设备会占整个投资的40%,比如地王60%、宏昌50%;设备功能亦不断增强。 2.用电量大,即负载密度大 由于照明及空调负荷多,电梯等运输设备多,给排水设备多,所以用电量特别大 负载密度在60W/MM,高的有200/MM。此数字是按照建筑面积来计算的。 3.供电可靠性要求高 现代高层建筑均是采用两路独立的10kV电源同时供电。一般高压采用单母线分段,自动切换,互为备用。另外,还须装设应急备用柴油发电机组,要求在15秒钟内自动恢复供电,保证事故照明、电脑设备、消防设备、电梯等设备的事故用电。应急备用发电机组:过去大多是采用柴油发电机组做应急备用电源的。近年国外高层建筑已开始采用燃汽轮发电机。这种发电机具有体积小、重量轻、反应速度快,故障率低等优点。 应急备用发电机组必须是快速自起动的。按国外规定,应能在15s内恢复供电。从可靠性出发最好选用两台,自动并车。容量较小时也可选用一台。 4.电气系统复杂,电气线路多自动化程度高,电气用房多 (二)高层建筑供配电系统的发展趋势: 随着科学技术的飞速发展以及人民生活水平的不断提高,高层建筑正向着自动化、

某小区供配电系统设计

, 南阳理工学院 本科生毕业设计(论文)( @ 学院(系):电子与电气工程学院 专业:电气工程及其自动化 学生: 指导教师: : 完成日期 2014 年 5 月

$

南阳理工学院本科生毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 总计: 36 页 表格: 10 个 插图: 9 幅

南阳理工学院本科毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 学院:电子与电气工程学院 专业:电气工程及其自动化 学生姓名: 学号: 指导教师(职称): 评阅教师: 完成日期: 南阳理工学院 Nanyang Institute of Technology

某小区供配电系统设计 [摘要]住宅小区供配电系统的稳定运行直接影响着人们的日常生活及秩序。因此研究小区供配电系统如何更好的实现安全、可靠、经济运行具有现实的意义。本课题初步对住宅小区的供配电系统进行设计,并根据国家相关标准对所设计的内容进行规范化。分析小区的原始数据和供电特点,对小区各类负荷进行计算;通过计算负荷选择变压器的容量和数目完成变电所的设计;合理选择电气主接线方式;根据短路电流选择合适的电力电缆;确定建筑物防雷等级,做好小区的防雷接地保护。设计过程中不仅要保证供电的质量和安全性,还应尽量满足供电的经济性,节省能源和材料。 [关键词]计算负荷;短路电流;变压器;供配电设计;防雷接地 Design for the Power Supply and Distribution System of a Residence Community Electrical Engineering and Automation Specialty MA Jun-yao Abstract: Residence community for safe and reliable operation of the distribution system directly affects people's daily project is initially designed for the power supply and distribution system of the residence community. And also the design is normalized in accordance with the relevant national regulations and standards. So the power supply and distribution system in residence community district how to realize the safe, reliable and economic operation has realistic meaning. Analysis the raw data for the residence community and load calculation of the residence community. Based on the calculated load the measures of power supply and distribution of the residence community is designed. It includes the electric main wiring design, transformer and distribution substation design. Meanwhile the appropriate electric power cable are selected according to the short-circuit current. And the protection design about grounding for lightning is also essential. Not only must the quality and safety of power supply be ensured, but also the economical power supply, energy-saving and material-saving should be met as much as possible. Key words: Load calculation; Short-circuit current; Transformer; Power supply and distribution design; Grounding for lightning